INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} outputs 1,114,104 W AC at 450 V, 3-phase (1429.4 A continuous, 1,800 A OCPD), ranking #550 of 2,343 CEC inverters at 97.49% efficiency with a 652-800 V MPPT window and 800 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 1,114,104 W
- AC Voltage
- 450 V, 3-phase
- Min PV Breaker
- 1,800 A (parallel Cu feeders)
- CEC Efficiency
- 97.49%
How Does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 450 V, 3-phase grid-support overview for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V}.
Rated at 1,114,104 W AC (1429.4 A continuous), INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} ranks #550 of 2,343 CEC units at 97.49% efficiency (+0.50 pts vs the 96.99% 450 V median). Minimum 75 C copper conductor sizing for its 1,800 A circuit is parallel Cu feeders per NEC Table 310.16. Cold-weather string Voc must remain under 800 V DC at record local winter lows.
Where Does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} Fall Across Listed CEC Models?
Marks INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} (1,114,104 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V}?
Benchmarks INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} continuous AC output, 97.49% CEC weighted efficiency, and 1,800 A OCPD breaker demand.
What Do the Dataset Ranks Show for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V}?
Four key NEC 705.12 and California Energy Commission metrics defining INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} by INGETEAM POWER TECHNOLOGY SA.
97.49% CEC Weighted Efficiency
+0.50 pts vs the 96.99% 450 V median; overall power rank #156 (1,114,104 W, top 6.7%; higher than 93.3% of peers).
1,800 A Required Backfeed OCPD
125% x 1429.4 A = 1786.8 A -> 1,800 A standard OCPD using parallel Cu feeders (75 C).
652 V - 800 V (Max 800 V DC)
Tracking span of 148.0 V; active in CEC directory (hybrid battery-capable inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 450 V, 3-phase switchgear (200A Bus / 200A Main (450V) to 1,200A Bus / 1,200A Main (450V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 1114104.0W / 450 V 3-phase -> 1429.4 A | Breaker >= 1.25 * 1429.4 = 1786.8 A -> 1,800 A
CEC Inverters.csv for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V}: Paco=1114104.0 W, Vac=450 V, Vdcmax=800.0 V, Eff=97.49%.
Result: Min 1,800 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (450V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 1,114,104 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 450 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 800 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 652 V - 800 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 1641.89 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.49% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} (450 V, 3-phase)?
Evaluates INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} (1,800 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (450V) | 40 A | 1,800 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (450V) | 80 A | 1,800 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (450V) | 120 A | 1,800 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (450V) | 160 A | 1,800 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (450V) | 240 A | 1,800 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which Competing Grid-Support Inverters Compare to INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V}?
Competing CEC grid-support inverters near 1,114,104 W AC and 450 V, 3-phase, led by Schneider Electric USA Inc: CS1666-3-NA {575V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Schneider Electric USA Inc: CS1666-3-NA {575V} Schneider Electric USA Inc |
1,666,000 W | +551896 W | 575.0 V | 1200.0 V | 97.54% |
| EPC Power Corp: 50-200100 {720V} EPC Power Corp |
561,806 W | -552298 W | 720.0 V | 1500.0 V | 98.58% |
| SINENG ELECTRIC CO LTD: EH-1725-HA-UD-US {690V} SINENG ELECTRIC CO LTD |
1,726,700 W | +612596 W | 690.0 V | 1500.0 V | 98.32% |
| ABB: PVS-175-TL-POWER-MODULE-1-US {800V} ABB |
179,574 W | -934530 W | 800.0 V | 1200.0 V | 97.39% |
What Are the Interconnection Limits and Best-Fit Uses for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V}?
Check INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} (1,114,104 W AC, 1,800 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 450 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (450V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 800 V DC on INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V}.
INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 1,800 A OCPD breaker (1429.4 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.49%) and MPPT window (652-800 V) directly against Schneider Electric USA Inc: CS1666-3-NA {575V} (1,666,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} by INGETEAM POWER TECHNOLOGY SA covering breaker sizing, MPPT limits, and 450 V, 3-phase interconnection.
What breaker and wire size does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} require?
At 1,114,104 W continuous AC (450 V, 3-phase), continuous current is 1429.4 A; 125% NEC 690.8/705.12 sizing requires a 1,800 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} require?
At 1,114,104 W AC and 450 V, 3-phase, continuous line current is 1429.4 A, requiring a 1,800 A OCPD and 1,200A Bus / 1,200A Main (450V) or NEC 705.11 interconnection.
How does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} compare to Schneider Electric USA Inc: CS1666-3-NA {575V}?
INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1250TL U B450 {450V} delivers 1,114,104 W AC at 97.49% CEC efficiency with a 800 V DC ceiling, while Schneider Electric USA Inc: CS1666-3-NA {575V} outputs 1,666,000 W at 450 V, 3-phase.