Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} — CEC Inverter Specifications

Manufacturer: Guangzhou Sanjing Electric Co Ltd Registry: CEC Verified Engineering Specification

Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} outputs 8,316 W AC at 208 V, commercial single-phase (40.0 A continuous, 50 A OCPD), ranking #1,112 of 2,343 CEC inverters at 96.92% efficiency with a 190-510 V MPPT window and 510 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
8,316 W
AC Voltage
208 V, commercial single-phase
Min PV Breaker
50 A (8 AWG Cu)
CEC Efficiency
96.92%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} Compare Against Peer CEC Listings?

CEC efficiency rank (#1,112), 190-510 V MPPT tracking, and panel fit for Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V}.

Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} from Guangzhou Sanjing Electric Co Ltd outputs 40.0 A continuous AC at 208 V, commercial single-phase (8,316 W AC, rank #1,081). Paired with 8 AWG Cu conductors and a 50 A OCPD, its 96.92% CEC efficiency compares closely with Altenergy Power System Inc: ELS-96 {208V} (8,308 W). Keep NEC 690.7 winter string Voc below 510 V DC.

Where Does Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} Fall Across Listed CEC Models?

CEC inverter wattage histogram highlighting Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} at 8,316 W continuous AC output.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} (8,316 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACGuangzhou Sanjing : 8,316 W

What Dataset Percentiles Define Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V}?

Dataset percentiles comparing Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} against 2,343 certified grid-support inverters nationwide. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} Technical ThresholdsPercentile comparison for Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output8,316 WCEC Efficiency96.92%Backfeed Breaker50 A

What Do the Dataset Ranks Show for Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V}?

Engineering highlights for Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} covering efficiency, 8 AWG Cu feeder, and panel compatibility.

Eff #1,112 / 2,343

96.92% CEC Weighted Efficiency

+0.51 pts vs the 96.41% 208 V median; overall power rank #1,081 (8,316 W, top 46.1%; higher than 53.9% of peers).

NEC 705.12 Check

50 A Required Backfeed OCPD

125% x 40.0 A = 50.0 A -> 50 A standard OCPD using 8 AWG Cu (75 C).

MPPT Window

190 V - 510 V (Max 510 V DC)

Tracking span of 320.0 V; active in CEC directory (hybrid battery-capable inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 8316.0W / 208 V -> 40.0 A | Breaker >= 1.25 * 40.0 = 50.0 A -> 50 A

CEC Inverters.csv for Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V}: Paco=8316.0 W, Vac=208 V, Vdcmax=510.0 V, Eff=96.92%.

Result: Min 50 A breaker & 8 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V}?

California Energy Commission Solar Equipment List parameters for Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} (hybrid battery-capable inverter) interconnection.

Official California Energy Commission (NREL SAM) test parameters for Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 8,316 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 208 V, commercial single-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 510 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 190 V - 510 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 22.5788 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 96.92% Calculated AC/DC conversion ratio from CEC test protocol
Inverter Topology Hybrid: Yes (Battery Capable) CEC Solar Equipment List grid-support certification

What Switchgear Limits Apply to Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} (208 V, commercial single-phase)?

Panelboard and switchgear backfeed allowances for Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} (50 A OCPD). Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Evaluates Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} (50 A required OCPD at 208 V, commercial single-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (208V) 40 A 50 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (208V) 80 A 50 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (208V) 120 A 50 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (208V) 160 A 50 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (208V) 240 A 50 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V}?

Representative PV panel pairings verified under NEC 690.7 cold Voc for Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V}.

Sampled CEC PV modules aligned within 190.0-510.0 V MPPT and 510.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 5 to 9 panels 5.31 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 6 to 12 panels 5.28 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 6 to 11 panels 4.67 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 7 to 12 panels 2.4 kW

Which Competing Grid-Support Inverters Compare to Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V}?

Four alternative CEC inverters matched to Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} (8,316 W AC), led by Altenergy Power System Inc: ELS-96 {208V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Altenergy Power System Inc: ELS-96 {208V}
Altenergy Power System Inc
8,308 W -8 W 208.0 V 60.0 V 93.5%
Delta Electronics: E10-TL-US(AC) {208V}
Delta Electronics
8,327 W +11 W 208.0 V 480.0 V 97.45%
Delta Electronics: M10-TL-US {208V}
Delta Electronics
8,360 W +44 W 208.0 V 480.0 V 96.83%
Delta Electronics: M10-4-TL-US {208V}
Delta Electronics
8,385 W +69 W 208.0 V 480.0 V 96.94%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V}?

Check Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} (8,316 W AC, 50 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 510 V DC on Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V}.

Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} Panel & Wire Spec

Size 75 C copper conductors at 8 AWG Cu on a 50 A OCPD breaker (40.0 A continuous).

Alternative Inverter Comparison

Compare efficiency (96.92%) and MPPT window (190-510 V) directly against Altenergy Power System Inc: ELS-96 {208V} (8,308 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} by Guangzhou Sanjing Electric Co Ltd covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.

What breaker and wire size does Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} require?

At 8,316 W continuous AC (208 V, commercial single-phase), continuous current is 40.0 A; 125% NEC 690.8/705.12 sizing requires a 50 A breaker and 8 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} require?

At 8,316 W AC and 208 V, commercial single-phase, continuous line current is 40.0 A, requiring a 50 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

How does Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} compare to Altenergy Power System Inc: ELS-96 {208V}?

Guangzhou Sanjing Electric Co Ltd: H2-96K-LS4-US {208V} delivers 8,316 W AC at 96.92% CEC efficiency with a 510 V DC ceiling, while Altenergy Power System Inc: ELS-96 {208V} outputs 8,308 W at 208 V, commercial single-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.