HiQ Solar: TSXL480-10k {480V} outputs 9,975 W AC at 480 V, 3-phase (12.0 A continuous, 15 A OCPD), ranking #314 of 2,343 CEC inverters at 98.06% efficiency with a 450-850 V MPPT window and 850 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 9,975 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 15 A (14 AWG Cu)
- CEC Efficiency
- 98.06%
How Does HiQ Solar: TSXL480-10k {480V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 480 V, 3-phase grid-support overview for HiQ Solar: TSXL480-10k {480V}. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
Rated at 9,975 W AC (12.0 A continuous), HiQ Solar: TSXL480-10k {480V} ranks #314 of 2,343 CEC units at 98.06% efficiency (+0.04 pts vs the 98.02% 480 V median). Minimum 75 C copper conductor sizing for its 15 A circuit is 14 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 850 V DC at record local winter lows.
Where Does HiQ Solar: TSXL480-10k {480V} Fall Across Listed CEC Models?
Marks HiQ Solar: TSXL480-10k {480V} (9,975 W AC) across the California Energy Commission inverter AC capacity distribution. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
What Dataset Percentiles Define HiQ Solar: TSXL480-10k {480V}?
Benchmarks HiQ Solar: TSXL480-10k {480V} continuous AC output, 98.06% CEC weighted efficiency, and 15 A OCPD breaker demand.
What Do the Dataset Ranks Show for HiQ Solar: TSXL480-10k {480V}?
Four key NEC 705.12 and California Energy Commission metrics defining HiQ Solar: TSXL480-10k {480V} by HiQ Solar. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
98.06% CEC Weighted Efficiency
+0.04 pts vs the 98.02% 480 V median; overall power rank #923 (9,975 W, top 39.5%; higher than 60.5% of peers).
15 A Required Backfeed OCPD
125% x 12.0 A = 15.0 A -> 15 A standard OCPD using 14 AWG Cu (75 C).
450 V - 850 V (Max 850 V DC)
Tracking span of 400.0 V; listed since 2019-02-15 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 9975.0W / 480 V 3-phase -> 12.0 A | Breaker >= 1.25 * 12.0 = 15.0 A -> 15 A
CEC Inverters.csv for HiQ Solar: TSXL480-10k {480V}: Paco=9975.0 W, Vac=480 V, Vdcmax=850.0 V, Eff=98.06%.
Result: Min 15 A breaker & 14 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for HiQ Solar: TSXL480-10k {480V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for HiQ Solar: TSXL480-10k {480V}. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 9,975 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 850 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 450 V - 850 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 13.5625 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.06% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2019-02-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to HiQ Solar: TSXL480-10k {480V} (480 V, 3-phase)?
Evaluates HiQ Solar: TSXL480-10k {480V} (15 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 15 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (480V) | 80 A | 15 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 15 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 15 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 15 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With HiQ Solar: TSXL480-10k {480V}?
Sample PV string lengths aligned within 450-850 V MPPT and 850 V DC max at -10 C. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 11 to 15 panels | 8.85 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 14 to 20 panels | 8.8 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 14 to 18 panels | 7.65 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 16 to 20 panels | 4.0 kW |
Which Competing Grid-Support Inverters Compare to HiQ Solar: TSXL480-10k {480V}?
Competing CEC grid-support inverters near 9,975 W AC and 480 V, 3-phase, led by Fronius International GmbH: Fronius Symo 100-3 480 {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Fronius International GmbH: Fronius Symo 100-3 480 {480V} Fronius International GmbH |
9,995 W | +20 W | 480.0 V | 800.0 V | 97.42% |
| Fronius International GmbH: Fronius Symo 125-3 480 {480V} Fronius International GmbH |
12,500 W | +2525 W | 480.0 V | 800.0 V | 97.57% |
| Fronius International GmbH: Fronius Symo 150-3 480 {480V} Fronius International GmbH |
15,000 W | +5025 W | 480.0 V | 800.0 V | 97.47% |
| Fronius International GmbH: Fronius Symo Advanced 150-3 480 {480V} Fronius International GmbH |
15,197 W | +5222 W | 480.0 V | 800.0 V | 97.48% |
What Are the Interconnection Limits and Best-Fit Uses for HiQ Solar: TSXL480-10k {480V}?
Check HiQ Solar: TSXL480-10k {480V} (9,975 W AC, 15 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 850 V DC on HiQ Solar: TSXL480-10k {480V}.
HiQ Solar: TSXL480-10k {480V} Panel & Wire Spec
Size 75 C copper conductors at 14 AWG Cu on a 15 A OCPD breaker (12.0 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.06%) and MPPT window (450-850 V) directly against Fronius International GmbH: Fronius Symo 100-3 480 {480V} (9,995 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for HiQ Solar: TSXL480-10k {480V} by HiQ Solar covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does HiQ Solar: TSXL480-10k {480V} require?
At 9,975 W continuous AC (480 V, 3-phase), continuous current is 12.0 A; 125% NEC 690.8/705.12 sizing requires a 15 A breaker and 14 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does HiQ Solar: TSXL480-10k {480V} require?
At 9,975 W AC and 480 V, 3-phase, continuous line current is 12.0 A, requiring a 15 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does HiQ Solar: TSXL480-10k {480V} compare to Fronius International GmbH: Fronius Symo 100-3 480 {480V}?
HiQ Solar: TSXL480-10k {480V} delivers 9,975 W AC at 98.06% CEC efficiency with a 850 V DC ceiling, while Fronius International GmbH: Fronius Symo 100-3 480 {480V} outputs 9,995 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)