INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} outputs 1,048,594 W AC at 430 V, 3-phase (1408.0 A continuous, 1,800 A OCPD), ranking #595 of 2,343 CEC inverters at 97.41% efficiency with a 624-800 V MPPT window and 800 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 1,048,594 W
- AC Voltage
- 430 V, 3-phase
- Min PV Breaker
- 1,800 A (parallel Cu feeders)
- CEC Efficiency
- 97.41%
How Does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} Compare Against Peer CEC Listings?
CEC efficiency rank (#595), 624-800 V MPPT tracking, and panel fit for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V}.
Operating at 430 V, 3-phase, INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} converts DC array energy at 97.41% CEC weighted efficiency (top 25.9%; higher than 74.1% of peers) with a 800 V max DC input and 1578.34 A max input current for NEC 690.7 string safety. Compare this 1,048,594 W hybrid battery-capable inverter directly with EPC Power Corp: 50-200100 {720V} (561,806 W). Commercial 430 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (430V) or NEC 705.11 supply-side tap.
Where Does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} at 1,048,594 W continuous AC output.
What Dataset Percentiles Define INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V}?
Dataset percentiles comparing INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} against 2,343 certified grid-support inverters nationwide.
What Do the Dataset Ranks Show for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V}?
Engineering highlights for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} covering efficiency, parallel Cu feeders feeder, and panel compatibility.
97.41% CEC Weighted Efficiency
equal to the 97.41% 430 V median; overall power rank #161 (1,048,594 W, top 6.9%; higher than 93.1% of peers).
1,800 A Required Backfeed OCPD
125% x 1408.0 A = 1760.0 A -> 1,800 A standard OCPD using parallel Cu feeders (75 C).
624 V - 800 V (Max 800 V DC)
Tracking span of 176.0 V; active in CEC directory (hybrid battery-capable inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 430 V, 3-phase switchgear (200A Bus / 200A Main (430V) to 1,200A Bus / 1,200A Main (430V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 1048594.0W / 430 V 3-phase -> 1408.0 A | Breaker >= 1.25 * 1408.0 = 1760.0 A -> 1,800 A
CEC Inverters.csv for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V}: Paco=1048594.0 W, Vac=430 V, Vdcmax=800.0 V, Eff=97.41%.
Result: Min 1,800 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (430V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V}?
California Energy Commission Solar Equipment List parameters for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} (hybrid battery-capable inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 1,048,594 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 430 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 800 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 624 V - 800 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 1578.34 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.41% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} (430 V, 3-phase)?
Panelboard and switchgear backfeed allowances for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} (1,800 A OCPD).
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (430V) | 40 A | 1,800 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (430V) | 80 A | 1,800 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (430V) | 120 A | 1,800 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (430V) | 160 A | 1,800 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (430V) | 240 A | 1,800 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which Competing Grid-Support Inverters Compare to INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V}?
Four alternative CEC inverters matched to INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} (1,048,594 W AC), led by EPC Power Corp: 50-200100 {720V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| EPC Power Corp: 50-200100 {720V} EPC Power Corp |
561,806 W | -486788 W | 720.0 V | 1500.0 V | 98.58% |
| Schneider Electric USA Inc: CS1666-3-NA {575V} Schneider Electric USA Inc |
1,666,000 W | +617406 W | 575.0 V | 1200.0 V | 97.54% |
| SINENG ELECTRIC CO LTD: EH-1725-HA-UD-US {690V} SINENG ELECTRIC CO LTD |
1,726,700 W | +678106 W | 690.0 V | 1500.0 V | 98.32% |
| ABB: PVS-175-TL-POWER-MODULE-1-US {800V} ABB |
179,574 W | -869020 W | 800.0 V | 1200.0 V | 97.39% |
What Are the Interconnection Limits and Best-Fit Uses for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V}?
Check INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} (1,048,594 W AC, 1,800 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 430 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (430V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 800 V DC on INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V}.
INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 1,800 A OCPD breaker (1408.0 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.41%) and MPPT window (624-800 V) directly against EPC Power Corp: 50-200100 {720V} (561,806 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} by INGETEAM POWER TECHNOLOGY SA covering breaker sizing, MPPT limits, and 430 V, 3-phase interconnection.
What breaker and wire size does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} require?
At 1,048,594 W continuous AC (430 V, 3-phase), continuous current is 1408.0 A; 125% NEC 690.8/705.12 sizing requires a 1,800 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} require?
At 1,048,594 W AC and 430 V, 3-phase, continuous line current is 1408.0 A, requiring a 1,800 A OCPD and 1,200A Bus / 1,200A Main (430V) or NEC 705.11 interconnection.
How does INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} compare to EPC Power Corp: 50-200100 {720V}?
INGETEAM POWER TECHNOLOGY SA: INGECON SUN 1190TL U B430 {430V} delivers 1,048,594 W AC at 97.41% CEC efficiency with a 800 V DC ceiling, while EPC Power Corp: 50-200100 {720V} outputs 561,806 W at 430 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)