Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} outputs 3,802 W AC at 240 V (15.8 A continuous, 20 A OCPD), ranking #630 of 2,343 CEC inverters at 97.38% efficiency with a 200-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 3,802 W
- AC Voltage
- 240 V
- Min PV Breaker
- 20 A (12 AWG Cu)
- CEC Efficiency
- 97.38%
How Does Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} Compare Against Peer CEC Listings?
CEC efficiency rank (#630), 200-480 V MPPT tracking, and panel fit for Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V}.
Operating at 240 V, Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} converts DC array energy at 97.38% CEC weighted efficiency (top 27.2%; higher than 72.8% of peers) with a 480 V max DC input and 9.76072 A max input current for NEC 690.7 string safety. Compare this 3,802 W hybrid battery-capable inverter directly with ABB: PVI-38-OUTD-S-US-A {240V} (3,800 W). Requires a 20 A breaker, passing directly inside a standard 200 A main / 200 A busbar panel (40 A limit).
Where Does Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} Fall Across Listed CEC Models?
CEC inverter wattage histogram highlighting Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} at 3,802 W continuous AC output.
What Dataset Percentiles Define Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V}?
Dataset percentiles comparing Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} against 2,343 certified grid-support inverters nationwide.
What Do the Dataset Ranks Show for Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V}?
Engineering highlights for Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} covering efficiency, 12 AWG Cu feeder, and panel compatibility.
97.38% CEC Weighted Efficiency
+0.70 pts vs the 96.68% 240 V median; overall power rank #1,647 (3,802 W, below CEC median; higher than 29.7% of peers).
20 A Required Backfeed OCPD
125% x 15.8 A = 19.8 A -> 20 A standard OCPD using 12 AWG Cu (75 C).
200 V - 480 V (Max 480 V DC)
Tracking span of 280.0 V; listed since 2025-05-01 (hybrid battery-capable inverter).
PASS (120% Rule)
200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 3802.0W / 240 V -> 15.8 A | Breaker >= 1.25 * 15.8 = 19.8 A -> 20 A
CEC Inverters.csv for Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V}: Paco=3802.0 W, Vac=240 V, Vdcmax=480.0 V, Eff=97.38%.
Result: Min 20 A breaker & 12 AWG Cu (75 C); 200A Bus / 200A Main: PASS (120% Rule).
What Are the Published CEC Specifications for Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V}?
California Energy Commission Solar Equipment List parameters for Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} (hybrid battery-capable inverter) interconnection.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 3,802 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 200 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 9.76072 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.38% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2025-05-01 / Hybrid: Yes (Battery Capable) | Utility interconnection approval metadata |
Can a Residential Panel Meet 120% Busbar Limits for Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V}?
Panelboard and switchgear backfeed allowances for Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} (20 A OCPD).
| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 100A Bus / 100A Main | 20 A | 20 A | PASS (120% Rule) |
| 150A Bus / 150A Main | 30 A | 20 A | PASS (120% Rule) |
| 200A Bus / 200A Main | 40 A | 20 A | PASS (120% Rule) |
| 200A Bus / 175A Main | 65 A | 20 A | PASS (120% Rule) |
| 225A Bus / 200A Main | 70 A | 20 A | PASS (120% Rule) |
Which CEC PV Module Strings Pair With Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V}?
Representative PV panel pairings verified under NEC 690.7 cold Voc for Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V}.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 5 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 6 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 6 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 7 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V}?
Four alternative CEC inverters matched to Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} (3,802 W AC), led by ABB: PVI-38-OUTD-S-US-A {240V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| ABB: PVI-38-OUTD-S-US-A {240V} ABB |
3,800 W | -2 W | 240.0 V | 480.0 V | 96.2% |
| ABB: PVI-38-OUTD-S-US-Z-A {240V} ABB |
3,800 W | -2 W | 240.0 V | 480.0 V | 96.2% |
| ABB: PVI-38-OUTD-S-US-Z-M-A {240V} ABB |
3,800 W | -2 W | 240.0 V | 480.0 V | 96.2% |
| ABB: UNO-DM-38-TL-PLUS-US-SB-RA {240V} ABB |
3,800 W | -2 W | 240.0 V | 480.0 V | 96.39% |
What Are the Interconnection Limits and Best-Fit Uses for Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V}?
Check Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} (3,802 W AC, 20 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Requires a 20 A breaker, passing directly inside a standard 200 A main / 200 A busbar panel (40 A limit).
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V}.
Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} Panel & Wire Spec
Size 75 C copper conductors at 12 AWG Cu on a 20 A OCPD breaker (15.8 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.38%) and MPPT window (200-480 V) directly against ABB: PVI-38-OUTD-S-US-A {240V} (3,800 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} by Fronius International GmbH covering breaker sizing, MPPT limits, and 240 V interconnection.
What breaker and wire size does Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} require?
At 3,802 W continuous AC (240 V), continuous current is 15.8 A; 125% NEC 690.8/705.12 sizing requires a 20 A breaker and 12 AWG Cu (75 C) wire.
Does Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} fit a 200 A main panel under the 120% busbar rule?
A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 20 A at 240 V means PASS (120% Rule).
How does Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} compare to ABB: PVI-38-OUTD-S-US-A {240V}?
Fronius International GmbH: Primo GEN24 38 208-240 Plus {240V} delivers 3,802 W AC at 97.38% CEC efficiency with a 480 V DC ceiling, while ABB: PVI-38-OUTD-S-US-A {240V} outputs 3,800 W at 240 V.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)