INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} outputs 1,042,220 W AC at 480 V, 3-phase (1253.6 A continuous, 1,600 A OCPD), ranking #1,149 of 2,343 CEC inverters at 96.84% efficiency with a 697-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 1,042,220 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 1,600 A (parallel Cu feeders)
- CEC Efficiency
- 96.84%
How Does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} Compare Against Peer CEC Listings?
Breaker sizing (1,600 A), parallel Cu feeders wire rules, and DC input limits for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}.
Classified as a hybrid battery-capable inverter (active in CEC directory), INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} requires 1567.0 A design capacity -> 1,600 A breaker using parallel Cu feeders copper at 75 C terminals. Weighted efficiency sits at 96.84% (+0.02 pts vs overall CEC median) across 2,343 CEC models, while commercial 480 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (480v) or nec 705.11 supply-side tap.
Where Does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} Fall Across Listed CEC Models?
Output power comparison showing where INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}?
Relative ranking of INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}?
Snapshot of INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} efficiency rank (#1,149), OCPD breaker size, MPPT span, and busbar verdict.
96.84% CEC Weighted Efficiency
-1.18 pts vs the 98.02% 480 V median; overall power rank #163 (1,042,220 W, top 7.0%; higher than 93.0% of peers).
1,600 A Required Backfeed OCPD
125% x 1253.6 A = 1567.0 A -> 1,600 A standard OCPD using parallel Cu feeders (75 C).
697 V - 1,200 V (Max 1,200 V DC)
Tracking span of 503.0 V; active in CEC directory (hybrid battery-capable inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 1042220.0W / 480 V 3-phase -> 1253.6 A | Breaker >= 1.25 * 1253.6 = 1567.0 A -> 1,600 A
CEC Inverters.csv for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}: Paco=1042220.0 W, Vac=480 V, Vdcmax=1200.0 V, Eff=96.84%.
Result: Min 1,600 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (480V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 1,042,220 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 697 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 1134.09 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.84% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} (480 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} at 480 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 1,600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 1,600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (480V) | 120 A | 1,600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (480V) | 160 A | 1,600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 1,600 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}?
Minimum and maximum series solar module strings fitting INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} MPPT and 1,200 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 17 to 21 panels | 12.39 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 21 to 28 panels | 12.32 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 21 to 26 panels | 11.05 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 25 to 29 panels | 5.8 kW |
Which Competing Grid-Support Inverters Compare to INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}?
Peer 480 V, 3-phase CEC inverters near 1,042,220 W AC output such as EPC Power Corp: 50-100181 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| EPC Power Corp: 50-100181 {480V} EPC Power Corp |
1,044,200 W | +1980 W | 480.0 V | 1500.0 V | 97.49% |
| EPC Power Corp: 50-100100 {480V} EPC Power Corp |
1,036,840 W | -5380 W | 480.0 V | 1250.0 V | 95.42% |
| DYNAPOWER COMPANY LLC: CPS-1500 Gen4 {480V} DYNAPOWER COMPANY LLC |
1,199,640 W | +157420 W | 480.0 V | 1500.0 V | 96.13% |
| Delta Electronics: EPCS-1200US {480V} Delta Electronics |
1,216,710 W | +174490 W | 480.0 V | 1500.0 V | 97.82% |
What Are the Interconnection Limits and Best-Fit Uses for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}?
Check INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} (1,042,220 W AC, 1,600 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V}.
INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 1,600 A OCPD breaker (1253.6 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.84%) and MPPT window (697-1,200 V) directly against EPC Power Corp: 50-100181 {480V} (1,044,200 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} by INGETEAM POWER TECHNOLOGY SA covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} require?
At 1,042,220 W continuous AC (480 V, 3-phase), continuous current is 1253.6 A; 125% NEC 690.8/705.12 sizing requires a 1,600 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} require?
At 1,042,220 W AC and 480 V, 3-phase, continuous line current is 1253.6 A, requiring a 1,600 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} compare to EPC Power Corp: 50-100181 {480V}?
INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1245TL U B480 {480V} delivers 1,042,220 W AC at 96.84% CEC efficiency with a 1,200 V DC ceiling, while EPC Power Corp: 50-100181 {480V} outputs 1,044,200 W at 480 V, 3-phase.