GoodWe Technologies Co Ltd: GW8600A-BP {240V} outputs 8,680 W AC at 240 V (36.2 A continuous, 50 A OCPD), ranking #1,785 of 2,343 CEC inverters at 96.28% efficiency with a 200-495 V MPPT window and 495 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 8,680 W
- AC Voltage
- 240 V
- Min PV Breaker
- 50 A (8 AWG Cu)
- CEC Efficiency
- 96.28%
How Does GoodWe Technologies Co Ltd: GW8600A-BP {240V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 240 V grid-support overview for GoodWe Technologies Co Ltd: GW8600A-BP {240V}.
Ranking #1,049 of 2,343 CEC inverters (top 44.8%; higher than 55.2% of peers), GoodWe Technologies Co Ltd: GW8600A-BP {240V} is a grid-tied PV inverter delivering 8,680 W continuous AC at 240 V (36.2 A continuous). Its 50 A backfeed breaker exceeds a 200A/200A panel's 40 A ceiling, requiring a 175 A main derate, 225 A busbar, or NEC 705.11 tap. Weighted CEC efficiency reaches 96.28% (-0.40 pts vs the 96.68% 240 V median) against peers like ABB: UNO-86-TL-OUTD-S-US-A {240V} (8,600 W).
Where Does GoodWe Technologies Co Ltd: GW8600A-BP {240V} Fall Across Listed CEC Models?
Marks GoodWe Technologies Co Ltd: GW8600A-BP {240V} (8,680 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define GoodWe Technologies Co Ltd: GW8600A-BP {240V}?
Benchmarks GoodWe Technologies Co Ltd: GW8600A-BP {240V} continuous AC output, 96.28% CEC weighted efficiency, and 50 A OCPD breaker demand.
What Do the Dataset Ranks Show for GoodWe Technologies Co Ltd: GW8600A-BP {240V}?
Four key NEC 705.12 and California Energy Commission metrics defining GoodWe Technologies Co Ltd: GW8600A-BP {240V} by GoodWe Technologies Co Ltd.
96.28% CEC Weighted Efficiency
-0.40 pts vs the 96.68% 240 V median; overall power rank #1,049 (8,680 W, top 44.8%; higher than 55.2% of peers).
50 A Required Backfeed OCPD
125% x 36.2 A = 45.2 A -> 50 A standard OCPD using 8 AWG Cu (75 C).
200 V - 495 V (Max 495 V DC)
Tracking span of 295.0 V; listed since 2023-12-11 (grid-tied PV inverter).
Needs Derate / Tap 705.11
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 8680.0W / 240 V -> 36.2 A | Breaker >= 1.25 * 36.2 = 45.2 A -> 50 A
CEC Inverters.csv for GoodWe Technologies Co Ltd: GW8600A-BP {240V}: Paco=8680.0 W, Vac=240 V, Vdcmax=495.0 V, Eff=96.28%.
Result: Min 50 A breaker & 8 AWG Cu (75 C); 200A Bus / 200A Main: Needs Derate / Tap 705.11.
What Are the Published CEC Specifications for GoodWe Technologies Co Ltd: GW8600A-BP {240V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for GoodWe Technologies Co Ltd: GW8600A-BP {240V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 8,680 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 495 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 200 V - 495 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 25.7592 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.28% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2023-12-11 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
Can a Residential Panel Meet 120% Busbar Limits for GoodWe Technologies Co Ltd: GW8600A-BP {240V}?
Evaluates GoodWe Technologies Co Ltd: GW8600A-BP {240V} (50 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 50 A | Needs Derate / Tap 705.11 |
| 150A Bus / 150A Main | 30 A | 50 A | Needs Derate / Tap 705.11 |
| 200A Bus / 200A Main | 40 A | 50 A | Needs Derate / Tap 705.11 |
| 200A Bus / 175A Main | 65 A | 50 A | PASS (120% Rule) |
| 225A Bus / 200A Main | 70 A | 50 A | PASS (120% Rule) |
Which CEC PV Module Strings Pair With GoodWe Technologies Co Ltd: GW8600A-BP {240V}?
Sample PV string lengths aligned within 200-495 V MPPT and 495 V DC max at -10 C. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 5 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 6 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 6 to 11 panels | 4.67 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 7 to 12 panels | 2.4 kW |
Which Competing Grid-Support Inverters Compare to GoodWe Technologies Co Ltd: GW8600A-BP {240V}?
Competing CEC grid-support inverters near 8,680 W AC and 240 V, led by ABB: UNO-86-TL-OUTD-S-US-A {240V}. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| ABB: UNO-86-TL-OUTD-S-US-A {240V} ABB |
8,600 W | -80 W | 240.0 V | 480.0 V | 97.03% |
| ABB: UNO-86-TL-OUTD-S-US-Z-A {240V} ABB |
8,600 W | -80 W | 240.0 V | 480.0 V | 97.03% |
| ABB: UNO-86-TL-OUTD-S-US-Z-M-A {240V} ABB |
8,600 W | -80 W | 240.0 V | 480.0 V | 97.03% |
| Afore New Energy Technology (Shanghai) Co Ltd: AF86K-DH {240V} Afore New Energy Technology (Shanghai) Co Ltd |
8,596 W | -84 W | 240.0 V | 480.0 V | 97.91% |
What Are the Interconnection Limits and Best-Fit Uses for GoodWe Technologies Co Ltd: GW8600A-BP {240V}?
Check GoodWe Technologies Co Ltd: GW8600A-BP {240V} (8,680 W AC, 50 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Its 50 A backfeed breaker exceeds a 200A/200A panel's 40 A ceiling, requiring a 175 A main derate, 225 A busbar, or NEC 705.11 tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 495 V DC on GoodWe Technologies Co Ltd: GW8600A-BP {240V}.
GoodWe Technologies Co Ltd: GW8600A-BP {240V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 50 A OCPD breaker (36.2 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.28%) and MPPT window (200-495 V) directly against ABB: UNO-86-TL-OUTD-S-US-A {240V} (8,600 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for GoodWe Technologies Co Ltd: GW8600A-BP {240V} by GoodWe Technologies Co Ltd covering breaker sizing, MPPT limits, and 240 V interconnection.
What breaker and wire size does GoodWe Technologies Co Ltd: GW8600A-BP {240V} require?
At 8,680 W continuous AC (240 V), continuous current is 36.2 A; 125% NEC 690.8/705.12 sizing requires a 50 A breaker and 8 AWG Cu (75 C) wire.
Does GoodWe Technologies Co Ltd: GW8600A-BP {240V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 50 A at 240 V means Needs Derate / Tap 705.11.
How does GoodWe Technologies Co Ltd: GW8600A-BP {240V} compare to ABB: UNO-86-TL-OUTD-S-US-A {240V}?
GoodWe Technologies Co Ltd: GW8600A-BP {240V} delivers 8,680 W AC at 96.28% CEC efficiency with a 495 V DC ceiling, while ABB: UNO-86-TL-OUTD-S-US-A {240V} outputs 8,600 W at 240 V.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)