Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} outputs 6,000 W AC at 240 V (25.0 A continuous, 35 A OCPD), ranking #932 of 2,343 CEC inverters at 97.06% efficiency with a 300-500 V MPPT window and 500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 6,000 W
- AC Voltage
- 240 V
- Min PV Breaker
- 35 A (8 AWG Cu)
- CEC Efficiency
- 97.06%
How Does Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} Compare Against Peer CEC Listings?
How Ginlong Technologies Co Ltd Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} compares on 97.06% efficiency, MPPT span, and 120% busbar interconnection.
With a 300-500 V MPPT tracking band and 500 V DC ceiling, Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} handles 6,000 W continuous AC (224 W above the 5,776 W 240 V median). Requires a 35 A breaker, passing directly inside a standard 200 A main / 200 A busbar panel (40 A limit). Installers comparing Ginlong Technologies Co Ltd against ABB: PVI-6000-OUTD-US-A {240V} (6,000 W) should verify whether listed since 2020-09-11 grid-support firmware meets local IEEE 1547 utility rules.
Where Does Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} Fall Across Listed CEC Models?
Position of Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} (6,000 W AC) relative to the 7,680 W CEC median inverter.
What Dataset Percentiles Define Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}?
Percentile placement of Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} across AC power class, conversion efficiency, and backfeed breaker size.
What Do the Dataset Ranks Show for Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}?
Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}.
97.06% CEC Weighted Efficiency
+0.38 pts vs the 96.68% 240 V median; overall power rank #1,387 (6,000 W, below CEC median; higher than 39.4% of peers).
35 A Required Backfeed OCPD
125% x 25.0 A = 31.2 A -> 35 A standard OCPD using 8 AWG Cu (75 C).
300 V - 500 V (Max 500 V DC)
Tracking span of 200.0 V; listed since 2020-09-11 (grid-tied PV inverter).
PASS (120% Rule)
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 6000.0W / 240 V -> 25.0 A | Breaker >= 1.25 * 25.0 = 31.2 A -> 35 A
CEC Inverters.csv for Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}: Paco=6000.0 W, Vac=240 V, Vdcmax=500.0 V, Eff=97.06%.
Result: Min 35 A breaker & 8 AWG Cu (75 C); 200A Bus / 200A Main: PASS (120% Rule).
What Are the Published CEC Specifications for Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}?
Official California Energy Commission electrical test parameters, AC voltage, and DC limits for Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 6,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 300 V - 500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 17.1718 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.06% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2020-09-11 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
Can a Residential Panel Meet 120% Busbar Limits for Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}?
Check whether Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} (35 A breaker) fits without main breaker derate or supply-side taps.
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 35 A | Needs Derate / Tap 705.11 |
| 150A Bus / 150A Main | 30 A | 35 A | Needs Derate / Tap 705.11 |
| 200A Bus / 200A Main | 40 A | 35 A | PASS (120% Rule) |
| 200A Bus / 175A Main | 65 A | 35 A | PASS (120% Rule) |
| 225A Bus / 200A Main | 70 A | 35 A | PASS (120% Rule) |
Which CEC PV Module Strings Pair With Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}?
Verified cold-weather (-10 C) series module counts matched to Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}'s 500 V DC ceiling.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 7 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 9 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 9 to 11 panels | 4.67 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 11 to 12 panels | 2.4 kW |
Which Competing Grid-Support Inverters Compare to Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}?
Alternative CEC inverters comparable to Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}, including ABB: PVI-6000-OUTD-US-A {240V} (6,000 W) at 240 V.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| ABB: PVI-6000-OUTD-US-A {240V} ABB |
6,000 W | Tie (0 W) | 240.0 V | 480.0 V | 96.21% |
| ABB: PVI-6000-OUTD-US-Z-A {240V} ABB |
6,000 W | Tie (0 W) | 240.0 V | 480.0 V | 96.21% |
| ABB: PVI-6000-OUTD-US-Z-M-A {240V} ABB |
6,000 W | Tie (0 W) | 240.0 V | 480.0 V | 96.21% |
| ABB: UNO-DM-60-TL-PLUS-US-S-XRA {240V} ABB |
6,000 W | Tie (0 W) | 240.0 V | 480.0 V | 97.03% |
What Are the Interconnection Limits and Best-Fit Uses for Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}?
Check Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} (6,000 W AC, 35 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Requires a 35 A breaker, passing directly inside a standard 200 A main / 200 A busbar panel (40 A limit).
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 500 V DC on Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V}.
Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 35 A OCPD breaker (25.0 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.06%) and MPPT window (300-500 V) directly against ABB: PVI-6000-OUTD-US-A {240V} (6,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} by Ginlong Technologies Co Ltd covering breaker sizing, MPPT limits, and 240 V interconnection.
What breaker and wire size does Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} require?
At 6,000 W continuous AC (240 V), continuous current is 25.0 A; 125% NEC 690.8/705.12 sizing requires a 35 A breaker and 8 AWG Cu (75 C) wire.
Does Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 35 A at 240 V means PASS (120% Rule).
How does Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} compare to ABB: PVI-6000-OUTD-US-A {240V}?
Ginlong Technologies Co Ltd: Solis-1P6K2-4G-US {240V} delivers 6,000 W AC at 97.06% CEC efficiency with a 500 V DC ceiling, while ABB: PVI-6000-OUTD-US-A {240V} outputs 6,000 W at 240 V.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)