Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} outputs 10,005 W AC at 240 V (41.7 A continuous, 60 A OCPD), ranking #663 of 2,343 CEC inverters at 97.34% efficiency with a 230-450 V MPPT window and 450 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 10,005 W
- AC Voltage
- 240 V
- Min PV Breaker
- 60 A (6 AWG Cu)
- CEC Efficiency
- 97.34%
How Does Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} Compare Against Peer CEC Listings?
Breaker sizing (60 A), 6 AWG Cu wire rules, and DC input limits for Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V}.
Classified as a hybrid battery-capable inverter (listed since 2020-10-01), Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} requires 52.1 A design capacity -> 60 A breaker using 6 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 97.34% (+0.52 pts vs overall CEC median) across 2,343 CEC models, while its 60 a backfeed breaker exceeds a 200a/200a panel's 40 a ceiling, requiring a 175 a main derate, 225 a busbar, or nec 705.11 tap.
Where Does Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} Fall Across Listed CEC Models?
Output power comparison showing where Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V}?
Relative ranking of Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V}?
Snapshot of Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} efficiency rank (#663), OCPD breaker size, MPPT span, and busbar verdict.
97.34% CEC Weighted Efficiency
+0.66 pts vs the 96.68% 240 V median; overall power rank #905 (10,005 W, top 38.6%; higher than 61.4% of peers).
60 A Required Backfeed OCPD
125% x 41.7 A = 52.1 A -> 60 A standard OCPD using 6 AWG Cu (75 C).
230 V - 450 V (Max 450 V DC)
Tracking span of 220.0 V; listed since 2020-10-01 (hybrid battery-capable inverter).
Needs Derate / Tap 705.11
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 10005.0W / 240 V -> 41.7 A | Breaker >= 1.25 * 41.7 = 52.1 A -> 60 A
CEC Inverters.csv for Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V}: Paco=10005.0 W, Vac=240 V, Vdcmax=450.0 V, Eff=97.34%.
Result: Min 60 A breaker & 6 AWG Cu (75 C); 200A Bus / 200A Main: Needs Derate / Tap 705.11.
What Are the Published CEC Specifications for Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 10,005 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 450 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 230 V - 450 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 31.1477 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.34% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2020-10-01 / Hybrid: Yes (Battery Capable) | Utility interconnection approval metadata |
Can a Residential Panel Meet 120% Busbar Limits for Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V}?
NEC 705.12(B)(3)(2) backfeed compliance table for Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} at 240 V.
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 60 A | Needs Derate / Tap 705.11 |
| 150A Bus / 150A Main | 30 A | 60 A | Needs Derate / Tap 705.11 |
| 200A Bus / 200A Main | 40 A | 60 A | Needs Derate / Tap 705.11 |
| 200A Bus / 175A Main | 65 A | 60 A | PASS (120% Rule) |
| 225A Bus / 200A Main | 70 A | 60 A | PASS (120% Rule) |
Which CEC PV Module Strings Pair With Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V}?
Minimum and maximum series solar module strings fitting Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} MPPT and 450 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 6 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 7 to 10 panels | 4.4 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 7 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 8 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V}?
Peer 240 V CEC inverters near 10,005 W AC output such as Base Power Inc: MIN 10000TL-XH-US {240V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Base Power Inc: MIN 10000TL-XH-US {240V} Base Power Inc |
10,082 W | +77 W | 240.0 V | 480.0 V | 97.61% |
| Amensolar Ess Co Ltd: N3H-X100-US {240V} Amensolar Ess Co Ltd |
10,177 W | +172 W | 240.0 V | 430.0 V | 97.15% |
| Amensolar Ess Co Ltd: N3H-X10US {240V} Amensolar Ess Co Ltd |
10,177 W | +172 W | 240.0 V | 430.0 V | 97.15% |
| Delta Electronics: E10_BDI {240V} Delta Electronics |
9,674 W | -331 W | 240.0 V | 480.0 V | 97.21% |
What Are the Interconnection Limits and Best-Fit Uses for Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V}?
Check Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} (10,005 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Its 60 A backfeed breaker exceeds a 200A/200A panel's 40 A ceiling, requiring a 175 A main derate, 225 A busbar, or NEC 705.11 tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 450 V DC on Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V}.
Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} Panel & Wire Spec
Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (41.7 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.34%) and MPPT window (230-450 V) directly against Base Power Inc: MIN 10000TL-XH-US {240V} (10,082 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} by Ginlong Technologies Co Ltd covering breaker sizing, MPPT limits, and 240 V interconnection.
What breaker and wire size does Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} require?
At 10,005 W continuous AC (240 V), continuous current is 41.7 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.
Does Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 60 A at 240 V means Needs Derate / Tap 705.11.
How does Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} compare to Base Power Inc: MIN 10000TL-XH-US {240V}?
Ginlong Technologies Co Ltd: RHI-1P10K-HVES-5G {240V} delivers 10,005 W AC at 97.34% CEC efficiency with a 450 V DC ceiling, while Base Power Inc: MIN 10000TL-XH-US {240V} outputs 10,082 W at 240 V.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)