Delta Electronics: E4-TL-US(AC) {208V} — CEC Inverter Specifications

Manufacturer: Delta Electronics Registry: CEC Verified Engineering Specification

Delta Electronics: E4-TL-US(AC) {208V} outputs 3,364 W AC at 208 V, commercial single-phase (16.2 A continuous, 25 A OCPD), ranking #290 of 2,343 CEC inverters at 98.11% efficiency with a 350-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

AC Output (Paco)
3,364 W
AC Voltage
208 V, commercial single-phase
Min PV Breaker
25 A (10 AWG Cu)
CEC Efficiency
98.11%
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit
Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

How Does Delta Electronics: E4-TL-US(AC) {208V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 208 V, commercial single-phase grid-support overview for Delta Electronics: E4-TL-US(AC) {208V}.

Ranking #1,699 of 2,343 CEC inverters (below CEC median; higher than 27.5% of peers), Delta Electronics: E4-TL-US(AC) {208V} is a grid-tied PV inverter delivering 3,364 W continuous AC at 208 V, commercial single-phase (16.2 A continuous). Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 98.11% (+1.70 pts vs the 96.41% 208 V median) against peers like ABB: UNO-DM-38-TL-PLUS-US-SB-RA {208V} (3,300 W).

Where Does Delta Electronics: E4-TL-US(AC) {208V} Fall Across Listed CEC Models?

Marks Delta Electronics: E4-TL-US(AC) {208V} (3,364 W AC) across the California Energy Commission inverter AC capacity distribution.

AC Power Distribution Across Listed CEC Inverters (up to 25 kW)Shows where Delta Electronics: E4-TL-US(AC) {208V} (3,364 W AC) sits across CEC inverters. 190-2258 W AC: 584 entries1902258-4325 W AC: 158 entries4325-6392 W AC: 259 entries6392-8460 W AC: 270 entries63928460-10528 W AC: 258 entries10528-12595 W AC: 116 entries12595-14662 W AC: 17 entries1259514662-16730 W AC: 37 entries16730-18798 W AC: 7 entries18798-20865 W AC: 11 entries1879820865-22932 W AC: 5 entries22932-25000 W AC: 26 entries22932Median 7,680 W ACDelta Electronics:: 3,364 W

What Dataset Percentiles Define Delta Electronics: E4-TL-US(AC) {208V}?

Benchmarks Delta Electronics: E4-TL-US(AC) {208V} continuous AC output, 98.11% CEC weighted efficiency, and 25 A OCPD breaker demand.

Delta Electronics: E4-TL-US(AC) {208V} Technical ThresholdsPercentile comparison for Delta Electronics: E4-TL-US(AC) {208V} AC output, weighted CEC efficiency, and OCPD sizing. 0% (Low)50% Median100% (Top)Rated AC Output3,364 WCEC Efficiency98.11%Backfeed Breaker25 A

What Do the Dataset Ranks Show for Delta Electronics: E4-TL-US(AC) {208V}?

Four key NEC 705.12 and California Energy Commission metrics defining Delta Electronics: E4-TL-US(AC) {208V} by Delta Electronics.

Eff #290 / 2,343

98.11% CEC Weighted Efficiency

+1.70 pts vs the 96.41% 208 V median; overall power rank #1,699 (3,364 W, below CEC median; higher than 27.5% of peers).

NEC 705.12 Check

25 A Required Backfeed OCPD

125% x 16.2 A = 20.2 A -> 25 A standard OCPD using 10 AWG Cu (75 C).

MPPT Window

350 V - 480 V (Max 480 V DC)

Tracking span of 130.0 V; listed since 2024-04-02 (grid-tied PV inverter).

Commercial / 3-Phase Fit

PASS (120% Commercial Busbar)

Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 3364.0W / 208 V -> 16.2 A | Breaker >= 1.25 * 16.2 = 20.2 A -> 25 A

CEC Inverters.csv for Delta Electronics: E4-TL-US(AC) {208V}: Paco=3364.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=98.11%.

Result: Min 25 A breaker & 10 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

What Are the Published CEC Specifications for Delta Electronics: E4-TL-US(AC) {208V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Delta Electronics: E4-TL-US(AC) {208V}.

Official California Energy Commission (NREL SAM) test parameters for Delta Electronics: E4-TL-US(AC) {208V}.
ParameterMeasured / Listed ValueEngineering Significance
Max Continuous AC Power (Paco) 3,364 W Determines required backfeed OCPD size via 125% continuous rule
Nominal AC Voltage (Vac) 208 V, commercial single-phase 240V split-phase residential vs. 208V/480V/MV commercial
Max DC Input Voltage (Vdcmax) 480 V Hard ceiling for cold-weather PV string Voc under NEC 690.7
MPPT Operating Range 350 V - 480 V Optimal DC string Vmp window for full power harvest
Max Input DC Current (Idcmax) 8.5722 A Used to verify parallel string combiner limits
CEC Weighted Efficiency 98.11% Calculated AC/DC conversion ratio from CEC test protocol
CEC Listing Date & Hybrid 2024-04-02 / Hybrid: No (Grid-Tied PV) Utility interconnection approval metadata

What Switchgear Limits Apply to Delta Electronics: E4-TL-US(AC) {208V} (208 V, commercial single-phase)?

Evaluates Delta Electronics: E4-TL-US(AC) {208V} (25 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates Delta Electronics: E4-TL-US(AC) {208V} (25 A required OCPD at 208 V, commercial single-phase) across standard distribution busbars.
Switchboard / Interconnect120% Max BackfeedRequired PV OCPDCompliance Verdict
200A Bus / 200A Main (208V) 40 A 25 A PASS (120% Commercial Busbar)
400A Bus / 400A Main (208V) 80 A 25 A PASS (120% Commercial Busbar)
600A Bus / 600A Main (208V) 120 A 25 A PASS (120% Commercial Busbar)
800A Bus / 800A Main (208V) 160 A 25 A PASS (120% Commercial Busbar)
1,200A Bus / 1,200A Main (208V) 240 A 25 A PASS (120% Commercial Busbar)

Which CEC PV Module Strings Pair With Delta Electronics: E4-TL-US(AC) {208V}?

Sample PV string lengths aligned within 350-480 V MPPT and 480 V DC max at -10 C. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Sampled CEC PV modules aligned within 350.0-480.0 V MPPT and 480.0 V max DC at -10 C.
CEC ModuleSTC (W)-10 C VocValid String RangeMax String DC
Aptos Solar Technology LLC DNA-108-MFN10-440W 440.0 W 42.15 V 11 panels (fixed) 4.84 kW

Which Competing Grid-Support Inverters Compare to Delta Electronics: E4-TL-US(AC) {208V}?

Competing CEC grid-support inverters near 3,364 W AC and 208 V, commercial single-phase, led by ABB: UNO-DM-38-TL-PLUS-US-SB-RA {208V}.

Alternative CEC inverters at comparable AC output power and voltage class.
Alternative InverterAC OutputDeltaVacMax DCCEC Eff
ABB: UNO-DM-38-TL-PLUS-US-SB-RA {208V}
ABB
3,300 W -64 W 208.0 V 480.0 V 95.88%
ABB: UNO-DM-38-TL-PLUS-US-SB-RA-Q {208V}
ABB
3,300 W -64 W 208.0 V 480.0 V 95.88%
ABB: UNO-DM-38-TL-PLUS-US-SE-RA {208V}
ABB
3,300 W -64 W 208.0 V 480.0 V 95.88%
ABB: UNO-DM-38-TL-PLUS-US-SZ-RA {208V}
ABB
3,300 W -64 W 208.0 V 480.0 V 95.88%
What to Check & Best-Fit Scenarios

What Are the Interconnection Limits and Best-Fit Uses for Delta Electronics: E4-TL-US(AC) {208V}?

Check Delta Electronics: E4-TL-US(AC) {208V} (3,364 W AC, 25 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

  • Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
  • Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
  • Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on Delta Electronics: E4-TL-US(AC) {208V}.

Delta Electronics: E4-TL-US(AC) {208V} Panel & Wire Spec

Size 75 C copper conductors at 10 AWG Cu on a 25 A OCPD breaker (16.2 A continuous).

Alternative Inverter Comparison

Compare efficiency (98.11%) and MPPT window (350-480 V) directly against ABB: UNO-DM-38-TL-PLUS-US-SB-RA {208V} (3,300 W).

Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Delta Electronics: E4-TL-US(AC) {208V} by Delta Electronics covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.

What breaker and wire size does Delta Electronics: E4-TL-US(AC) {208V} require?

At 3,364 W continuous AC (208 V, commercial single-phase), continuous current is 16.2 A; 125% NEC 690.8/705.12 sizing requires a 25 A breaker and 10 AWG Cu (75 C) wire.

What commercial switchgear or feeder sizing does Delta Electronics: E4-TL-US(AC) {208V} require?

At 3,364 W AC and 208 V, commercial single-phase, continuous line current is 16.2 A, requiring a 25 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

How does Delta Electronics: E4-TL-US(AC) {208V} compare to ABB: UNO-DM-38-TL-PLUS-US-SB-RA {208V}?

Delta Electronics: E4-TL-US(AC) {208V} delivers 3,364 W AC at 98.11% CEC efficiency with a 480 V DC ceiling, while ABB: UNO-DM-38-TL-PLUS-US-SB-RA {208V} outputs 3,300 W at 208 V, commercial single-phase.

Sources

  1. CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  2. CEC Solar Equipment List — PV Modules (NREL SAM Distribution) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
  3. NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Which Regional Electrical & Panel Upgrade Metros Compare Closest?

Check Wiring & Solar Numbers Before Getting Quotes

Verify panel capacity for solar, electrical box space, proper wire gauge for EV chargers, and 2026 home solar payback using local utility rates.

Verify State-Licensed Electricians & Safety Recalls

Look up active state electrician licenses (TX, WA, CO, OR, DE), check local power-outage history, and inspect federal product recall notices.