Delta Electronics: M42U_120 {480V} outputs 45,972 W AC at 480 V, 3-phase (55.3 A continuous, 70 A OCPD), ranking #394 of 2,343 CEC inverters at 97.87% efficiency with a 545-830 V MPPT window and 830 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 45,972 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 70 A (4 AWG Cu)
- CEC Efficiency
- 97.87%
How Does Delta Electronics: M42U_120 {480V} Compare Against Peer CEC Listings?
Breaker sizing (70 A), 4 AWG Cu wire rules, and DC input limits for Delta Electronics: M42U_120 {480V}.
Classified as a grid-tied PV inverter (listed since 2020-11-12), Delta Electronics: M42U_120 {480V} requires 69.1 A design capacity -> 70 A breaker using 4 AWG Cu copper at 75 C terminals. Weighted efficiency sits at 97.87% (+1.05 pts vs overall CEC median) across 2,343 CEC models, while commercial 480 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (480v) or nec 705.11 supply-side tap.
Where Does Delta Electronics: M42U_120 {480V} Fall Across Listed CEC Models?
Output power comparison showing where Delta Electronics: M42U_120 {480V} sits among all 2,343 CEC-listed grid-support inverters. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.
What Dataset Percentiles Define Delta Electronics: M42U_120 {480V}?
Relative ranking of Delta Electronics: M42U_120 {480V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.
What Do the Dataset Ranks Show for Delta Electronics: M42U_120 {480V}?
Snapshot of Delta Electronics: M42U_120 {480V} efficiency rank (#394), OCPD breaker size, MPPT span, and busbar verdict.
97.87% CEC Weighted Efficiency
-0.15 pts vs the 98.02% 480 V median; overall power rank #473 (45,972 W, top 20.3%; higher than 79.7% of peers).
70 A Required Backfeed OCPD
125% x 55.3 A = 69.1 A -> 70 A standard OCPD using 4 AWG Cu (75 C).
545 V - 830 V (Max 830 V DC)
Tracking span of 285.0 V; listed since 2020-11-12 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 45972.0W / 480 V 3-phase -> 55.3 A | Breaker >= 1.25 * 55.3 = 69.1 A -> 70 A
CEC Inverters.csv for Delta Electronics: M42U_120 {480V}: Paco=45972.0 W, Vac=480 V, Vdcmax=830.0 V, Eff=97.87%.
Result: Min 70 A breaker & 4 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Delta Electronics: M42U_120 {480V}?
Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Delta Electronics: M42U_120 {480V}. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 45,972 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 830 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 545 V - 830 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 66.1599 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 97.87% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2020-11-12 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Delta Electronics: M42U_120 {480V} (480 V, 3-phase)?
NEC 705.12(B)(3)(2) backfeed compliance table for Delta Electronics: M42U_120 {480V} at 480 V, 3-phase.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 70 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| 400A Bus / 400A Main (480V) | 80 A | 70 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 70 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 70 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 70 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Delta Electronics: M42U_120 {480V}?
Minimum and maximum series solar module strings fitting Delta Electronics: M42U_120 {480V} MPPT and 830 V limits.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 13 to 14 panels | 8.26 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 17 to 19 panels | 8.36 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 16 to 18 panels | 7.65 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 19 to 20 panels | 4.0 kW |
Which Competing Grid-Support Inverters Compare to Delta Electronics: M42U_120 {480V}?
Peer 480 V, 3-phase CEC inverters near 45,972 W AC output such as Ginlong Technologies Co Ltd: S6-EH3P50K04-NV-YD-H-US {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Ginlong Technologies Co Ltd: S6-EH3P50K04-NV-YD-H-US {480V} Ginlong Technologies Co Ltd |
49,800 W | +3828 W | 480.0 V | 850.0 V | 97.14% |
| Fortress Power LLC: FP-Nano-50k-N {480V} Fortress Power LLC |
49,803 W | +3831 W | 480.0 V | 850.0 V | 97.41% |
| Ginlong Technologies Co Ltd: S6-EH3P50K04-NV-YD-H-US(21A) {480V} Ginlong Technologies Co Ltd |
49,803 W | +3831 W | 480.0 V | 850.0 V | 97.41% |
| CSI Solar Co Ltd: CSI-50K-T480GL03-U {480V} CSI Solar Co Ltd |
49,848 W | +3876 W | 480.0 V | 850.0 V | 98.29% |
What Are the Interconnection Limits and Best-Fit Uses for Delta Electronics: M42U_120 {480V}?
Check Delta Electronics: M42U_120 {480V} (45,972 W AC, 70 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 830 V DC on Delta Electronics: M42U_120 {480V}.
Delta Electronics: M42U_120 {480V} Panel & Wire Spec
Size 75 C copper conductors at 4 AWG Cu on a 70 A OCPD breaker (55.3 A continuous).
Alternative Inverter Comparison
Compare efficiency (97.87%) and MPPT window (545-830 V) directly against Ginlong Technologies Co Ltd: S6-EH3P50K04-NV-YD-H-US {480V} (49,800 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Delta Electronics: M42U_120 {480V} by Delta Electronics covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Delta Electronics: M42U_120 {480V} require?
At 45,972 W continuous AC (480 V, 3-phase), continuous current is 55.3 A; 125% NEC 690.8/705.12 sizing requires a 70 A breaker and 4 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Delta Electronics: M42U_120 {480V} require?
At 45,972 W AC and 480 V, 3-phase, continuous line current is 55.3 A, requiring a 70 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Delta Electronics: M42U_120 {480V} compare to Ginlong Technologies Co Ltd: S6-EH3P50K04-NV-YD-H-US {480V}?
Delta Electronics: M42U_120 {480V} delivers 45,972 W AC at 97.87% CEC efficiency with a 830 V DC ceiling, while Ginlong Technologies Co Ltd: S6-EH3P50K04-NV-YD-H-US {480V} outputs 49,800 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)