Skip to main content
WireAndSun
Calculators
CEC Grid-Support Inverter

Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} — CEC Inverter Specifications

Manufacturer: Shenzhen Growatt New Energy Co Ltd Registry: CEC Verified Engineering Specification

Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} outputs 4,050 W AC at 240 V (16.9 A continuous, 25 A OCPD), ranking #1,107 of 2,343 CEC inverters at 96.93% efficiency with a 100-550 V MPPT window and 550 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
4,050 W
AC Voltage
240 V
Min PV Breaker
25 A (10 AWG Cu)
CEC Efficiency
96.93%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} Compare Against Peer CEC Listings?

CEC efficiency rank (#1,107), 100-550 V MPPT tracking, and panel fit for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}.

Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} from Shenzhen Growatt New Energy Co Ltd outputs 16.9 A continuous AC at 240 V (4,050 W AC, rank #1,622). Paired with 10 AWG Cu conductors and a 25 A OCPD, its 96.93% CEC efficiency compares closely with ABB: PVI-42-OUTD-S-US-A {240V} (4,200 W). Keep NEC 690.7 winter string Voc below 550 V DC.

Where Does Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} Fall Across Listed CEC Models?

CEC inverter wattage histogram highlighting Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} at 4,050 W continuous AC output.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} (4,050 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACShenzhen Growatt N: 4,050 W

What Dataset Percentiles Define Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?

Dataset percentiles comparing Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} against 2,343 certified grid-support inverters nationwide.

Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} Technical ThresholdsPercentile comparison for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output4,050 WCEC Efficiency96.93%Backfeed Breaker25 A

What Do the Dataset Ranks Show for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?

Engineering highlights for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} covering efficiency, 10 AWG Cu feeder, and panel compatibility.

Eff #1,107 / 2,343

96.93% CEC Weighted Efficiency

+0.25 pts vs the 96.68% 240 V median; overall power rank #1,622 (4,050 W, below CEC median; higher than 30.8% of peers).

NEC 705.12 Check

25 A Required Backfeed OCPD

125% x 16.9 A = 21.1 A -> 25 A standard OCPD using 10 AWG Cu (75 C).

MPPT Window

100 V - 550 V (Max 550 V DC)

Tracking span of 450.0 V; listed since 2019-01-15 (grid-tied PV inverter).

Panel Fit (240V)

PASS (120% Rule)

200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 4050.0W / 240 V -> 16.9 A | Breaker >= 1.25 * 16.9 = 21.1 A -> 25 A

CEC Inverters.csv for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}: Paco=4050.0 W, Vac=240 V, Vdcmax=550.0 V, Eff=96.93%.

Result: Min 25 A breaker & 10 AWG Cu (75 C); 200A Bus / 200A Main: PASS (120% Rule).

What Are the Published CEC Specifications for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?

California Energy Commission Solar Equipment List parameters for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} (grid-tied PV inverter) interconnection.

Official California Energy Commission (NREL SAM) test parameters for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 4,050 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 240 V 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 550 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 100 V - 550 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 8.66891 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 96.93% Calculated AC/DC conversion ratio from CEC test protocol
CEC Listing Date & Hybrid 2019-01-15 / Hybrid: No (Grid-Tied PV) Utility interconnection approval metadata

Can a Residential Panel Meet 120% Busbar Limits for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?

Panelboard and switchgear backfeed allowances for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} (25 A OCPD).

Evaluates Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} (25 A required OCPD at 240 V) across standard distribution busbars.
Panel Configuration120% Max BackfeedRequired PV OCPDCompliance Verdict
100A Bus / 100A Main 20 A 25 A Needs Derate / Tap 705.11
150A Bus / 150A Main 30 A 25 A PASS (120% Rule)
200A Bus / 200A Main 40 A 25 A PASS (120% Rule)
200A Bus / 175A Main 65 A 25 A PASS (120% Rule)
225A Bus / 200A Main 70 A 25 A PASS (120% Rule)

Which CEC PV Module Strings Pair With Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?

Representative PV panel pairings verified under NEC 690.7 cold Voc for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}.

Sampled CEC PV modules aligned within 100.0-550.0 V MPPT and 550.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 3 to 9 panels 5.31 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 3 to 13 panels 5.72 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 3 to 12 panels 5.1 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 4 to 13 panels 2.6 kW

Which Competing Grid-Support Inverters Compare to Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?

Four alternative CEC inverters matched to Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} (4,050 W AC), led by ABB: PVI-42-OUTD-S-US-A {240V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
ABB: PVI-42-OUTD-S-US-A {240V}
ABB
4,200 W +150 W 240.0 V 480.0 V 96.11%
ABB: PVI-42-OUTD-S-US-Z-A {240V}
ABB
4,200 W +150 W 240.0 V 480.0 V 96.11%
ABB: PVI-42-OUTD-S-US-Z-M-A {240V}
ABB
4,200 W +150 W 240.0 V 480.0 V 96.11%
Delta Electronics: E4_BDI {240V}
Delta Electronics
3,898 W -152 W 240.0 V 480.0 V 97.67%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?

Check Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} (4,050 W AC, 25 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Requires a 25 A breaker, passing directly inside a standard 200 A main / 200 A busbar panel (40 A limit).
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 550 V DC on Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}.

Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} Panel & Wire Spec

Size 75 C copper conductors at 10 AWG Cu on a 25 A OCPD breaker (16.9 A continuous).

Alternative Inverter Comparison

Compare efficiency (96.93%) and MPPT window (100-550 V) directly against ABB: PVI-42-OUTD-S-US-A {240V} (4,200 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} by Shenzhen Growatt New Energy Co Ltd covering breaker sizing, MPPT limits, and 240 V interconnection.

What breaker and wire size does Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} require?

At 4,050 W continuous AC (240 V), continuous current is 16.9 A; 125% NEC 690.8/705.12 sizing requires a 25 A breaker and 10 AWG Cu (75 C) wire.

Does Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} fit a 200 A main panel under the 120% busbar rule?

A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 25 A at 240 V means PASS (120% Rule).

How does Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} compare to ABB: PVI-42-OUTD-S-US-A {240V}?

Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} delivers 4,050 W AC at 96.93% CEC efficiency with a 550 V DC ceiling, while ABB: PVI-42-OUTD-S-US-A {240V} outputs 4,200 W at 240 V.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.