Delta Electronics: M24U_122 {480V} outputs 26,403 W AC at 480 V, 3-phase (31.8 A continuous, 40 A OCPD), ranking #238 of 2,343 CEC inverters at 98.21% efficiency with a 415-830 V MPPT window and 830 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.
- AC Output (Paco)
- 26,403 W
- AC Voltage
- 480 V, 3-phase
- Min PV Breaker
- 40 A (8 AWG Cu)
- CEC Efficiency
- 98.21%
How Does Delta Electronics: M24U_122 {480V} Compare Against Peer CEC Listings?
NEC 705.12 breaker requirements, efficiency placement, and 480 V, 3-phase grid-support overview for Delta Electronics: M24U_122 {480V}.
Ranking #588 of 2,343 CEC inverters (top 25.2%; higher than 74.8% of peers), Delta Electronics: M24U_122 {480V} is a grid-tied PV inverter delivering 26,403 W continuous AC at 480 V, 3-phase (31.8 A continuous). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 98.21% (+0.19 pts vs the 98.02% 480 V median) against peers like Canadian Solar Inc: CSI-25KTL-GS-FL {480V} (25,000 W).
Where Does Delta Electronics: M24U_122 {480V} Fall Across Listed CEC Models?
Marks Delta Electronics: M24U_122 {480V} (26,403 W AC) across the California Energy Commission inverter AC capacity distribution.
What Dataset Percentiles Define Delta Electronics: M24U_122 {480V}?
Benchmarks Delta Electronics: M24U_122 {480V} continuous AC output, 98.21% CEC weighted efficiency, and 40 A OCPD breaker demand.
What Do the Dataset Ranks Show for Delta Electronics: M24U_122 {480V}?
Four key NEC 705.12 and California Energy Commission metrics defining Delta Electronics: M24U_122 {480V} by Delta Electronics.
98.21% CEC Weighted Efficiency
+0.19 pts vs the 98.02% 480 V median; overall power rank #588 (26,403 W, top 25.2%; higher than 74.8% of peers).
40 A Required Backfeed OCPD
125% x 31.8 A = 39.8 A -> 40 A standard OCPD using 8 AWG Cu (75 C).
415 V - 830 V (Max 830 V DC)
Tracking span of 415.0 V; listed since 2020-03-02 (grid-tied PV inverter).
PASS (120% Commercial Busbar)
Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.
NEC 705.12 Backfeed OCPD & 120% Busbar Formula
I_cont = 26403.0W / 480 V 3-phase -> 31.8 A | Breaker >= 1.25 * 31.8 = 39.8 A -> 40 A
CEC Inverters.csv for Delta Electronics: M24U_122 {480V}: Paco=26403.0 W, Vac=480 V, Vdcmax=830.0 V, Eff=98.21%.
Result: Min 40 A breaker & 8 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).
What Are the Published CEC Specifications for Delta Electronics: M24U_122 {480V}?
Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Delta Electronics: M24U_122 {480V}.
| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| Max Continuous AC Power (Paco) | 26,403 W | Determines required backfeed OCPD size via 125% continuous rule |
| Nominal AC Voltage (Vac) | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| Max DC Input Voltage (Vdcmax) | 830 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| MPPT Operating Range | 415 V - 830 V | Optimal DC string Vmp window for full power harvest |
| Max Input DC Current (Idcmax) | 37.8664 A | Used to verify parallel string combiner limits |
| CEC Weighted Efficiency | 98.21% | Calculated AC/DC conversion ratio from CEC test protocol |
| CEC Listing Date & Hybrid | 2020-03-02 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |
What Switchgear Limits Apply to Delta Electronics: M24U_122 {480V} (480 V, 3-phase)?
Evaluates Delta Electronics: M24U_122 {480V} (40 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.
| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| 200A Bus / 200A Main (480V) | 40 A | 40 A | PASS (120% Commercial Busbar) |
| 400A Bus / 400A Main (480V) | 80 A | 40 A | PASS (120% Commercial Busbar) |
| 600A Bus / 600A Main (480V) | 120 A | 40 A | PASS (120% Commercial Busbar) |
| 800A Bus / 800A Main (480V) | 160 A | 40 A | PASS (120% Commercial Busbar) |
| 1,200A Bus / 1,200A Main (480V) | 240 A | 40 A | PASS (120% Commercial Busbar) |
Which CEC PV Module Strings Pair With Delta Electronics: M24U_122 {480V}?
Sample PV string lengths aligned within 415-830 V MPPT and 830 V DC max at -10 C. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.
| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| AXITEC AC-590TGB/144TS | 590.0 W | 56.24 V | 10 to 14 panels | 8.26 kW |
| Aptos Solar Technology LLC DNA-108-MFN10-440W | 440.0 W | 42.15 V | 13 to 19 panels | 8.36 kW |
| Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF | 425.0 W | 44.75 V | 13 to 18 panels | 7.65 kW |
| CSI Solar Co Ltd CS6P-200P | 200.0 W | 40.6 V | 15 to 20 panels | 4.0 kW |
Which Competing Grid-Support Inverters Compare to Delta Electronics: M24U_122 {480V}?
Competing CEC grid-support inverters near 26,403 W AC and 480 V, 3-phase, led by Canadian Solar Inc: CSI-25KTL-GS-FL {480V}.
| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| Canadian Solar Inc: CSI-25KTL-GS-FL {480V} Canadian Solar Inc |
25,000 W | -1403 W | 480.0 V | 780.0 V | 97.73% |
| Chint Power Systems America: CPS SCA25KTL-DO-R/US-480 {480V} Chint Power Systems America |
25,000 W | -1403 W | 480.0 V | 850.0 V | 97.85% |
| CSI Solar Co Ltd: CSI-25KTL-GS-FLB {480V} CSI Solar Co Ltd |
25,000 W | -1403 W | 480.0 V | 770.0 V | 97.78% |
| CSI Solar Co Ltd: CSI-25K-T480GL01-UB {480V} CSI Solar Co Ltd |
24,958 W | -1445 W | 480.0 V | 800.0 V | 98.35% |
What Are the Interconnection Limits and Best-Fit Uses for Delta Electronics: M24U_122 {480V}?
Check Delta Electronics: M24U_122 {480V} (26,403 W AC, 40 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.
- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 830 V DC on Delta Electronics: M24U_122 {480V}.
Delta Electronics: M24U_122 {480V} Panel & Wire Spec
Size 75 C copper conductors at 8 AWG Cu on a 40 A OCPD breaker (31.8 A continuous).
Alternative Inverter Comparison
Compare efficiency (98.21%) and MPPT window (415-830 V) directly against Canadian Solar Inc: CSI-25KTL-GS-FL {480V} (25,000 W).
Which Homeowner Electrical & Solar Questions Come Up Most Often?
Answers for Delta Electronics: M24U_122 {480V} by Delta Electronics covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.
What breaker and wire size does Delta Electronics: M24U_122 {480V} require?
At 26,403 W continuous AC (480 V, 3-phase), continuous current is 31.8 A; 125% NEC 690.8/705.12 sizing requires a 40 A breaker and 8 AWG Cu (75 C) wire.
What commercial switchgear or feeder sizing does Delta Electronics: M24U_122 {480V} require?
At 26,403 W AC and 480 V, 3-phase, continuous line current is 31.8 A, requiring a 40 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.
How does Delta Electronics: M24U_122 {480V} compare to Canadian Solar Inc: CSI-25KTL-GS-FL {480V}?
Delta Electronics: M24U_122 {480V} delivers 26,403 W AC at 98.21% CEC efficiency with a 830 V DC ceiling, while Canadian Solar Inc: CSI-25KTL-GS-FL {480V} outputs 25,000 W at 480 V, 3-phase.
Sources
- CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
- NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)