Enphase Energy Inc: IQ8X-80-M-US {208V} outputs 360 W AC at 208 V, commercial single-phase (1.7 A continuous, 15 A OCPD), ranking #1,922 of 2,343 CEC inverters at 96.07% efficiency with a 43-60 V MPPT window and 60 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 360 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 15 A (14 AWG Cu)
- CEC Efficiency
- 96.07%
How Does Enphase Energy Inc: IQ8X-80-M-US {208V} Compare Against Peer CEC Listings?
Breaker sizing (15 A), 14 AWG Cu wire rules, and DC input limits for Enphase Energy Inc: IQ8X-80-M-US {208V}.
For NEC 705.12 solar interconnection, Enphase Energy Inc: IQ8X-80-M-US {208V} outputs 1.7 A continuous AC at 208 V, commercial single-phase and needs a 15 A backfeed breaker on 14 AWG Cu (75 C). Module-level microinverter output eliminates high-voltage DC rooftop strings and connects via a 240V AC trunk circuit. Conversion efficiency scores 96.07% (#1,922 of 2,343, -0.75 pts vs overall CEC median).
Where Does Enphase Energy Inc: IQ8X-80-M-US {208V} Fall Across Listed CEC Models?
Output power comparison showing where Enphase Energy Inc: IQ8X-80-M-US {208V} sits among all 2,343 CEC-listed grid-support inverters. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.
What Dataset Percentiles Define Enphase Energy Inc: IQ8X-80-M-US {208V}?
Relative ranking of Enphase Energy Inc: IQ8X-80-M-US {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Enphase Energy Inc: IQ8X-80-M-US {208V}?
Snapshot of Enphase Energy Inc: IQ8X-80-M-US {208V} efficiency rank (#1,922), OCPD breaker size, MPPT span, and busbar verdict.
96.07% CEC Weighted Efficiency
-0.34 pts vs the 96.41% 208 V median; overall power rank #2,038 (360 W, below CEC median; higher than 12.9% of peers).
15 A Required Backfeed OCPD
125% x 1.7 A = 2.1 A -> 15 A standard OCPD using 14 AWG Cu (75 C).
43 V - 60 V (Max 60 V DC)
Tracking span of 17.0 V; listed since 2025-06-23 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 360.0W / 208 V -> 1.7 A | Breaker >= 1.25 * 1.7 = 2.1 A -> 15 A
CEC Inverters.csv for Enphase Energy Inc: IQ8X-80-M-US {208V}: Paco=360.0 W, Vac=208 V, Vdcmax=60.0 V, Eff=96.07%.
Result: Min 15 A breaker & 14 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Enphase Energy Inc: IQ8X-80-M-US {208V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Enphase Energy Inc: IQ8X-80-M-US {208V}. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 360 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 60 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 43 V - 60 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 7.27619 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.07% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2025-06-23 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Enphase Energy Inc: IQ8X-80-M-US {208V} (208 V, commercial single-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Enphase Energy Inc: IQ8X-80-M-US {208V} at 208 V, commercial single-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 15 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (208V) | 80 A | 15 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 15 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 15 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 15 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Enphase Energy Inc: IQ8X-80-M-US {208V}?
Minimum and maximum series solar module strings fitting Enphase Energy Inc: IQ8X-80-M-US {208V} MPPT and 60 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 1 panel (micro/module) | 0.59 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 1 panel (micro/module) | 0.44 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 1 panel (micro/module) | 0.42 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 1 panel (micro/module) | 0.2 kW |
Which Competing Grid-Support Inverters Compare to Enphase Energy Inc: IQ8X-80-M-US {208V}?
Peer 208 V, commercial single-phase CEC inverters near 360 W AC output such as Aptos Solar Technology LLC: MAC-400 {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Aptos Solar Technology LLC: MAC-400 {208V} Aptos Solar Technology LLC |
387 W | +27 W | 208.0 V | 48.0 V | 96.11% |
| Aptos Solar Technology LLC: MAC-400R {208V} Aptos Solar Technology LLC |
387 W | +27 W | 208.0 V | 48.0 V | 96.11% |
| Chilicon Power LLC: CP-250E-60/72-208/240-MC4 {208V} Chilicon Power LLC |
277 W | -83 W | 208.0 V | 32.0 V | 95.08% |
| Cherry Solution Co Ltd: CMI-600S-SA {208V} Cherry Solution Co Ltd |
608 W | +248 W | 208.0 V | 50.0 V | 96.49% |
What Are the Interconnection Limits and Best-Fit Uses for Enphase Energy Inc: IQ8X-80-M-US {208V}?
Check Enphase Energy Inc: IQ8X-80-M-US {208V} (360 W AC, 15 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Module-level microinverter output eliminates high-voltage DC rooftop strings and connects via a 240V AC trunk circuit.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 60 V DC on Enphase Energy Inc: IQ8X-80-M-US {208V}.
Enphase Energy Inc: IQ8X-80-M-US {208V} Panel & Wire Spec
Size 75 C copper conductors at 14 AWG Cu on a 15 A OCPD breaker (1.7 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.07%) and MPPT window (43-60 V) directly against Aptos Solar Technology LLC: MAC-400 {208V} (387 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Enphase Energy Inc: IQ8X-80-M-US {208V} by Enphase Energy Inc covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does Enphase Energy Inc: IQ8X-80-M-US {208V} require?
At 360 W continuous AC (208 V, commercial single-phase), continuous current is 1.7 A; 125% NEC 690.8/705.12 sizing requires a 15 A breaker and 14 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Enphase Energy Inc: IQ8X-80-M-US {208V} require?
At 360 W AC and 208 V, commercial single-phase, continuous line current is 1.7 A, requiring a 15 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does Enphase Energy Inc: IQ8X-80-M-US {208V} compare to Aptos Solar Technology LLC: MAC-400 {208V}?
Enphase Energy Inc: IQ8X-80-M-US {208V} delivers 360 W AC at 96.07% CEC efficiency with a 60 V DC ceiling, while Aptos Solar Technology LLC: MAC-400 {208V} outputs 387 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)