CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} outputs 49,916 W AC at 480 V, 3-phase (60.0 A continuous, 80 A OCPD), ranking #175 of 2,343 CEC inverters at 98.32% efficiency with a 568-850 V MPPT window and 850 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 49,916 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 80 A (4 AWG Cu)
- CEC Efficiency
- 98.32%
How Does CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} Compare Against Peer CEC Listings?
Breaker sizing (80 A), 4 AWG Cu wire rules, and DC input limits for CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V}.
For NEC 705.12 solar interconnection, CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} outputs 60.0 A continuous AC at 480 V, 3-phase and needs an 80 A backfeed breaker on 4 AWG Cu (75 C). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Conversion efficiency scores 98.32% (#175 of 2,343, +1.50 pts vs overall CEC median).
Where Does CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} Fall Across Listed CEC Models?
Output power comparison showing where CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V}?
Relative ranking of CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V}?
Snapshot of CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} efficiency rank (#175), OCPD breaker size, MPPT span, and busbar verdict.
98.32% CEC Weighted Efficiency
+0.30 pts vs the 98.02% 480 V median; overall power rank #455 (49,916 W, top 19.5%; higher than 80.5% of peers).
80 A Required Backfeed OCPD
125% x 60.0 A = 75.0 A -> 80 A standard OCPD using 4 AWG Cu (75 C).
568 V - 850 V (Max 850 V DC)
Tracking span of 282.0 V; listed since 2021-12-01 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 49916.0W / 480 V 3-phase -> 60.0 A | Breaker >= 1.25 * 60.0 = 75.0 A -> 80 A
CEC Inverters.csv for CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V}: Paco=49916.0 W, Vac=480 V, Vdcmax=850.0 V, Eff=98.32%.
Result: Min 80 A breaker & 4 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 49,916 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 850 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 568 V - 850 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 70.5089 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.32% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2021-12-01 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} (480 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} at 480 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 80 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 80 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 80 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 80 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 80 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V}?
Minimum and maximum series solar module strings fitting CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} MPPT and 850 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 14 to 15 panels | 8.85 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 17 to 20 panels | 8.8 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 17 to 18 panels | 7.65 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 20 panels (fixed) | 4.0 kW |
Which Competing Grid-Support Inverters Compare to CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V}?
Peer 480 V, 3-phase CEC inverters near 49,916 W AC output such as Ginlong Technologies Co Ltd: Solis-50K-US-F-LSW {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Ginlong Technologies Co Ltd: Solis-50K-US-F-LSW {480V} Ginlong Technologies Co Ltd |
49,916 W | Tie (0 W) | 480.0 V | 850.0 V | 98.32% |
| Ginlong Technologies Co Ltd: Solis-50K-US-LSW {480V} Ginlong Technologies Co Ltd |
49,984 W | +68 W | 480.0 V | 850.0 V | 98.33% |
| Ginlong Technologies Co Ltd: S6-GC50K-US {480V} Ginlong Technologies Co Ltd |
49,848 W | -68 W | 480.0 V | 850.0 V | 98.29% |
| ABB: TRIO-500-TL-OUTD-US-480 {480V} ABB |
50,000 W | +84 W | 480.0 V | 800.0 V | 98.27% |
What Are the Interconnection Limits and Best-Fit Uses for CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V}?
Check CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} (49,916 W AC, 80 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 850 V DC on CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V}.
CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} Panel & Wire Spec
Size 75 C copper conductors at 4 AWG Cu on an 80 A OCPD breaker (60.0 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.32%) and MPPT window (568-850 V) directly against Ginlong Technologies Co Ltd: Solis-50K-US-F-LSW {480V} (49,916 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} by CSI Solar Co Ltd covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} require?
At 49,916 W continuous AC (480 V, 3-phase), continuous current is 60.0 A; 125% NEC 690.8/705.12 sizing requires an 80 A breaker and 4 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} require?
At 49,916 W AC and 480 V, 3-phase, continuous line current is 60.0 A, requiring an 80 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} compare to Ginlong Technologies Co Ltd: Solis-50K-US-F-LSW {480V}?
CSI Solar Co Ltd: CSI-50K-T480GL01-UB {480V} delivers 49,916 W AC at 98.32% CEC efficiency with a 850 V DC ceiling, while Ginlong Technologies Co Ltd: Solis-50K-US-F-LSW {480V} outputs 49,916 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)