FranklinWH Energy Storage Inc: aPower Syyy {240V} outputs 9,776 W AC at 240 V (40.7 A continuous, 60 A OCPD), ranking #511 of 2,343 CEC inverters at 97.6% efficiency with a 250-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 9,776 W
- AC Voltage
- 240 V
- Min PV Breaker
- 60 A (6 AWG Cu)
- CEC Efficiency
- 97.6%
How Does FranklinWH Energy Storage Inc: aPower Syyy {240V} Compare Against Peer CEC Listings?
CEC efficiency rank (#511), 250-480 V MPPT tracking, and panel fit for FranklinWH Energy Storage Inc: aPower Syyy {240V}.
Operating at 240 V, FranklinWH Energy Storage Inc: aPower Syyy {240V} converts DC array energy at 97.6% CEC weighted efficiency (top 22.0%; higher than 78.0% of peers) with a 480 V max DC input and 25.041 A max input current for NEC 690.7 string safety. Compare this 9,776 W hybrid battery-capable inverter directly with Delta Electronics: E10_BDI {240V} (9,674 W). Its 60 A backfeed breaker exceeds a 200A/200A panel's 40 A ceiling, requiring a 175 A main derate, 225 A busbar, or NEC 705.11 tap.
Where Does FranklinWH Energy Storage Inc: aPower Syyy {240V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting FranklinWH Energy Storage Inc: aPower Syyy {240V} at 9,776 W continuous AC output.
What Dataset Percentiles Define FranklinWH Energy Storage Inc: aPower Syyy {240V}?
Dataset percentiles comparing FranklinWH Energy Storage Inc: aPower Syyy {240V} against 2,343 certified grid-support inverters nationwide. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
What Do the Dataset Ranks Show for FranklinWH Energy Storage Inc: aPower Syyy {240V}?
Engineering highlights for FranklinWH Energy Storage Inc: aPower Syyy {240V} covering efficiency, 6 AWG Cu feeder, and panel compatibility.
97.6% CEC Weighted Efficiency
+0.92 pts vs the 96.68% 240 V median; overall power rank #944 (9,776 W, top 40.3%; higher than 59.7% of peers).
60 A Required Backfeed OCPD
125% x 40.7 A = 50.9 A -> 60 A standard OCPD using 6 AWG Cu (75 C).
250 V - 480 V (Max 480 V DC)
Tracking span of 230.0 V; active in CEC directory (hybrid battery-capable inverter).
Needs Derate / Tap 705.11
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 9776.4W / 240 V -> 40.7 A | Breaker >= 1.25 * 40.7 = 50.9 A -> 60 A
CEC Inverters.csv for FranklinWH Energy Storage Inc: aPower Syyy {240V}: Paco=9776.4 W, Vac=240 V, Vdcmax=480.0 V, Eff=97.6%.
Result: Min 60 A breaker & 6 AWG Cu (75 C); 200A Bus / 200A Main: Needs Derate / Tap 705.11.
What Are the Published CEC Specifications for FranklinWH Energy Storage Inc: aPower Syyy {240V}?
California Energy Commission Solar Equipment List parameters for FranklinWH Energy Storage Inc: aPower Syyy {240V} (hybrid battery-capable inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 9,776 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 250 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 25.041 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.6% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: Yes (Battery Capable) | CEC Solar Equipment List grid-support certification |
Can a Residential Panel Meet 120% Busbar Limits for FranklinWH Energy Storage Inc: aPower Syyy {240V}?
Panelboard and switchgear backfeed allowances for FranklinWH Energy Storage Inc: aPower Syyy {240V} (60 A OCPD). Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 60 A | Needs Derate / Tap 705.11 |
| 150A Bus / 150A Main | 30 A | 60 A | Needs Derate / Tap 705.11 |
| 200A Bus / 200A Main | 40 A | 60 A | Needs Derate / Tap 705.11 |
| 200A Bus / 175A Main | 65 A | 60 A | PASS (120% Rule) |
| 225A Bus / 200A Main | 70 A | 60 A | PASS (120% Rule) |
Which CEC PV Module Strings Pair With FranklinWH Energy Storage Inc: aPower Syyy {240V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for FranklinWH Energy Storage Inc: aPower Syyy {240V}.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 6 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 8 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 8 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 9 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to FranklinWH Energy Storage Inc: aPower Syyy {240V}?
Four alternative CEC inverters matched to FranklinWH Energy Storage Inc: aPower Syyy {240V} (9,776 W AC), led by Delta Electronics: E10_BDI {240V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Delta Electronics: E10_BDI {240V} Delta Electronics |
9,674 W | -102 W | 240.0 V | 480.0 V | 97.21% |
| Delta Electronics: E10-TL-US {240V} Delta Electronics |
9,674 W | -102 W | 240.0 V | 480.0 V | 97.21% |
| Delta Electronics: M10-4-TL-US {240V} Delta Electronics |
9,674 W | -102 W | 240.0 V | 480.0 V | 97.21% |
| Dyness Digital Energy Technology Co LTD: TX96K-AM {240V} Dyness Digital Energy Technology Co LTD |
9,662 W | -114 W | 240.0 V | 490.0 V | 96.46% |
What Are the Interconnection Limits and Best-Fit Uses for FranklinWH Energy Storage Inc: aPower Syyy {240V}?
Check FranklinWH Energy Storage Inc: aPower Syyy {240V} (9,776 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Its 60 A backfeed breaker exceeds a 200A/200A panel's 40 A ceiling, requiring a 175 A main derate, 225 A busbar, or NEC 705.11 tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on FranklinWH Energy Storage Inc: aPower Syyy {240V}.
FranklinWH Energy Storage Inc: aPower Syyy {240V} Panel & Wire Spec
Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (40.7 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.6%) and MPPT window (250-480 V) directly against Delta Electronics: E10_BDI {240V} (9,674 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for FranklinWH Energy Storage Inc: aPower Syyy {240V} by FranklinWH Energy Storage Inc covering breaker sizing, MPPT limits, and 240 V interconnection.
What breaker and wire size does FranklinWH Energy Storage Inc: aPower Syyy {240V} require?
At 9,776 W continuous AC (240 V), continuous current is 40.7 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.
Does FranklinWH Energy Storage Inc: aPower Syyy {240V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 60 A at 240 V means Needs Derate / Tap 705.11.
How does FranklinWH Energy Storage Inc: aPower Syyy {240V} compare to Delta Electronics: E10_BDI {240V}?
FranklinWH Energy Storage Inc: aPower Syyy {240V} delivers 9,776 W AC at 97.6% CEC efficiency with a 480 V DC ceiling, while Delta Electronics: E10_BDI {240V} outputs 9,674 W at 240 V.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)