Pika Energy: X11402 {208V} outputs 11,187 W AC at 208 V, commercial single-phase (53.8 A continuous, 70 A OCPD), ranking #1,019 of 2,343 CEC inverters at 96.99% efficiency with a 390-420 V MPPT window and 420 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 11,187 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 70 A (4 AWG Cu)
- CEC Efficiency
- 96.99%
How Does Pika Energy: X11402 {208V} Compare Against Peer CEC Listings?
Breaker sizing (70 A), 4 AWG Cu wire rules, and DC input limits for Pika Energy: X11402 {208V}.
Classified as a hybrid battery-capable inverter (active in CEC directory), Pika Energy: X11402 {208V} requires 67.2 A design capacity -> 70 A breaker using 4 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 96.99% (+0.17 pts vs overall CEC median) across 2,343 CEC models, while commercial 208 v, commercial single-phase switchgear interconnection uses 1,200a bus / 1,200a main (208v) or nec 705.11 supply-side tap.
Where Does Pika Energy: X11402 {208V} Fall Across Listed CEC Models?
Output power comparison showing where Pika Energy: X11402 {208V} sits among all 2,343 CEC-listed grid-support inverters. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
What Dataset Percentiles Define Pika Energy: X11402 {208V}?
Relative ranking of Pika Energy: X11402 {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Pika Energy: X11402 {208V}?
Snapshot of Pika Energy: X11402 {208V} efficiency rank (#1,019), OCPD breaker size, MPPT span, and busbar verdict. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
96.99% CEC Weighted Efficiency
+0.58 pts vs the 96.41% 208 V median; overall power rank #810 (11,187 W, top 34.6%; higher than 65.4% of peers).
70 A Required Backfeed OCPD
125% x 53.8 A = 67.2 A -> 70 A standard OCPD using 4 AWG Cu (75 C).
390 V - 420 V (Max 420 V DC)
Tracking span of 30.0 V; active in CEC directory (hybrid battery-capable inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 11187.0W / 208 V -> 53.8 A | Breaker >= 1.25 * 53.8 = 67.2 A -> 70 A
CEC Inverters.csv for Pika Energy: X11402 {208V}: Paco=11187.0 W, Vac=208 V, Vdcmax=420.0 V, Eff=96.99%.
Result: Min 70 A breaker & 4 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Pika Energy: X11402 {208V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Pika Energy: X11402 {208V}. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 11,187 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 420 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 390 V - 420 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 28.8353 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.99% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to Pika Energy: X11402 {208V} (208 V, commercial single-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Pika Energy: X11402 {208V} at 208 V, commercial single-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 70 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (208V) | 80 A | 70 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 70 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 70 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 70 A | PASS (120% Commercial Busbar) |
Which Competing Grid-Support Inverters Compare to Pika Energy: X11402 {208V}?
Peer 208 V, commercial single-phase CEC inverters near 11,187 W AC output such as EG4 Electronics LLC: IV-13000-HYB-AW-FX-xx {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| EG4 Electronics LLC: IV-13000-HYB-AW-FX-xx {208V} EG4 Electronics LLC |
11,325 W | +138 W | 208.0 V | 440.0 V | 96.79% |
| Chint Power Systems America: CPS ECH114KTL/US {208V} Chint Power Systems America |
11,350 W | +163 W | 208.0 V | 480.0 V | 96.63% |
| EcoFlow Inc: EF-PCS-24 {208V 115kW} EcoFlow Inc |
11,444 W | +257 W | 208.0 V | 480.0 V | 96.52% |
| EG4 Electronics LLC: 18KPV-12LV {208V} EG4 Electronics LLC |
10,499 W | -688 W | 208.0 V | 480.0 V | 96.07% |
What Are the Interconnection Limits and Best-Fit Uses for Pika Energy: X11402 {208V}?
Check Pika Energy: X11402 {208V} (11,187 W AC, 70 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 420 V DC on Pika Energy: X11402 {208V}.
Pika Energy: X11402 {208V} Panel & Wire Spec
Size 75 C copper conductors at 4 AWG Cu on a 70 A OCPD breaker (53.8 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.99%) and MPPT window (390-420 V) directly against EG4 Electronics LLC: IV-13000-HYB-AW-FX-xx {208V} (11,325 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Pika Energy: X11402 {208V} by Pika Energy covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does Pika Energy: X11402 {208V} require?
At 11,187 W continuous AC (208 V, commercial single-phase), continuous current is 53.8 A; 125% NEC 690.8/705.12 sizing requires a 70 A breaker and 4 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Pika Energy: X11402 {208V} require?
At 11,187 W AC and 208 V, commercial single-phase, continuous line current is 53.8 A, requiring a 70 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does Pika Energy: X11402 {208V} compare to EG4 Electronics LLC: IV-13000-HYB-AW-FX-xx {208V}?
Pika Energy: X11402 {208V} delivers 11,187 W AC at 96.99% CEC efficiency with a 420 V DC ceiling, while EG4 Electronics LLC: IV-13000-HYB-AW-FX-xx {208V} outputs 11,325 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)