Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} outputs 4,050 W AC at 240 V (16.9 A continuous, 25 A OCPD), ranking #1,107 of 2,343 CEC inverters at 96.93% efficiency with a 100-550 V MPPT window and 550 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 4,050 W
- AC Voltage
- 240 V
- Min PV Breaker
- 25 A (10 AWG Cu)
- CEC Efficiency
- 96.93%
How Does Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} Compare Against Peer CEC Listings?
CEC efficiency rank (#1,107), 100-550 V MPPT tracking, and panel fit for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}.
Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} from Shenzhen Growatt New Energy Co Ltd outputs 16.9 A continuous AC at 240 V (4,050 W AC, rank #1,622). Paired with 10 AWG Cu conductors and a 25 A OCPD, its 96.93% CEC efficiency compares closely with ABB: PVI-42-OUTD-S-US-A {240V} (4,200 W). Keep NEC 690.7 winter string Voc below 550 V DC.
Where Does Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} at 4,050 W continuous AC output.
What Dataset Percentiles Define Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?
Dataset percentiles comparing Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} against 2,343 certified grid-support inverters nationwide.
What Do the Dataset Ranks Show for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?
Engineering highlights for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} covering efficiency, 10 AWG Cu feeder, and panel compatibility.
96.93% CEC Weighted Efficiency
+0.25 pts vs the 96.68% 240 V median; overall power rank #1,622 (4,050 W, below CEC median; higher than 30.8% of peers).
25 A Required Backfeed OCPD
125% x 16.9 A = 21.1 A -> 25 A standard OCPD using 10 AWG Cu (75 C).
100 V - 550 V (Max 550 V DC)
Tracking span of 450.0 V; listed since 2019-01-15 (grid-tied PV inverter).
PASS (120% Rule)
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 4050.0W / 240 V -> 16.9 A | Breaker >= 1.25 * 16.9 = 21.1 A -> 25 A
CEC Inverters.csv for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}: Paco=4050.0 W, Vac=240 V, Vdcmax=550.0 V, Eff=96.93%.
Result: Min 25 A breaker & 10 AWG Cu (75 C); 200A Bus / 200A Main: PASS (120% Rule).
What Are the Published CEC Specifications for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?
California Energy Commission Solar Equipment List parameters for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} (grid-tied PV inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 4,050 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 550 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 100 V - 550 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 8.66891 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.93% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2019-01-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
Can a Residential Panel Meet 120% Busbar Limits for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?
Panelboard and switchgear backfeed allowances for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} (25 A OCPD).
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 25 A | Needs Derate / Tap 705.11 |
| 150A Bus / 150A Main | 30 A | 25 A | PASS (120% Rule) |
| 200A Bus / 200A Main | 40 A | 25 A | PASS (120% Rule) |
| 200A Bus / 175A Main | 65 A | 25 A | PASS (120% Rule) |
| 225A Bus / 200A Main | 70 A | 25 A | PASS (120% Rule) |
Which CEC PV Module Strings Pair With Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 3 to 9 panels | 5.31 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 3 to 13 panels | 5.72 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 3 to 12 panels | 5.1 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 4 to 13 panels | 2.6 kW |
Which Competing Grid-Support Inverters Compare to Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?
Four alternative CEC inverters matched to Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} (4,050 W AC), led by ABB: PVI-42-OUTD-S-US-A {240V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| ABB: PVI-42-OUTD-S-US-A {240V} ABB |
4,200 W | +150 W | 240.0 V | 480.0 V | 96.11% |
| ABB: PVI-42-OUTD-S-US-Z-A {240V} ABB |
4,200 W | +150 W | 240.0 V | 480.0 V | 96.11% |
| ABB: PVI-42-OUTD-S-US-Z-M-A {240V} ABB |
4,200 W | +150 W | 240.0 V | 480.0 V | 96.11% |
| Delta Electronics: E4_BDI {240V} Delta Electronics |
3,898 W | -152 W | 240.0 V | 480.0 V | 97.67% |
What Are the Interconnection Limits and Best-Fit Uses for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}?
Check Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} (4,050 W AC, 25 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Requires a 25 A breaker, passing directly inside a standard 200 A main / 200 A busbar panel (40 A limit).
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 550 V DC on Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V}.
Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} Panel & Wire Spec
Size 75 C copper conductors at 10 AWG Cu on a 25 A OCPD breaker (16.9 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.93%) and MPPT window (100-550 V) directly against ABB: PVI-42-OUTD-S-US-A {240V} (4,200 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} by Shenzhen Growatt New Energy Co Ltd covering breaker sizing, MPPT limits, and 240 V interconnection.
What breaker and wire size does Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} require?
At 4,050 W continuous AC (240 V), continuous current is 16.9 A; 125% NEC 690.8/705.12 sizing requires a 25 A breaker and 10 AWG Cu (75 C) wire.
Does Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 25 A at 240 V means PASS (120% Rule).
How does Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} compare to ABB: PVI-42-OUTD-S-US-A {240V}?
Shenzhen Growatt New Energy Co Ltd: GROWATT 4000MTLP-US {240V} delivers 4,050 W AC at 96.93% CEC efficiency with a 550 V DC ceiling, while ABB: PVI-42-OUTD-S-US-A {240V} outputs 4,200 W at 240 V.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)