Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} outputs 293 W AC at 208 V, commercial single-phase (1.4 A continuous, 15 A OCPD), ranking #1,719 of 2,343 CEC inverters at 96.35% efficiency with a 38-43 V MPPT window and 43 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 293 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 15 A (14 AWG Cu)
- CEC Efficiency
- 96.35%
How Does Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 208 V, commercial single-phase grid-support overview for Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V}.
Rated at 293 W AC (1.4 A continuous), Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} ranks #1,719 of 2,343 CEC units at 96.35% efficiency (-0.06 pts vs the 96.41% 208 V median). Minimum 75 C copper conductor sizing for its 15 A circuit is 14 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 43 V DC at record local winter lows.
Where Does Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} Fall Across Listed CEC Models?
Marks Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} (293 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V}?
Benchmarks Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} continuous AC output, 96.35% CEC weighted efficiency, and 15 A OCPD breaker demand.
What Do the Dataset Ranks Show for Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V}?
Four key NEC 705.12 and California Energy Commission metrics defining Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} by Enphase Energy Inc.
96.35% CEC Weighted Efficiency
-0.06 pts vs the 96.41% 208 V median; overall power rank #2,249 (293 W, below CEC median; higher than 4.0% of peers).
15 A Required Backfeed OCPD
125% x 1.4 A = 1.8 A -> 15 A standard OCPD using 14 AWG Cu (75 C).
38 V - 43 V (Max 43 V DC)
Tracking span of 5.0 V; listed since 2020-11-12 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 292.9W / 208 V -> 1.4 A | Breaker >= 1.25 * 1.4 = 1.8 A -> 15 A
CEC Inverters.csv for Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V}: Paco=292.9 W, Vac=208 V, Vdcmax=43.0 V, Eff=96.35%.
Result: Min 15 A breaker & 14 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 293 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 43 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 38 V - 43 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 7.50662 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 96.35% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2020-11-12 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} (208 V, commercial single-phase)?
Evaluates Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} (15 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 15 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (208V) | 80 A | 15 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 15 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 15 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 15 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V}?
Sample PV string lengths aligned within 38-43 V MPPT and 43 V DC max at -10 C. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 1 panel (micro/module) | 0.44 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 1 panel (micro/module) | 0.2 kW |
| Hanwha Qcells (Qidong) Co Ltd HSL60P6-PB-0-270TW | 270.0 W | 42.56 V | 1 panel (micro/module) | 0.27 kW |
Which Competing Grid-Support Inverters Compare to Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V}?
Competing CEC grid-support inverters near 293 W AC and 208 V, commercial single-phase, led by Chilicon Power LLC: CP-250E-60/72-208/240-MC4 {208V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Chilicon Power LLC: CP-250E-60/72-208/240-MC4 {208V} Chilicon Power LLC |
277 W | -16 W | 208.0 V | 32.0 V | 95.08% |
| Aptos Solar Technology LLC: MAC-400 {208V} Aptos Solar Technology LLC |
387 W | +94 W | 208.0 V | 48.0 V | 96.11% |
| Aptos Solar Technology LLC: MAC-400R {208V} Aptos Solar Technology LLC |
387 W | +94 W | 208.0 V | 48.0 V | 96.11% |
| Cherry Solution Co Ltd: CMI-600S-SA {208V} Cherry Solution Co Ltd |
608 W | +315 W | 208.0 V | 50.0 V | 96.49% |
What Are the Interconnection Limits and Best-Fit Uses for Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V}?
Check Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} (293 W AC, 15 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Module-level microinverter output eliminates high-voltage DC rooftop strings and connects via a 240V AC trunk circuit.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 43 V DC on Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V}.
Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} Panel & Wire Spec
Size 75 C copper conductors at 14 AWG Cu on a 15 A OCPD breaker (1.4 A continuous).
Alternative Inverter Comparison
Compare efficiency (96.35%) and MPPT window (38-43 V) directly against Chilicon Power LLC: CP-250E-60/72-208/240-MC4 {208V} (277 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} by Enphase Energy Inc covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} require?
At 293 W continuous AC (208 V, commercial single-phase), continuous current is 1.4 A; 125% NEC 690.8/705.12 sizing requires a 15 A breaker and 14 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} require?
At 293 W AC and 208 V, commercial single-phase, continuous line current is 1.4 A, requiring a 15 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} compare to Chilicon Power LLC: CP-250E-60/72-208/240-MC4 {208V}?
Enphase Energy Inc: IQ7A-66-x-ACM-US-y-z-& {208V} delivers 293 W AC at 96.35% CEC efficiency with a 43 V DC ceiling, while Chilicon Power LLC: CP-250E-60/72-208/240-MC4 {208V} outputs 277 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)