INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} outputs 1,099,306 W AC at 440 V, 3-phase (1442.5 A continuous, 1,850 A OCPD), ranking #573 of 2,343 CEC inverters at 97.44% efficiency with a 638-800 V MPPT window and 800 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 1,099,306 W
- AC Voltage
- 440 V, 3-phase
- Min PV Breaker
- 1,850 A (parallel Cu feeders)
- CEC Efficiency
- 97.44%
How Does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} Compare Against Peer CEC Listings?
CEC efficiency rank (#573), 638-800 V MPPT tracking, and panel fit for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V}.
INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} from INGETEAM POWER TECHNOLOGY SA outputs 1442.5 A continuous AC at 440 V, 3-phase (1,099,306 W AC, rank #159). Paired with parallel Cu feeders conductors and a 1,850 A OCPD, its 97.44% CEC efficiency compares closely with EPC Power Corp: 50-200100 {720V} (561,806 W). Keep NEC 690.7 winter string Voc below 800 V DC.
Where Does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} at 1,099,306 W continuous AC output.
What Dataset Percentiles Define INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V}?
Dataset percentiles comparing INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} against 2,343 certified grid-support inverters nationwide.
What Do the Dataset Ranks Show for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V}?
Engineering highlights for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} covering efficiency, parallel Cu feeders feeder, and panel compatibility.
97.44% CEC Weighted Efficiency
-0.03 pts vs the 97.47% 440 V median; overall power rank #159 (1,099,306 W, top 6.8%; higher than 93.2% of peers).
1,850 A Required Backfeed OCPD
125% x 1442.5 A = 1803.1 A -> 1,850 A standard OCPD using parallel Cu feeders (75 C).
638 V - 800 V (Max 800 V DC)
Tracking span of 162.0 V; active in CEC directory (hybrid battery-capable inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 440 V, 3-phase switchgear (200A Bus / 200A Main (440V) to 1,200A Bus / 1,200A Main (440V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 1099306.0W / 440 V 3-phase -> 1442.5 A | Breaker >= 1.25 * 1442.5 = 1803.1 A -> 1,850 A
CEC Inverters.csv for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V}: Paco=1099306.0 W, Vac=440 V, Vdcmax=800.0 V, Eff=97.44%.
Result: Min 1,850 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (440V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V}?
California Energy Commission Solar Equipment List parameters for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} (hybrid battery-capable inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 1,099,306 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 440 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 800 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 638 V - 800 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 1637.37 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.44% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} (440 V, 3-phase)?
Panelboard and switchgear backfeed allowances for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} (1,850 A OCPD).
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (440V) | 40 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (440V) | 80 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (440V) | 120 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (440V) | 160 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (440V) | 240 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which Competing Grid-Support Inverters Compare to INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V}?
Four alternative CEC inverters matched to INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} (1,099,306 W AC), led by EPC Power Corp: 50-200100 {720V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| EPC Power Corp: 50-200100 {720V} EPC Power Corp |
561,806 W | -537500 W | 720.0 V | 1500.0 V | 98.58% |
| Schneider Electric USA Inc: CS1666-3-NA {575V} Schneider Electric USA Inc |
1,666,000 W | +566694 W | 575.0 V | 1200.0 V | 97.54% |
| SINENG ELECTRIC CO LTD: EH-1725-HA-UD-US {690V} SINENG ELECTRIC CO LTD |
1,726,700 W | +627394 W | 690.0 V | 1500.0 V | 98.32% |
| ABB: PVS-175-TL-POWER-MODULE-1-US {800V} ABB |
179,574 W | -919732 W | 800.0 V | 1200.0 V | 97.39% |
What Are the Interconnection Limits and Best-Fit Uses for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V}?
Check INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} (1,099,306 W AC, 1,850 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 440 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (440V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 800 V DC on INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V}.
INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 1,850 A OCPD breaker (1442.5 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.44%) and MPPT window (638-800 V) directly against EPC Power Corp: 50-200100 {720V} (561,806 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} by INGETEAM POWER TECHNOLOGY SA covering breaker sizing, MPPT limits, and 440 V, 3-phase interconnection.
What breaker and wire size does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} require?
At 1,099,306 W continuous AC (440 V, 3-phase), continuous current is 1442.5 A; 125% NEC 690.8/705.12 sizing requires a 1,850 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} require?
At 1,099,306 W AC and 440 V, 3-phase, continuous line current is 1442.5 A, requiring a 1,850 A OCPD and 1,200A Bus / 1,200A Main (440V) or NEC 705.11 interconnection.
How does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} compare to EPC Power Corp: 50-200100 {720V}?
INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1220TL U B440 {440V} delivers 1,099,306 W AC at 97.44% CEC efficiency with a 800 V DC ceiling, while EPC Power Corp: 50-200100 {720V} outputs 561,806 W at 440 V, 3-phase.