Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} outputs 10,058 W AC at 240 V (41.9 A continuous, 60 A OCPD), ranking #805 of 2,343 CEC inverters at 97.17% efficiency with a 330-550 V MPPT window and 550 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 10,058 W
- AC Voltage
- 240 V
- Min PV Breaker
- 60 A (6 AWG Cu)
- CEC Efficiency
- 97.17%
How Does Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 240 V grid-support overview for Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V}.
Rated at 10,058 W AC (41.9 A continuous), Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} ranks #805 of 2,343 CEC units at 97.17% efficiency (+0.49 pts vs the 96.68% 240 V median). Minimum 75 C copper conductor sizing for its 60 A circuit is 6 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 550 V DC at record local winter lows.
Where Does Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} Fall Across Listed CEC Models?
Marks Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} (10,058 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V}?
Benchmarks Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} continuous AC output, 97.17% CEC weighted efficiency, and 60 A OCPD breaker demand.
What Do the Dataset Ranks Show for Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V}?
Four key NEC 705.12 and California Energy Commission metrics defining Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} by Shenzhen Growatt New Energy Co Ltd.
97.17% CEC Weighted Efficiency
+0.49 pts vs the 96.68% 240 V median; overall power rank #871 (10,058 W, top 37.2%; higher than 62.8% of peers).
60 A Required Backfeed OCPD
125% x 41.9 A = 52.4 A -> 60 A standard OCPD using 6 AWG Cu (75 C).
330 V - 550 V (Max 550 V DC)
Tracking span of 220.0 V; listed since 2018-10-15 (grid-tied PV inverter).
Needs Derate / Tap 705.11
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 10058.0W / 240 V -> 41.9 A | Breaker >= 1.25 * 41.9 = 52.4 A -> 60 A
CEC Inverters.csv for Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V}: Paco=10058.0 W, Vac=240 V, Vdcmax=550.0 V, Eff=97.17%.
Result: Min 60 A breaker & 6 AWG Cu (75 C); 200A Bus / 200A Main: Needs Derate / Tap 705.11.
What Are the Published CEC Specifications for Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 10,058 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 550 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 330 V - 550 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 21.5655 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.17% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2018-10-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
Can a Residential Panel Meet 120% Busbar Limits for Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V}?
Evaluates Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} (60 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 60 A | Needs Derate / Tap 705.11 |
| 150A Bus / 150A Main | 30 A | 60 A | Needs Derate / Tap 705.11 |
| 200A Bus / 200A Main | 40 A | 60 A | Needs Derate / Tap 705.11 |
| 200A Bus / 175A Main | 65 A | 60 A | PASS (120% Rule) |
| 225A Bus / 200A Main | 70 A | 60 A | PASS (120% Rule) |
Which CEC PV Module Strings Pair With Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V}?
Sample PV string lengths aligned within 330-550 V MPPT and 550 V DC max at -10 C. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 8 to 9 panels | 5.31 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 10 to 13 panels | 5.72 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 10 to 12 panels | 5.1 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 12 to 13 panels | 2.6 kW |
Which Competing Grid-Support Inverters Compare to Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V}?
Competing CEC grid-support inverters near 10,058 W AC and 240 V, led by Base Power Inc: MIN 10000TL-XH-US {240V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Base Power Inc: MIN 10000TL-XH-US {240V} Base Power Inc |
10,082 W | +24 W | 240.0 V | 480.0 V | 97.61% |
| Amensolar Ess Co Ltd: N3H-X100-US {240V} Amensolar Ess Co Ltd |
10,177 W | +119 W | 240.0 V | 430.0 V | 97.15% |
| Amensolar Ess Co Ltd: N3H-X10US {240V} Amensolar Ess Co Ltd |
10,177 W | +119 W | 240.0 V | 430.0 V | 97.15% |
| Delta Electronics: E10_BDI {240V} Delta Electronics |
9,674 W | -384 W | 240.0 V | 480.0 V | 97.21% |
What Are the Interconnection Limits and Best-Fit Uses for Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V}?
Check Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} (10,058 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Its 60 A backfeed breaker exceeds a 200A/200A panel's 40 A ceiling, requiring a 175 A main derate, 225 A busbar, or NEC 705.11 tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 550 V DC on Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V}.
Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} Panel & Wire Spec
Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (41.9 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.17%) and MPPT window (330-550 V) directly against Base Power Inc: MIN 10000TL-XH-US {240V} (10,082 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} by Shenzhen Growatt New Energy Co Ltd covering breaker sizing, MPPT limits, and 240 V interconnection.
What breaker and wire size does Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} require?
At 10,058 W continuous AC (240 V), continuous current is 41.9 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.
Does Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 60 A at 240 V means Needs Derate / Tap 705.11.
How does Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} compare to Base Power Inc: MIN 10000TL-XH-US {240V}?
Shenzhen Growatt New Energy Co Ltd: GROWATT 10000MTLP-US {240V} delivers 10,058 W AC at 97.17% CEC efficiency with a 550 V DC ceiling, while Base Power Inc: MIN 10000TL-XH-US {240V} outputs 10,082 W at 240 V.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)