Fronius International GmbH: Primo GEN24 38 208-240 {208V} outputs 3,805 W AC at 208 V, commercial single-phase (18.3 A continuous, 25 A OCPD), ranking #1,014 of 2,343 CEC inverters at 97.0% efficiency with a 200-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 3,805 W
- AC Voltage
- 208 V, commercial single-phase
- Min PV Breaker
- 25 A (10 AWG Cu)
- CEC Efficiency
- 97.0%
How Does Fronius International GmbH: Primo GEN24 38 208-240 {208V} Compare Against Peer CEC Listings?
Breaker sizing (25 A), 10 AWG Cu wire rules, and DC input limits for Fronius International GmbH: Primo GEN24 38 208-240 {208V}.
Classified as a hybrid battery-capable inverter (listed since 2025-05-01), Fronius International GmbH: Primo GEN24 38 208-240 {208V} requires 22.9 A design capacity -> 25 A breaker using 10 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 97.0% (+0.18 pts vs overall CEC median) across 2,343 CEC models, while commercial 208 v, commercial single-phase switchgear interconnection uses 1,200a bus / 1,200a main (208v) or nec 705.11 supply-side tap.
Where Does Fronius International GmbH: Primo GEN24 38 208-240 {208V} Fall Across Listed CEC Models?
Output power comparison showing where Fronius International GmbH: Primo GEN24 38 208-240 {208V} sits among all 2,343 CEC-listed grid-support inverters.
What Dataset Percentiles Define Fronius International GmbH: Primo GEN24 38 208-240 {208V}?
Relative ranking of Fronius International GmbH: Primo GEN24 38 208-240 {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Fronius International GmbH: Primo GEN24 38 208-240 {208V}?
Snapshot of Fronius International GmbH: Primo GEN24 38 208-240 {208V} efficiency rank (#1,014), OCPD breaker size, MPPT span, and busbar verdict.
97.0% CEC Weighted Efficiency
+0.59 pts vs the 96.41% 208 V median; overall power rank #1,643 (3,805 W, below CEC median; higher than 29.7% of peers).
25 A Required Backfeed OCPD
125% x 18.3 A = 22.9 A -> 25 A standard OCPD using 10 AWG Cu (75 C).
200 V - 480 V (Max 480 V DC)
Tracking span of 280.0 V; listed since 2025-05-01 (hybrid battery-capable inverter).
PASS (120% Commercial Busbar)
Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 3805.0W / 208 V -> 18.3 A | Breaker >= 1.25 * 18.3 = 22.9 A -> 25 A
CEC Inverters.csv for Fronius International GmbH: Primo GEN24 38 208-240 {208V}: Paco=3805.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=97.0%.
Result: Min 25 A breaker & 10 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Fronius International GmbH: Primo GEN24 38 208-240 {208V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Fronius International GmbH: Primo GEN24 38 208-240 {208V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 3,805 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 200 V - 480 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 10.8962 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.0% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2025-05-01 / Hybrid: Yes (Battery Capable) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Fronius International GmbH: Primo GEN24 38 208-240 {208V} (208 V, commercial single-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Fronius International GmbH: Primo GEN24 38 208-240 {208V} at 208 V, commercial single-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (208V) | 40 A | 25 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (208V) | 80 A | 25 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (208V) | 120 A | 25 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (208V) | 160 A | 25 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (208V) | 240 A | 25 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Fronius International GmbH: Primo GEN24 38 208-240 {208V}?
Minimum and maximum series solar module strings fitting Fronius International GmbH: Primo GEN24 38 208-240 {208V} MPPT and 480 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 5 to 8 panels | 4.72 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 6 to 11 panels | 4.84 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 6 to 10 panels | 4.25 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 7 to 11 panels | 2.2 kW |
Which Competing Grid-Support Inverters Compare to Fronius International GmbH: Primo GEN24 38 208-240 {208V}?
Peer 208 V, commercial single-phase CEC inverters near 3,805 W AC output such as ABB: PVI-38-OUTD-S-US-A {208V}. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| ABB: PVI-38-OUTD-S-US-A {208V} ABB |
3,800 W | -5 W | 208.0 V | 480.0 V | 95.65% |
| ABB: PVI-38-OUTD-S-US-Z-A {208V} ABB |
3,800 W | -5 W | 208.0 V | 480.0 V | 95.65% |
| ABB: PVI-38-OUTD-S-US-Z-M-A {208V} ABB |
3,800 W | -5 W | 208.0 V | 480.0 V | 95.65% |
| ABB: PVI-36-OUTD-S-US-A {208V} ABB |
3,600 W | -205 W | 208.0 V | 480.0 V | 95.81% |
What Are the Interconnection Limits and Best-Fit Uses for Fronius International GmbH: Primo GEN24 38 208-240 {208V}?
Check Fronius International GmbH: Primo GEN24 38 208-240 {208V} (3,805 W AC, 25 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on Fronius International GmbH: Primo GEN24 38 208-240 {208V}.
Fronius International GmbH: Primo GEN24 38 208-240 {208V} Panel & Wire Spec
Size 75 C copper conductors at 10 AWG Cu on a 25 A OCPD breaker (18.3 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.0%) and MPPT window (200-480 V) directly against ABB: PVI-38-OUTD-S-US-A {208V} (3,800 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Fronius International GmbH: Primo GEN24 38 208-240 {208V} by Fronius International GmbH covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.
What breaker and wire size does Fronius International GmbH: Primo GEN24 38 208-240 {208V} require?
At 3,805 W continuous AC (208 V, commercial single-phase), continuous current is 18.3 A; 125% NEC 690.8/705.12 sizing requires a 25 A breaker and 10 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Fronius International GmbH: Primo GEN24 38 208-240 {208V} require?
At 3,805 W AC and 208 V, commercial single-phase, continuous line current is 18.3 A, requiring a 25 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.
How does Fronius International GmbH: Primo GEN24 38 208-240 {208V} compare to ABB: PVI-38-OUTD-S-US-A {208V}?
Fronius International GmbH: Primo GEN24 38 208-240 {208V} delivers 3,805 W AC at 97.0% CEC efficiency with a 480 V DC ceiling, while ABB: PVI-38-OUTD-S-US-A {208V} outputs 3,800 W at 208 V, commercial single-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)