GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} outputs 8,301 W AC at 208 V, commercial single-phase (39.9 A continuous, 50 A OCPD), ranking #1,938 of 2,343 CEC inverters at 96.03% efficiency with a 182-500 V MPPT window and 500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 8,301 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 50 A (8 AWG Cu)
- CEC Efficiency
- 96.03%
How Does GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} Compare Against Peer CEC Listings?
Breaker sizing (50 A), 8 AWG Cu wire rules, and DC input limits for GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V}.
For NEC 705.12 solar interconnection, GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} outputs 39.9 A continuous AC at 208 V, commercial single-phase and needs a 50 A backfeed breaker on 8 AWG Cu (75 C). Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Conversion efficiency scores 96.03% (#1,938 of 2,343, -0.79 pts vs overall CEC median).
Where Does GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} Fall Across Listed CEC Models?
Output power comparison showing where GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V}?
Relative ranking of GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V}?
Snapshot of GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} efficiency rank (#1,938), OCPD breaker size, MPPT span, and busbar verdict.
96.03% CEC Weighted Efficiency
-0.38 pts vs the 96.41% 208 V median; overall power rank #1,084 (8,301 W, top 46.3%; higher than 53.7% of peers).
50 A Required Backfeed OCPD
125% x 39.9 A = 49.9 A -> 50 A standard OCPD using 8 AWG Cu (75 C).
182 V - 500 V (Max 500 V DC)
Tracking span of 318.0 V; active in CEC directory (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 8301.0W / 208 V -> 39.9 A | Breaker >= 1.25 * 39.9 = 49.9 A -> 50 A
CEC Inverters.csv for GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V}: Paco=8301.0 W, Vac=208 V, Vdcmax=500.0 V, Eff=96.03%.
Result: Min 50 A breaker & 8 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 8,301 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 182 V - 500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 26.1953 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.03% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} (208 V, commercial single-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} at 208 V, commercial single-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 50 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (208V) | 80 A | 50 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 50 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 50 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 50 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V}?
Minimum and maximum series solar module strings fitting GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} MPPT and 500 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 5 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 6 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 6 to 11 panels | 4.67 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 7 to 12 panels | 2.4 kW |
Which Competing Grid-Support Inverters Compare to GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V}?
Peer 208 V, commercial single-phase CEC inverters near 8,301 W AC output such as Altenergy Power System Inc: ELS-96 {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Altenergy Power System Inc: ELS-96 {208V} Altenergy Power System Inc |
8,308 W | +7 W | 208.0 V | 60.0 V | 93.5% |
| Delta Electronics: E10-TL-US(AC) {208V} Delta Electronics |
8,327 W | +26 W | 208.0 V | 480.0 V | 97.45% |
| Delta Electronics: M10-TL-US {208V} Delta Electronics |
8,360 W | +59 W | 208.0 V | 480.0 V | 96.83% |
| Delta Electronics: M10-4-TL-US {208V} Delta Electronics |
8,385 W | +84 W | 208.0 V | 480.0 V | 96.94% |
What Are the Interconnection Limits and Best-Fit Uses for GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V}?
Check GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} (8,301 W AC, 50 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 500 V DC on GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V}.
GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 50 A OCPD breaker (39.9 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.03%) and MPPT window (182-500 V) directly against Altenergy Power System Inc: ELS-96 {208V} (8,308 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} by GoodWe Technologies Co Ltd covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} require?
At 8,301 W continuous AC (208 V, commercial single-phase), continuous current is 39.9 A; 125% NEC 690.8/705.12 sizing requires a 50 A breaker and 8 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} require?
At 8,301 W AC and 208 V, commercial single-phase, continuous line current is 39.9 A, requiring a 50 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} compare to Altenergy Power System Inc: ELS-96 {208V}?
GoodWe Technologies Co Ltd: GW9600-MS-US30 {208V} delivers 8,301 W AC at 96.03% CEC efficiency with a 500 V DC ceiling, while Altenergy Power System Inc: ELS-96 {208V} outputs 8,308 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)