title: "Mitsubishi Electric PV-UD190HA6 Specs (190.0W, 30.5V Voc)"
url: https://epri-peac.com/solar-equipment/modules/mitsubishi-electric/mitsubishi-electric-pv-ud190ha6/
description: "CEC datasheet for Mitsubishi Electric PV-UD190HA6: 190.0W STC, 30.5V Voc, 43-panel 8kW sizing, and NEC 690.7 limits. Source-verified US engineering data."
---

CEC PV Module

# Mitsubishi Electric PV-UD190HA6 — CEC Solar Module Specifications

Manufacturer: [**Mitsubishi Electric**](https://epri-peac.com/solar-equipment/brands/mitsubishi-electric/) Registry: **CEC Verified Engineering Specification**

Mitsubishi Electric PV-UD190HA6 is a 190.0 W STC (174.3 W PTC) Multi-c-Si solar module ranking #21,132 of 21,677 CEC listings (below all-CEC median; higher than 2.3% of peers). It delivers 13.74% efficiency, 30.5 V Voc at 25 C, and 34.11 V cold Voc at -10 C (17 panels max per 600 V string).

- **STC Wattage** : 190.0 W

- **PTC Wattage** : 174.3 W

- **Voc @ 25C** : 30.5 V

- **Efficiency** : 13.74%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Mitsubishi Electric PV-UD190HA6 Compare Against Peer CEC Listings?

Solar engineering breakdown for Mitsubishi Electric PV-UD190HA6: PTC thermal retention, roof footprint, and cold Voc string bounds. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Measured at 190.0 W STC and 174.3 W PTC, Mitsubishi Electric PV-UD190HA6 sits -195.0 W vs all-CEC median (below all-CEC median; higher than 2.3% of peers) among 21,677 listed modules. Power density reaches 137.4 W/m2 (6.17 percentage points below 19.91% CEC median). Lower 30.5 V string voltage fits 17 panels in series at 14 F and pairs easily with microinverters, whereas 1,000 V commercial inverters handle up to 29 panels in series. Alternative peer Lightway Green New Energy LW190(23)P1310x990 rates 190.0 W.

## Where Does Mitsubishi Electric PV-UD190HA6 Fall Across Listed CEC Models?

Distribution marker showing Mitsubishi Electric PV-UD190HA6 (190.0 W) relative to the 385.0 W all-CEC solar panel median. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

## What Dataset Percentiles Define Mitsubishi Electric PV-UD190HA6?

Dataset percentiles tracking Mitsubishi Electric PV-UD190HA6 power output, thermal retention ratio, and aperture efficiency against 21,677 models. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

## What Do the Dataset Ranks Show for Mitsubishi Electric PV-UD190HA6?

Benchmark highlights for Mitsubishi Electric PV-UD190HA6 covering STC output, efficiency, 8 kW footprint, and OCPD breaker size. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Rank #21,132 / 21,677

### 190.0 W STC · Higher Than 2.3%

190.0 W STC (-195.0 W vs all-CEC median) vs 278.8 W Multi-c-Si median.

Eff #21,071

### 13.74% Aperture Efficiency

Power density 137.4 W/m2 (6.17 percentage points below 19.91% CEC median). PTC/STC ratio: 91.7% (rank #15,053).

NEC 690.7 Limit

### 17 Panels Max @ -10 C (600 V)

Cold Voc reaches 34.11 V at -10 C (579.9 V string) and 35.14 V at -20 C (17 max).

 8 kW Reference Array

### 43 Panels = 8,170 W STC

Occupies 59.5 m2 (640 sq ft) producing 7,495 W PTC; NEC 690.8 OCPD floor is 13.04 A (15 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 30.5 * (1 + (-0.338/100) * (-10 - 25)) = 34.11 V | OCPD = 1.56 * 8.36 = 13.04 A

Inputs from CEC Modules.csv for Mitsubishi Electric PV-UD190HA6: Voc=30.5 V, beta_Voc=-0.338%/C, Isc=8.36 A, STC=190.0 W, Area=1.383 m2.

**Result:** 17 panels max on 600 V (579.9 V); 43 panels for 8 kW (640 sq ft).

## What Are the Published CEC Specifications for Mitsubishi Electric PV-UD190HA6?

Official CEC datasheet figures for Mitsubishi Electric PV-UD190HA6 (Multi-c-Si) used in utility interconnection and permit reviews. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

Official California Energy Commission (NREL SAM) test parameters for Mitsubishi Electric PV-UD190HA6.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Nameplate Power (STC)** | 190.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| **Real-World Output (PTC)** | 174.3 W (91.7% STC) | PVUSA Test Conditions rating used for utility interconnection |
| **Open-Circuit Voltage (Voc)** | 30.5 V | Primary cold-weather string sizing limit under NEC 690.7 |
| **Short-Circuit Current (Isc)** | 8.36 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| **Max Power Voltage / Current** | 25.1 V / 7.56 A | Inverter MPPT operating window alignment |
| **Voc Temp Coefficient (beta_Voc)** | -0.338 %/C | Negative slope governing voltage rise below 25C |
| **Module Efficiency & Area** | 13.74% (1.383 m2) | Array roof footprint density |
| **Cell Count & Technology** | 50 cells (Multi-c-Si) | Monofacial backsheet |

## How Many Mitsubishi Electric PV-UD190HA6 Panels Build a 6 kW, 8 kW, or 10 kW Array?

How many Mitsubishi Electric PV-UD190HA6 modules and square feet are required for 6 kW, 8 kW, and 10 kW home solar arrays.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).

| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| **6 kW Class** | 32 | 6.08 kW | 476 sq ft | $1,522 | $2,573 |
| **8 kW Class** | 43 | 8.17 kW | 640 sq ft | $2,045 | $3,458 |
| **10 kW Class** | 53 | 10.07 kW | 789 sq ft | $2,520 | $4,262 |

## Which Sibling Wattage & Trim Variants Belong to This Mitsubishi Electric Series?

Consolidated Mitsubishi Electric wattage variants sharing the Mitsubishi Electric PV-UD190HA6 mechanical and cell layout. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Sibling CEC listings grouped into the Mitsubishi Electric PV-UD190HA6 wattage tier to avoid duplicate 5W/trim datasheets.

| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| **Mitsubishi Electric PV-UD185HA6** | 185.0 W | 169.6 W | 30.3 V | 24.9 V | 13.38% |
| **Mitsubishi Electric PV-UD190HA6** | 190.0 W | 174.3 W | 30.5 V | 25.1 V | 13.74% |
| **Mitsubishi Electric PV-UD195HA6** | 195.0 W | 179.0 W | 30.6 V | 25.4 V | 14.1% |

## How Many Mitsubishi Electric PV-UD190HA6 Modules Fit in a Cold-Weather String?

NEC 690.7(A) winter string table preventing overvoltage trips on Mitsubishi Electric PV-UD190HA6 (34.11 V at 14 F).

Computed from Voc=30.5V and beta_Voc=-0.338%/C across design ambient temperatures.

| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| **-20 C (-4 F)** | 35.14 V | 17 panels | 597.4 V | 28 panels |
| **-10 C (14 F)** | 34.11 V | 17 panels | 579.9 V | 29 panels |
| **0 C (32 F)** | 33.08 V | 18 panels | 595.4 V | 30 panels |
| **25 C (77 F STC)** | 30.5 V | 19 panels | 579.5 V | 32 panels |

## Which Cross-Brand Solar Modules Compare Closest to Mitsubishi Electric PV-UD190HA6?

Competing CEC solar panels closest to Mitsubishi Electric PV-UD190HA6 in nameplate wattage and Voc, starting with Lightway Green New Energy LW190(23)P1310x990.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.

| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| [**Lightway Green New Energy LW190(23)P1310x990**](https://epri-peac.com/solar-equipment/modules/lightway-green-new-energy/lightway-green-new-energy-lw190-23-p1310x990/) Lightway Green New Energy | 190.0 W | Tie (0 W) | 30.0 V | 14.8% | 89.6% |
| [**Perfect Source Technology PST 188 3GP48**](https://epri-peac.com/solar-equipment/modules/perfect-source-technology/perfect-source-technology-pst-188-3gp48/) Perfect Source Technology | 188.0 W | -2.0 W | 30.0 V | 14.02% | 89.3% |
| [**WAAREE ENERGIES LIMITED WU-190**](https://epri-peac.com/solar-equipment/modules/waaree-energies-limited/waaree-energies-limited-wu-190/) WAAREE ENERGIES LIMITED | 190.0 W | Tie (0 W) | 32.0 V | 12.88% | 88.8% |
| [**Lightway Green New Energy LW185(23)P1310x990**](https://epri-peac.com/solar-equipment/modules/lightway-green-new-energy/lightway-green-new-energy-lw185-23-p1310x990/) Lightway Green New Energy | 185.0 W | -5.0 W | 30.0 V | 14.41% | 89.6% |

What to Check & Best-Fit Scenarios

## What Are the Design Limits and Best-Fit Uses for Mitsubishi Electric PV-UD190HA6?

Evaluate Mitsubishi Electric PV-UD190HA6 (190.0 W STC, 30.5 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

- Winter overvoltage boundary: at -20 C (-4 F), Mitsubishi Electric PV-UD190HA6 reaches 35.14 V per panel—exceeding 17 panels in series voids 600 V inverter warranties.
- Footprint constraint: 43 panels for an 8 kW build require 640 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 43 panels (640 sq ft).
- 2026 tax credit baseline: cash residential installs of Mitsubishi Electric PV-UD190HA6 carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

### Mitsubishi Electric PV-UD190HA6 8 kW Residential Fit

Needs 43 modules (640 sq ft) with a 15 A string OCPD, offsetting ~$2,045/yr at US average tariffs.

### Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 17 panels (-10 C) or 17 panels (-20 C), or compare Lightway Green New Energy LW190(23)P1310x990.

### Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 174.3 W PTC.

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for Mitsubishi Electric PV-UD190HA6 by Mitsubishi Electric grounded in CEC test data and NEC 690.7/690.8 limits.

### How many Mitsubishi Electric PV-UD190HA6 panels fit on a 600 V winter solar string?

At -10 C (14 F), Mitsubishi Electric PV-UD190HA6 cold Voc rises from 30.5 V to 34.11 V (beta_Voc -0.338%/C), capping a 600 V string at 17 panels (579.9 V).

### How much roof area does an 8 kW array of Mitsubishi Electric PV-UD190HA6 need?

An 8 kW DC system uses 43 Mitsubishi Electric PV-UD190HA6 modules (8,170 W STC / 7,495 W PTC), covering roughly 640 sq ft and saving ~$2,045/yr at 18.54 c/kWh.

### How does Mitsubishi Electric PV-UD190HA6 compare against Lightway Green New Energy LW190(23)P1310x990?

Mitsubishi Electric PV-UD190HA6 outputs 190.0 W STC (30.5 V Voc, rank #21,132 of 21,677), while Lightway Green New Energy LW190(23)P1310x990 delivers 190.0 W STC; both comply with 2026 NEC 690.7 string sizing rules.

## Related Pages

Compare Mitsubishi Electric equipment, Lightway Green New Energy LW190(23)P1310x990 specs, utility payback rates, and NEC string calculators alongside Mitsubishi Electric PV-UD190HA6.

[All Mitsubishi Electric Certified Solar Models](https://epri-peac.com/solar-equipment/brands/mitsubishi-electric/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [Check NEC 705.12 120% Panel Busbar Backfeed Limit](https://epri-peac.com/tools/solar-busbar-120/)

## Sources

1. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- 6-10 kW Array Sizing
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Mitsubishi Electric

- [All Mitsubishi Electric Specs](https://epri-peac.com/solar-equipment/brands/mitsubishi-electric/)
- [Mitsubishi Electric PV-MJE280FB](https://epri-peac.com/solar-equipment/modules/mitsubishi-electric/mitsubishi-electric-pv-mje280fb/)
- [Mitsubishi Electric PV-MJE280FB-B](https://epri-peac.com/solar-equipment/modules/mitsubishi-electric/mitsubishi-electric-pv-mje280fb-b/)
- [Mitsubishi Electric PV-MLE280HD2](https://epri-peac.com/solar-equipment/modules/mitsubishi-electric/mitsubishi-electric-pv-mle280hd2/)
- [Mitsubishi Electric PV-MJE270FB](https://epri-peac.com/solar-equipment/modules/mitsubishi-electric/mitsubishi-electric-pv-mje270fb/)
- [Mitsubishi Electric PV-MLE270HD2](https://epri-peac.com/solar-equipment/modules/mitsubishi-electric/mitsubishi-electric-pv-mle270hd2/)