Delta Electronics: M42U_120 {480V} — CEC Inverter Specifications

Manufacturer: Delta Electronics Registry: CEC Verified Engineering Specification

Delta Electronics: M42U_120 {480V} outputs 45,972 W AC at 480 V, 3-phase (55.3 A continuous, 70 A OCPD), ranking #394 of 2,343 CEC inverters at 97.87% efficiency with a 545-830 V MPPT window and 830 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
45,972 W
AC Voltage
480 V, 3-phase
Min PV Breaker
70 A (4 AWG Cu)
CEC Efficiency
97.87%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Delta Electronics: M42U_120 {480V} Compare Against Peer CEC Listings?

Breaker sizing (70 A), 4 AWG Cu wire rules, and DC input limits for Delta Electronics: M42U_120 {480V}.

Classified as a grid-tied PV inverter (listed since 2020-11-12), Delta Electronics: M42U_120 {480V} requires 69.1 A design capacity -> 70 A breaker using 4 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 97.87% (+1.05 pts vs overall CEC median) across 2,343 CEC models, while commercial 480 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (480v) or nec 705.11 supply-side tap.

Where Does Delta Electronics: M42U_120 {480V} Fall Across Listed CEC Models?

Output power comparison showing where Delta Electronics: M42U_120 {480V} sits among all 2,343 CEC-listed grid-support inverters. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Delta Electronics: M42U_120 {480V} (45,972 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACDelta Electronics:: 45,972 W

What Dataset Percentiles Define Delta Electronics: M42U_120 {480V}?

Relative ranking of Delta Electronics: M42U_120 {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

Delta Electronics: M42U_120 {480V} Technical ThresholdsPercentile comparison for Delta Electronics: M42U_120 {480V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output45,972 WCEC Efficiency97.87%Backfeed Breaker70 A

What Do the Dataset Ranks Show for Delta Electronics: M42U_120 {480V}?

Snapshot of Delta Electronics: M42U_120 {480V} efficiency rank (#394), OCPD breaker size, MPPT span, and busbar verdict.

Eff #394 / 2,343

97.87% CEC Weighted Efficiency

-0.15 pts vs the 98.02% 480 V median; overall power rank #473 (45,972 W, top 20.3%; higher than 79.7% of peers).

NEC 705.12 Check

70 A Required Backfeed OCPD

125% x 55.3 A = 69.1 A -> 70 A standard OCPD using 4 AWG Cu (75 C).

MPPT Window

545 V - 830 V (Max 830 V DC)

Tracking span of 285.0 V; listed since 2020-11-12 (grid-tied PV inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 45972.0W / 480 V 3-phase -> 55.3 A | Breaker >= 1.25 * 55.3 = 69.1 A -> 70 A

CEC Inverters.csv for Delta Electronics: M42U_120 {480V}: Paco=45972.0 W, Vac=480 V, Vdcmax=830.0 V, Eff=97.87%.

Result: Min 70 A breaker & 4 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for Delta Electronics: M42U_120 {480V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Delta Electronics: M42U_120 {480V}. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Official California Energy Commission (NREL SAM) test parameters for Delta Electronics: M42U_120 {480V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 45,972 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 480 V, 3-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 830 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 545 V - 830 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 66.1599 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 97.87% Calculated AC/DC conversion ratio from CEC test protocol
CEC Listing Date & Hybrid 2020-11-12 / Hybrid: No (Grid-Tied PV) Utility interconnection approval metadata

What Switchgear Limits Apply to Delta Electronics: M42U_120 {480V} (480 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for Delta Electronics: M42U_120 {480V} at 480 V, 3-phase.

Evaluates Delta Electronics: M42U_120 {480V} (70 A required OCPD at 480 V, 3-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (480V) 40 A 70 A Supply-Side Tap (705.11) / Dedicated Switchboard
400A Bus / 400A Main (480V) 80 A 70 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (480V) 120 A 70 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (480V) 160 A 70 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (480V) 240 A 70 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With Delta Electronics: M42U_120 {480V}?

Minimum and maximum series solar module strings fitting Delta Electronics: M42U_120 {480V} MPPT and 830 V limits.

Sampled CEC PV modules aligned within 545.0-830.0 V MPPT and 830.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
AXITEC AC-590TGB/144TS 590.0 W 56.24 V 13 to 14 panels 8.26 kW
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 17 to 19 panels 8.36 kW
Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF 425.0 W 44.75 V 16 to 18 panels 7.65 kW
CSI Solar Co Ltd CS6P-200P 200.0 W 40.6 V 19 to 20 panels 4.0 kW

Which Competing Grid-Support Inverters Compare to Delta Electronics: M42U_120 {480V}?

Peer 480 V, 3-phase CEC inverters near 45,972 W AC output such as Ginlong Technologies Co Ltd: S6-EH3P50K04-NV-YD-H-US {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
Ginlong Technologies Co Ltd: S6-EH3P50K04-NV-YD-H-US {480V}
Ginlong Technologies Co Ltd
49,800 W +3828 W 480.0 V 850.0 V 97.14%
Fortress Power LLC: FP-Nano-50k-N {480V}
Fortress Power LLC
49,803 W +3831 W 480.0 V 850.0 V 97.41%
Ginlong Technologies Co Ltd: S6-EH3P50K04-NV-YD-H-US(21A) {480V}
Ginlong Technologies Co Ltd
49,803 W +3831 W 480.0 V 850.0 V 97.41%
CSI Solar Co Ltd: CSI-50K-T480GL03-U {480V}
CSI Solar Co Ltd
49,848 W +3876 W 480.0 V 850.0 V 98.29%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Delta Electronics: M42U_120 {480V}?

Check Delta Electronics: M42U_120 {480V} (45,972 W AC, 70 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 830 V DC on Delta Electronics: M42U_120 {480V}.

Delta Electronics: M42U_120 {480V} Panel & Wire Spec

Size 75 C copper conductors at 4 AWG Cu on a 70 A OCPD breaker (55.3 A continuous).

Alternative Inverter Comparison

Compare efficiency (97.87%) and MPPT window (545-830 V) directly against Ginlong Technologies Co Ltd: S6-EH3P50K04-NV-YD-H-US {480V} (49,800 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Delta Electronics: M42U_120 {480V} by Delta Electronics covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

What breaker and wire size does Delta Electronics: M42U_120 {480V} require?

At 45,972 W continuous AC (480 V, 3-phase), continuous current is 55.3 A; 125% NEC 690.8/705.12 sizing requires a 70 A breaker and 4 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does Delta Electronics: M42U_120 {480V} require?

At 45,972 W AC and 480 V, 3-phase, continuous line current is 55.3 A, requiring a 70 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

How does Delta Electronics: M42U_120 {480V} compare to Ginlong Technologies Co Ltd: S6-EH3P50K04-NV-YD-H-US {480V}?

Delta Electronics: M42U_120 {480V} delivers 45,972 W AC at 97.87% CEC efficiency with a 830 V DC ceiling, while Ginlong Technologies Co Ltd: S6-EH3P50K04-NV-YD-H-US {480V} outputs 49,800 W at 480 V, 3-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?