Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} outputs 29,834 W AC at 240 V, 3-phase (71.8 A continuous, 90 A OCPD), ranking #608 of 2,343 CEC inverters at 97.4% efficiency with a 500-850 V MPPT window and 850 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 29,834 W
- AC Voltage
- 240 V, 3-phase
- Min PV Breaker
- 90 A (3 AWG Cu)
- CEC Efficiency
- 97.4%
How Does Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 240 V, 3-phase grid-support overview for Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V}.
Ranking #576 of 2,343 CEC inverters (top 24.6%; higher than 75.4% of peers), Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} is a hybrid battery-capable inverter delivering 29,834 W continuous AC at 240 V, 3-phase (71.8 A continuous). Commercial 240 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (240V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 97.4% (+0.72 pts vs the 96.68% 240 V median) against peers like Amensolar Ess Co Ltd: N3H-X16US {240V} (16,199 W).
Where Does Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} Fall Across Listed CEC Models?
Marks Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} (29,834 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V}?
Benchmarks Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} continuous AC output, 97.4% CEC weighted efficiency, and 90 A OCPD breaker demand.
What Do the Dataset Ranks Show for Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V}?
Four key NEC 705.12 and California Energy Commission metrics defining Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} by Ginlong Technologies Co Ltd.
97.4% CEC Weighted Efficiency
+0.72 pts vs the 96.68% 240 V median; overall power rank #576 (29,834 W, top 24.6%; higher than 75.4% of peers).
90 A Required Backfeed OCPD
125% x 71.8 A = 89.8 A -> 90 A standard OCPD using 3 AWG Cu (75 C).
500 V - 850 V (Max 850 V DC)
Tracking span of 350.0 V; active in CEC directory (hybrid battery-capable inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 240 V, 3-phase switchgear (200A Bus / 200A Main (240V) to 1,200A Bus / 1,200A Main (240V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 29834.2W / 240 V 3-phase -> 71.8 A | Breaker >= 1.25 * 71.8 = 89.8 A -> 90 A
CEC Inverters.csv for Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V}: Paco=29834.2 W, Vac=240 V, Vdcmax=850.0 V, Eff=97.4%.
Result: Min 90 A breaker & 3 AWG Cu (75 C); 1,200A Bus / 1,200A Main (240V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 29,834 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 850 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 500 V - 850 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 45.3798 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.4% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} (240 V, 3-phase)?
Evaluates Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} (90 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (240V) | 40 A | 90 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (240V) | 80 A | 90 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (240V) | 120 A | 90 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (240V) | 160 A | 90 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (240V) | 240 A | 90 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V}?
Sample PV string lengths aligned within 500-850 V MPPT and 850 V DC max at -10 C. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 12 to 15 panels | 8.85 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 15 to 20 panels | 8.8 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 15 to 18 panels | 7.65 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 18 to 20 panels | 4.0 kW |
Which Competing Grid-Support Inverters Compare to Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V}?
Competing CEC grid-support inverters near 29,834 W AC and 240 V, 3-phase, led by Amensolar Ess Co Ltd: N3H-X16US {240V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Amensolar Ess Co Ltd: N3H-X16US {240V} Amensolar Ess Co Ltd |
16,199 W | -13635 W | 240.0 V | 430.0 V | 96.25% |
| Amensolar Ess Co Ltd: N3H-X12US {240V} Amensolar Ess Co Ltd |
12,214 W | -17620 W | 240.0 V | 430.0 V | 96.17% |
| Chint Power Systems America: CPS ECH12KTL/US {240V} Chint Power Systems America |
11,990 W | -17844 W | 240.0 V | 480.0 V | 96.59% |
| Delta Electronics: S12_BDI {240V} Delta Electronics |
11,589 W | -18246 W | 240.0 V | 480.0 V | 96.99% |
What Are the Interconnection Limits and Best-Fit Uses for Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V}?
Check Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} (29,834 W AC, 90 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 240 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (240V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 850 V DC on Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V}.
Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} Panel & Wire Spec
Size 75 C copper conductors at 3 AWG Cu on a 90 A OCPD breaker (71.8 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.4%) and MPPT window (500-850 V) directly against Amensolar Ess Co Ltd: N3H-X16US {240V} (16,199 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} by Ginlong Technologies Co Ltd covering breaker sizing, MPPT limits, and 240 V, 3-phase interconnection.
What breaker and wire size does Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} require?
At 29,834 W continuous AC (240 V, 3-phase), continuous current is 71.8 A; 125% NEC 690.8/705.12 sizing requires a 90 A breaker and 3 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} require?
At 29,834 W AC and 240 V, 3-phase, continuous line current is 71.8 A, requiring a 90 A OCPD and 1,200A Bus / 1,200A Main (240V) or NEC 705.11 interconnection.
How does Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} compare to Amensolar Ess Co Ltd: N3H-X16US {240V}?
Ginlong Technologies Co Ltd: S6-EH3P30K03-LV-YD-H-US(21A) {240V} delivers 29,834 W AC at 97.4% CEC efficiency with a 850 V DC ceiling, while Amensolar Ess Co Ltd: N3H-X16US {240V} outputs 16,199 W at 240 V, 3-phase.