SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} outputs 1,751,510 W AC at 690 V, 3-phase (1465.6 A continuous, 1,850 A OCPD), ranking #101 of 2,343 CEC inverters at 98.44% efficiency with a 1,000-1,500 V MPPT window and 1,500 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 1,751,510 W
- AC Voltage
- 690 V, 3-phase
- Min PV Breaker
- 1,850 A (parallel Cu feeders)
- CEC Efficiency
- 98.44%
How Does SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} Compare Against Peer CEC Listings?
Breaker sizing (1,850 A), parallel Cu feeders wire rules, and DC input limits for SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V}.
For NEC 705.12 solar interconnection, SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} outputs 1465.6 A continuous AC at 690 V, 3-phase and needs a 1,850 A backfeed breaker on parallel Cu feeders (75 C). Commercial 690 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (690V) or NEC 705.11 supply-side tap. Conversion efficiency scores 98.44% (#101 of 2,343, +1.62 pts vs overall CEC median).
Where Does SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} Fall Across Listed CEC Models?
Output power comparison showing where SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V}?
Relative ranking of SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V}?
Snapshot of SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} efficiency rank (#101), OCPD breaker size, MPPT span, and busbar verdict.
98.44% CEC Weighted Efficiency
+0.27 pts vs the 98.17% 690 V median; overall power rank #110 (1,751,510 W, top 4.7%; higher than 95.3% of peers).
1,850 A Required Backfeed OCPD
125% x 1465.6 A = 1832.0 A -> 1,850 A standard OCPD using parallel Cu feeders (75 C).
1,000 V - 1,500 V (Max 1,500 V DC)
Tracking span of 500.0 V; active in CEC directory (grid-tied PV inverter).
Supply-Side Tap (705.11) / Dedicated Switchboard
Evaluated for 690 V, 3-phase switchgear (200A Bus / 200A Main (690V) to 1,200A Bus / 1,200A Main (690V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 1751510.0W / 690 V 3-phase -> 1465.6 A | Breaker >= 1.25 * 1465.6 = 1832.0 A -> 1,850 A
CEC Inverters.csv for SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V}: Paco=1751510.0 W, Vac=690 V, Vdcmax=1500.0 V, Eff=98.44%.
Result: Min 1,850 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (690V): Supply-Side Tap (705.11) / Dedicated Switchboard.
What Are the Published CEC Specifications for SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 1,751,510 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 690 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 1,500 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 1,000 V - 1,500 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 1547.14 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.44% | Calculated AC/DC conversion ratio from CEC test protocol |
| Inverter Topology | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |
What Switchgear Limits Apply to SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} (690 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} at 690 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (690V) | 40 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (690V) | 80 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 600A Bus / 600A Main (690V) | 120 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 800A Bus / 800A Main (690V) | 160 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 1,200A Bus / 1,200A Main (690V) | 240 A | 1,850 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
Which CEC PV Module Strings Pair With SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V}?
Minimum and maximum series solar module strings fitting SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} MPPT and 1,500 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 24 to 26 panels | 15.34 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 30 to 35 panels | 15.4 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 30 to 33 panels | 14.03 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 35 to 36 panels | 7.2 kW |
Which Competing Grid-Support Inverters Compare to SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V}?
Peer 690 V, 3-phase CEC inverters near 1,751,510 W AC output such as Sungrow Power Supply Co Ltd: SC1725UD-US {690V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Sungrow Power Supply Co Ltd: SC1725UD-US {690V} Sungrow Power Supply Co Ltd |
1,728,406 W | -23104 W | 690.0 V | 1500.0 V | 98.38% |
| SINENG ELECTRIC CO LTD: EH-1725-HA-UD-US {690V} SINENG ELECTRIC CO LTD |
1,726,700 W | -24810 W | 690.0 V | 1500.0 V | 98.32% |
| Delta Electronics: EPCS-1725US {690V} Delta Electronics |
1,725,451 W | -26059 W | 690.0 V | 1500.0 V | 98.25% |
| Shenzhen Sinexcel Electric Co Ltd: PWS1-1725KTL-H-NA-8M8 {690V} Shenzhen Sinexcel Electric Co Ltd |
1,710,710 W | -40800 W | 690.0 V | 1450.0 V | 92.8% |
What Are the Interconnection Limits and Best-Fit Uses for SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V}?
Check SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} (1,751,510 W AC, 1,850 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 690 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (690V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,500 V DC on SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V}.
SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} Panel & Wire Spec
Size 75 C copper conductors at parallel Cu feeders on a 1,850 A OCPD breaker (1465.6 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.44%) and MPPT window (1,000-1,500 V) directly against Sungrow Power Supply Co Ltd: SC1725UD-US {690V} (1,728,406 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} by SYL (NINGBO) Battery Co Ltd covering breaker sizing, MPPT limits, and 690 V, 3-phase interconnection.
What breaker and wire size does SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} require?
At 1,751,510 W continuous AC (690 V, 3-phase), continuous current is 1465.6 A; 125% NEC 690.8/705.12 sizing requires a 1,850 A breaker and parallel Cu feeders (75 C) wire.
What commercial switchgear or feeder sizing does SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} require?
At 1,751,510 W AC and 690 V, 3-phase, continuous line current is 1465.6 A, requiring a 1,850 A OCPD and 1,200A Bus / 1,200A Main (690V) or NEC 705.11 interconnection.
How does SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} compare to Sungrow Power Supply Co Ltd: SC1725UD-US {690V}?
SYL (NINGBO) Battery Co Ltd: SP1750UHL {690V} delivers 1,751,510 W AC at 98.44% CEC efficiency with a 1,500 V DC ceiling, while Sungrow Power Supply Co Ltd: SC1725UD-US {690V} outputs 1,728,406 W at 690 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)