GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} outputs 9,566 W AC at 240 V (39.9 A continuous, 50 A OCPD), ranking #1,281 of 2,343 CEC inverters at 96.68% efficiency with a 210-500 V MPPT window and 500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 9,566 W
- AC Voltage
- 240 V
- Min PV Breaker
- 50 A (8 AWG Cu)
- CEC Efficiency
- 96.68%
How Does GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} Compare Against Peer CEC Listings?
Breaker sizing (50 A), 8 AWG Cu wire rules, and DC input limits for GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V}.
Classified as a grid-tied PV inverter (active in CEC directory), GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} requires 49.9 A design capacity -> 50 A breaker using 8 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 96.68% (-0.14 pts vs overall CEC median) across 2,343 CEC models, while its 50 a backfeed breaker exceeds a 200a/200a panel's 40 a ceiling, requiring a 175 a main derate, 225 a busbar, or nec 705.11 tap.
Where Does GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} Fall Across Listed CEC Models?
Output power comparison showing where GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V}?
Relative ranking of GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V}?
Snapshot of GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} efficiency rank (#1,281), OCPD breaker size, MPPT span, and busbar verdict.
96.68% CEC Weighted Efficiency
equal to the 96.68% 240 V median; overall power rank #998 (9,566 W, top 42.6%; higher than 57.4% of peers).
50 A Required Backfeed OCPD
125% x 39.9 A = 49.9 A -> 50 A standard OCPD using 8 AWG Cu (75 C).
210 V - 500 V (Max 500 V DC)
Tracking span of 290.0 V; active in CEC directory (grid-tied PV inverter).
Needs Derate / Tap 705.11
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 9566.0W / 240 V -> 39.9 A | Breaker >= 1.25 * 39.9 = 49.9 A -> 50 A
CEC Inverters.csv for GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V}: Paco=9566.0 W, Vac=240 V, Vdcmax=500.0 V, Eff=96.68%.
Result: Min 50 A breaker & 8 AWG Cu (75 C); 200A Bus / 200A Main: Needs Derate / Tap 705.11.
What Are the Published CEC Specifications for GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 9,566 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 210 V - 500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 26.0383 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.68% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
Can a Residential Panel Meet 120% Busbar Limits for GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V}?
NEC 705.12(B)(3)(2) backfeed compliance table for GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} at 240 V.
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 50 A | Needs Derate / Tap 705.11 |
| 150A Bus / 150A Main | 30 A | 50 A | Needs Derate / Tap 705.11 |
| 200A Bus / 200A Main | 40 A | 50 A | Needs Derate / Tap 705.11 |
| 200A Bus / 175A Main | 65 A | 50 A | PASS (120% Rule) |
| 225A Bus / 200A Main | 70 A | 50 A | PASS (120% Rule) |
Which CEC PV Module Strings Pair With GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V}?
Minimum and maximum series solar module strings fitting GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} MPPT and 500 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 5 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 7 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 7 to 11 panels | 4.67 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 8 to 12 panels | 2.4 kW |
Which Competing Grid-Support Inverters Compare to GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V}?
Peer 240 V CEC inverters near 9,566 W AC output such as Afore New Energy Technology (Shanghai) Co Ltd: AF96K-DH {240V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Afore New Energy Technology (Shanghai) Co Ltd: AF96K-DH {240V} Afore New Energy Technology (Shanghai) Co Ltd |
9,592 W | +26 W | 240.0 V | 480.0 V | 97.87% |
| AIMS Power Inc: PIHY9600 {240V} AIMS Power Inc |
9,592 W | +26 W | 240.0 V | 480.0 V | 97.87% |
| CESC New Energy Technology Co Ltd: Mars 9600 HVSP {240V} CESC New Energy Technology Co Ltd |
9,592 W | +26 W | 240.0 V | 480.0 V | 97.87% |
| Chint Power Systems America: CPS ECH96KTL/US {240V} Chint Power Systems America |
9,540 W | -26 W | 240.0 V | 480.0 V | 96.61% |
What Are the Interconnection Limits and Best-Fit Uses for GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V}?
Check GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} (9,566 W AC, 50 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Its 50 A backfeed breaker exceeds a 200A/200A panel's 40 A ceiling, requiring a 175 A main derate, 225 A busbar, or NEC 705.11 tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 500 V DC on GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V}.
GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 50 A OCPD breaker (39.9 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.68%) and MPPT window (210-500 V) directly against Afore New Energy Technology (Shanghai) Co Ltd: AF96K-DH {240V} (9,592 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} by GoodWe Technologies Co Ltd covering breaker sizing, MPPT limits, and 240 V interconnection.
What breaker and wire size does GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} require?
At 9,566 W continuous AC (240 V), continuous current is 39.9 A; 125% NEC 690.8/705.12 sizing requires a 50 A breaker and 8 AWG Cu (75 C) wire.
Does GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 50 A at 240 V means Needs Derate / Tap 705.11.
How does GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} compare to Afore New Energy Technology (Shanghai) Co Ltd: AF96K-DH {240V}?
GoodWe Technologies Co Ltd: GW9600-MS-US30 {240V} delivers 9,566 W AC at 96.68% CEC efficiency with a 500 V DC ceiling, while Afore New Energy Technology (Shanghai) Co Ltd: AF96K-DH {240V} outputs 9,592 W at 240 V.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)