CEC PV Module

# Suntech Power STP260-24/Vd — CEC Solar Module Specifications

Manufacturer: [**Suntech Power**](https://epri-peac.com/solar-equipment/brands/suntech-power/) Registry: **CEC Verified Engineering Specification**

Suntech Power STP260-24/Vd is a 260.0 W STC (235.4 W PTC) Multi-c-Si solar module ranking #19,146 of 21,677 CEC listings (below all-CEC median; higher than 10.4% of peers). It delivers 13.4% efficiency, 44.0 V Voc at 25 C, and 48.82 V cold Voc at -10 C (12 panels max per 600 V string).

- **STC Wattage** : 260.0 W

- **PTC Wattage** : 235.4 W

- **Voc @ 25C** : 44.0 V

- **Efficiency** : 13.4%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Suntech Power STP260-24/Vd Compare Against Peer CEC Listings?

CEC rank, roof space requirements, and NEC 690.7/690.8 limits for Suntech Power STP260-24/Vd (Multi-c-Si) residential solar systems.

Homeowners evaluating Suntech Power STP260-24/Vd need 24 panels for 6 kW or 31 panels (647 sq ft) for an 8 kW array—useful on tight dormer roofs or battery cabins, though 8 kW requires 31 panels (647 sq ft). Under NEC 690.7(A), beta_Voc (-0.313%/C) pushes open-circuit voltage to 48.82 V at 14 F and 50.2 V at -4 F. Monofacial backsheet sealing targets flush dark shingle rooftop mounts.

## Where Does Suntech Power STP260-24/Vd Fall Across Listed CEC Models?

Comparison of Suntech Power STP260-24/Vd (260.0 W STC) against all 21,677 California Energy Commission certified photovoltaic modules.

## What Dataset Percentiles Define Suntech Power STP260-24/Vd?

Relative ranking of Suntech Power STP260-24/Vd across nameplate watts, 90.5% PTC thermal ratio, and module aperture efficiency.

## What Do the Dataset Ranks Show for Suntech Power STP260-24/Vd?

Summary of Suntech Power STP260-24/Vd output rank, 8 kW array size (31 panels), efficiency rating, and 600 V string limit.

Rank #19,146 / 21,677

### 260.0 W STC · Higher Than 10.4%

260.0 W STC (-125.0 W vs all-CEC median) vs 278.8 W Multi-c-Si median.

Eff #21,253

### 13.4% Aperture Efficiency

Power density 134.0 W/m2 (6.51 percentage points below 19.91% CEC median). PTC/STC ratio: 90.5% (rank #17,786).

NEC 690.7 Limit

### 12 Panels Max @ -10 C (600 V)

Cold Voc reaches 48.82 V at -10 C (585.8 V string) and 50.2 V at -20 C (11 max).

 8 kW Reference Array

### 31 Panels = 8,060 W STC

Occupies 60.1 m2 (647 sq ft) producing 7,297 W PTC; NEC 690.8 OCPD floor is 12.62 A (15 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 44.0 * (1 + (-0.313/100) * (-10 - 25)) = 48.82 V | OCPD = 1.56 * 8.09 = 12.62 A

Inputs from CEC Modules.csv for Suntech Power STP260-24/Vd: Voc=44.0 V, beta_Voc=-0.313%/C, Isc=8.09 A, STC=260.0 W, Area=1.94 m2.

**Result:** 12 panels max on 600 V (585.8 V); 31 panels for 8 kW (647 sq ft).

## What Are the Published CEC Specifications for Suntech Power STP260-24/Vd?

Complete CEC test sheet for Suntech Power STP260-24/Vd including Isc (8.09 A), Voc (44.0 V), and thermal temperature coefficients.

Official California Energy Commission (NREL SAM) test parameters for Suntech Power STP260-24/Vd.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Nameplate Power (STC)** | 260.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| **Real-World Output (PTC)** | 235.4 W (90.5% STC) | PVUSA Test Conditions rating used for utility interconnection |
| **Open-Circuit Voltage (Voc)** | 44.0 V | Primary cold-weather string sizing limit under NEC 690.7 |
| **Short-Circuit Current (Isc)** | 8.09 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| **Max Power Voltage / Current** | 34.8 V / 7.47 A | Inverter MPPT operating window alignment |
| **Voc Temp Coefficient (beta_Voc)** | -0.313 %/C | Negative slope governing voltage rise below 25C |
| **Module Efficiency & Area** | 13.4% (1.94 m2) | Array roof footprint density |
| **Cell Count & Technology** | 72 cells (Multi-c-Si) | Monofacial backsheet |

## How Many Suntech Power STP260-24/Vd Panels Build a 6 kW, 8 kW, or 10 kW Array?

Residential array count and annual electric bill savings at 18.54 c/kWh US avg vs. California tariffs using Suntech Power STP260-24/Vd.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).

| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| **6 kW Class** | 24 | 6.24 kW | 501 sq ft | $1,562 | $2,641 |
| **8 kW Class** | 31 | 8.06 kW | 647 sq ft | $2,017 | $3,411 |
| **10 kW Class** | 39 | 10.14 kW | 814 sq ft | $2,538 | $4,292 |

## Which Sibling Wattage & Trim Variants Belong to This Suntech Power Series?

Related Suntech Power power steps and black/silver trims consolidated into this Suntech Power STP260-24/Vd series guide.

Sibling CEC listings grouped into the Suntech Power STP260-24/Vd wattage tier to avoid duplicate 5W/trim datasheets.

| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| **Suntech Power STP260-24/Vd** | 260.0 W | 235.4 W | 44.0 V | 34.8 V | 13.4% |
| **Suntech Power STP270-24/Vd** | 270.0 W | 244.7 W | 44.5 V | 35.0 V | 13.92% |

## How Many Suntech Power STP260-24/Vd Modules Fit in a Cold-Weather String?

Verify freezing-morning voltage rise for Suntech Power STP260-24/Vd (44.0 V STC) before wiring 600 V or 1,000 V strings.

Computed from Voc=44.0V and beta_Voc=-0.313%/C across design ambient temperatures.

| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| **-20 C (-4 F)** | 50.2 V | 11 panels | 552.2 V | 19 panels |
| **-10 C (14 F)** | 48.82 V | 12 panels | 585.8 V | 20 panels |
| **0 C (32 F)** | 47.44 V | 12 panels | 569.3 V | 21 panels |
| **25 C (77 F STC)** | 44.0 V | 13 panels | 572.0 V | 22 panels |

## Which Cross-Brand Solar Modules Compare Closest to Suntech Power STP260-24/Vd?

Four comparable CEC modules such as Gintung Energy ASEC-260G6M (260.0 W) for side-by-side solar quote checks. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.

| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| [**Gintung Energy ASEC-260G6M**](https://epri-peac.com/solar-equipment/modules/gintung-energy/gintung-energy-asec-260g6m/) Gintung Energy | 260.0 W | Tie (0 W) | 43.84 V | 13.29% | 89.3% |
| [**CSI Solar Co Ltd CS6X-265P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6x-265p/) CSI Solar Co Ltd | 265.0 W | +5.0 W | 43.9 V | 14.31% | 88.8% |
| [**Gintung Energy ASEC-265G6S**](https://epri-peac.com/solar-equipment/modules/gintung-energy/gintung-energy-asec-265g6s/) Gintung Energy | 265.0 W | +5.0 W | 44.12 V | 13.55% | 89.5% |
| [**Advance Power API-P265**](https://epri-peac.com/solar-equipment/modules/advance-power/advance-power-api-p265/) Advance Power | 265.0 W | +5.0 W | 43.27 V | 13.58% | 89.1% |

What to Check & Best-Fit Scenarios

## What Are the Design Limits and Best-Fit Uses for Suntech Power STP260-24/Vd?

Evaluate Suntech Power STP260-24/Vd (260.0 W STC, 44.0 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

- Winter overvoltage boundary: at -20 C (-4 F), Suntech Power STP260-24/Vd reaches 50.2 V per panel—exceeding 11 panels in series voids 600 V inverter warranties.
- Footprint constraint: 31 panels for an 8 kW build require 647 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 31 panels (647 sq ft).
- 2026 tax credit baseline: cash residential installs of Suntech Power STP260-24/Vd carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

### Suntech Power STP260-24/Vd 8 kW Residential Fit

Needs 31 modules (647 sq ft) with a 15 A string OCPD, offsetting ~$2,017/yr at US average tariffs.

### Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 12 panels (-10 C) or 11 panels (-20 C), or compare Gintung Energy ASEC-260G6M.

### Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 235.4 W PTC.

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for Suntech Power STP260-24/Vd by Suntech Power grounded in CEC test data and NEC 690.7/690.8 limits.

### Why is Suntech Power STP260-24/Vd PTC wattage (235.4 W) lower than STC (260.0 W)?

Laboratory STC tests at 25 C cell temperature, whereas real rooftop heat lowers voltage to 235.4 W PTC (90.5% retention) across Suntech Power STP260-24/Vd's 1.94 m2 aperture.

### Who should skip Suntech Power STP260-24/Vd on a complex residential roof?

Homes with chopped dormers or heavy chimney shade should compare smaller modules or microinverters if 31 Suntech Power STP260-24/Vd panels (647 sq ft) leave unusable roof gaps vs. Gintung Energy ASEC-260G6M.

### What is the 1,000 V commercial string limit for Suntech Power STP260-24/Vd?

On 1,000 V commercial inverters at -10 C (48.82 V cold Voc), Suntech Power STP260-24/Vd fits up to 20 panels per series string. Review current municipal Authority Having Jurisdiction (AHJ) code amendments affecting Suntech Power STP260-24/Vd.

## Related Pages

Compare Suntech Power equipment, Gintung Energy ASEC-260G6M specs, utility payback rates, and NEC string calculators alongside Suntech Power STP260-24/Vd.

[All Suntech Power Certified Solar Models](https://epri-peac.com/solar-equipment/brands/suntech-power/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [Check NEC 705.12 120% Panel Busbar Backfeed Limit](https://epri-peac.com/tools/solar-busbar-120/)

## Sources

1. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- 6-10 kW Array Sizing
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Suntech Power

- [All Suntech Power Specs](https://epri-peac.com/solar-equipment/brands/suntech-power/)
- [Suntech Power STP330-24/Vem](https://epri-peac.com/solar-equipment/modules/suntech-power/suntech-power-stp330-24-vem/)
- [Suntech Power STP315-24/Vem](https://epri-peac.com/solar-equipment/modules/suntech-power/suntech-power-stp315-24-vem/)
- [Suntech Power STP310-24/Vd](https://epri-peac.com/solar-equipment/modules/suntech-power/suntech-power-stp310-24-vd/)
- [Suntech Power STP310-24/Vdx](https://epri-peac.com/solar-equipment/modules/suntech-power/suntech-power-stp310-24-vdx/)
- [Suntech Power STP310-24/Ve](https://epri-peac.com/solar-equipment/modules/suntech-power/suntech-power-stp310-24-ve/)