SRNE Solar CoLtd: HEBP48120U240-Pro {208V} outputs 10,397 W AC at 208 V, commercial single-phase (50.0 A continuous, 70 A OCPD), ranking #2,199 of 2,343 CEC inverters at 95.4% efficiency with a 275-450 V MPPT window and 450 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 10,397 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 70 A (4 AWG Cu)
- CEC Efficiency
- 95.4%
How Does SRNE Solar CoLtd: HEBP48120U240-Pro {208V} Compare Against Peer CEC Listings?
Breaker sizing (70 A), 4 AWG Cu wire rules, and DC input limits for SRNE Solar CoLtd: HEBP48120U240-Pro {208V}.
For NEC 705.12 solar interconnection, SRNE Solar CoLtd: HEBP48120U240-Pro {208V} outputs 50.0 A continuous AC at 208 V, commercial single-phase and needs a 70 A backfeed breaker on 4 AWG Cu (75 C). Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Conversion efficiency scores 95.4% (#2,199 of 2,343, -1.42 pts vs overall CEC median).
Where Does SRNE Solar CoLtd: HEBP48120U240-Pro {208V} Fall Across Listed CEC Models?
Output power comparison showing where SRNE Solar CoLtd: HEBP48120U240-Pro {208V} sits among all 2,343 CEC-listed grid-support inverters. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
What Dataset Percentiles Define SRNE Solar CoLtd: HEBP48120U240-Pro {208V}?
Relative ranking of SRNE Solar CoLtd: HEBP48120U240-Pro {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for SRNE Solar CoLtd: HEBP48120U240-Pro {208V}?
Snapshot of SRNE Solar CoLtd: HEBP48120U240-Pro {208V} efficiency rank (#2,199), OCPD breaker size, MPPT span, and busbar verdict.
95.4% CEC Weighted Efficiency
-1.01 pts vs the 96.41% 208 V median; overall power rank #823 (10,397 W, top 35.2%; higher than 64.8% of peers).
70 A Required Backfeed OCPD
125% x 50.0 A = 62.5 A -> 70 A standard OCPD using 4 AWG Cu (75 C).
275 V - 450 V (Max 450 V DC)
Tracking span of 175.0 V; active in CEC directory (hybrid battery-capable inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 10397.2W / 208 V -> 50.0 A | Breaker >= 1.25 * 50.0 = 62.5 A -> 70 A
CEC Inverters.csv for SRNE Solar CoLtd: HEBP48120U240-Pro {208V}: Paco=10397.2 W, Vac=208 V, Vdcmax=450.0 V, Eff=95.4%.
Result: Min 70 A breaker & 4 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for SRNE Solar CoLtd: HEBP48120U240-Pro {208V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SRNE Solar CoLtd: HEBP48120U240-Pro {208V}. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 10,397 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 450 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 275 V - 450 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 30.0642 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 95.4% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to SRNE Solar CoLtd: HEBP48120U240-Pro {208V} (208 V, commercial single-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for SRNE Solar CoLtd: HEBP48120U240-Pro {208V} at 208 V, commercial single-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 70 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (208V) | 80 A | 70 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 70 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 70 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 70 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With SRNE Solar CoLtd: HEBP48120U240-Pro {208V}?
Minimum and maximum series solar module strings fitting SRNE Solar CoLtd: HEBP48120U240-Pro {208V} MPPT and 450 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 7 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 9 to 10 panels | 4.4 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 8 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 10 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to SRNE Solar CoLtd: HEBP48120U240-Pro {208V}?
Peer 208 V, commercial single-phase CEC inverters near 10,397 W AC output such as EG4 Electronics LLC: 18KPV-12LV {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| EG4 Electronics LLC: 18KPV-12LV {208V} EG4 Electronics LLC |
10,499 W | +102 W | 208.0 V | 480.0 V | 96.07% |
| Delta Electronics: S12_BDI {208V} Delta Electronics |
10,057 W | -340 W | 208.0 V | 480.0 V | 96.7% |
| Altenergy Power System Inc: ELS-114 {208V} Altenergy Power System Inc |
10,011 W | -386 W | 208.0 V | 60.0 V | 92.83% |
| Chint Power Systems America: CPS ECH96KTL/US {208V} Chint Power Systems America |
9,550 W | -847 W | 208.0 V | 480.0 V | 96.73% |
What Are the Interconnection Limits and Best-Fit Uses for SRNE Solar CoLtd: HEBP48120U240-Pro {208V}?
Check SRNE Solar CoLtd: HEBP48120U240-Pro {208V} (10,397 W AC, 70 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 450 V DC on SRNE Solar CoLtd: HEBP48120U240-Pro {208V}.
SRNE Solar CoLtd: HEBP48120U240-Pro {208V} Panel & Wire Spec
Size 75 C copper conductors at 4 AWG Cu on a 70 A OCPD breaker (50.0 A continuous).
Alternative Inverter Comparison
Compare efficiency (95.4%) and MPPT window (275-450 V) directly against EG4 Electronics LLC: 18KPV-12LV {208V} (10,499 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SRNE Solar CoLtd: HEBP48120U240-Pro {208V} by SRNE Solar CoLtd covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does SRNE Solar CoLtd: HEBP48120U240-Pro {208V} require?
At 10,397 W continuous AC (208 V, commercial single-phase), continuous current is 50.0 A; 125% NEC 690.8/705.12 sizing requires a 70 A breaker and 4 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does SRNE Solar CoLtd: HEBP48120U240-Pro {208V} require?
At 10,397 W AC and 208 V, commercial single-phase, continuous line current is 50.0 A, requiring a 70 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does SRNE Solar CoLtd: HEBP48120U240-Pro {208V} compare to EG4 Electronics LLC: 18KPV-12LV {208V}?
SRNE Solar CoLtd: HEBP48120U240-Pro {208V} delivers 10,397 W AC at 95.4% CEC efficiency with a 450 V DC ceiling, while EG4 Electronics LLC: 18KPV-12LV {208V} outputs 10,499 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)