# LONGi Green Energy Technology Co Ltd LR4-60HPB-340M — CEC Solar Module Specifications

Manufacturer: [**LONGi Green Energy Technology Co Ltd**](https://epri-peac.com/solar-equipment/brands/longi-green-energy-technology-co-ltd/) Registry: **CEC Verified Engineering Specification**

LONGi Green Energy Technology Co Ltd LR4-60HPB-340M is a 340.0 W STC (316.8 W PTC) Mono-c-Si solar module ranking #13,575 of 21,677 CEC listings (below all-CEC median; higher than 36.1% of peers). It delivers 18.76% efficiency, 40.1 V Voc at 25 C, and 43.88 V cold Voc at -10 C (13 panels max per 600 V string).

- **STC Wattage** : 340.0 W

- **PTC Wattage** : 316.8 W

- **Voc @ 25C** : 40.1 V

- **Efficiency** : 18.76%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does LONGi Green Energy Technology Co Ltd LR4-60HPB-340M Compare Against Peer CEC Listings?

Engineering position of LONGi Green Energy Technology Co Ltd LR4-60HPB-340M (340.0 W STC) vs. DualSun SAS DualSun 340M-120-00 across 5,889 CEC Mono-c-Si solar modules.

Built with 60 Mono-c-Si cells, LONGi Green Energy Technology Co Ltd LR4-60HPB-340M pairs strong 93.2% PTC-to-STC heat retention (#8,924 of 21,677) with 40.1 V nominal Voc. An 8 kW residential build (8,160 W DC, 7,603 W PTC) saves ~$2,042/yr at 18.54 c/kWh with zero federal 25D credit in 2026. Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Peer DualSun SAS DualSun 340M-120-00 offers a 340.0 W alternative.

## Where Does LONGi Green Energy Technology Co Ltd LR4-60HPB-340M Fall Across Listed CEC Models?

Plots LONGi Green Energy Technology Co Ltd LR4-60HPB-340M at 340.0 W STC across all 21,677 California Energy Commission photovoltaic modules relative to the 385.0 W median.

## What Dataset Percentiles Define LONGi Green Energy Technology Co Ltd LR4-60HPB-340M?

Benchmarks LONGi Green Energy Technology Co Ltd LR4-60HPB-340M on STC wattage, thermal PTC/STC retention, and 18.76 aperture conversion efficiency against CEC peers.

## What Do the Dataset Ranks Show for LONGi Green Energy Technology Co Ltd LR4-60HPB-340M?

Key electrical performance ranks, roof area sizing, and NEC 690.7/690.8 design boundaries for LONGi Green Energy Technology Co Ltd LR4-60HPB-340M by LONGi Green Energy Technology Co Ltd.

Rank #13,575 / 21,677

### 340.0 W STC · Higher Than 36.1%

340.0 W STC (-45.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.

Eff #13,911

### 18.76% Aperture Efficiency

Power density 187.6 W/m2 (1.15 percentage points below 19.91% CEC median). PTC/STC ratio: 93.2% (rank #8,924).

NEC 690.7 Limit

### 13 Panels Max @ -10 C (600 V)

Cold Voc reaches 43.88 V at -10 C (570.4 V string) and 44.95 V at -20 C (13 max).

 8 kW Reference Array

### 24 Panels = 8,160 W STC

Occupies 43.5 m2 (468 sq ft) producing 7,603 W PTC; NEC 690.8 OCPD floor is 16.91 A (20 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 40.1 * (1 + (-0.269/100) * (-10 - 25)) = 43.88 V | OCPD = 1.56 * 10.84 = 16.91 A

Inputs from CEC Modules.csv for LONGi Green Energy Technology Co Ltd LR4-60HPB-340M: Voc=40.1 V, beta_Voc=-0.269%/C, Isc=10.84 A, STC=340.0 W, Area=1.812 m2.

**Result:** 13 panels max on 600 V (570.4 V); 24 panels for 8 kW (468 sq ft).

## What Are the Published CEC Specifications for LONGi Green Energy Technology Co Ltd LR4-60HPB-340M?

Laboratory test ratings recorded for LONGi Green Energy Technology Co Ltd LR4-60HPB-340M (Mono-c-Si) in the official California Energy Commission NREL SAM equipment catalog.

Official California Energy Commission (NREL SAM) test parameters for LONGi Green Energy Technology Co Ltd LR4-60HPB-340M.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Nameplate Power (STC)** | 340.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| **Real-World Output (PTC)** | 316.8 W (93.2% STC) | PVUSA Test Conditions rating used for utility interconnection |
| **Open-Circuit Voltage (Voc)** | 40.1 V | Primary cold-weather string sizing limit under NEC 690.7 |
| **Short-Circuit Current (Isc)** | 10.84 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| **Max Power Voltage / Current** | 32.9 V / 10.34 A | Inverter MPPT operating window alignment |
| **Voc Temp Coefficient (beta_Voc)** | -0.269 %/C | Negative slope governing voltage rise below 25C |
| **Module Efficiency & Area** | 18.76% (1.812 m2) | Array roof footprint density |
| **Cell Count & Technology** | 60 cells (Mono-c-Si) | Monofacial backsheet |

## How Many LONGi Green Energy Technology Co Ltd LR4-60HPB-340M Panels Build a 6 kW, 8 kW, or 10 kW Array?

Panel counts, roof square footage (468 sq ft at 8 kW), and estimated Year-1 electric bill offset for LONGi Green Energy Technology Co Ltd LR4-60HPB-340M.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).

| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| **6 kW Class** | 18 | 6.12 kW | 351 sq ft | $1,532 | $2,590 |
| **8 kW Class** | 24 | 8.16 kW | 468 sq ft | $2,042 | $3,454 |
| **10 kW Class** | 30 | 10.2 kW | 585 sq ft | $2,553 | $4,317 |

## Which Sibling Wattage & Trim Variants Belong to This LONGi Green Energy Technology Co Ltd Series?

Sibling wattage bins and frame colors grouped with LONGi Green Energy Technology Co Ltd LR4-60HPB-340M under LONGi Green Energy Technology Co Ltd to prevent duplicate spec pages.

Sibling CEC listings grouped into the LONGi Green Energy Technology Co Ltd LR4-60HPB-340M wattage tier to avoid duplicate 5W/trim datasheets.

| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| **LONGi Green Energy Technology Co Ltd LR4-60HPB-335M** | 335.0 W | 312.0 W | 39.9 V | 32.7 V | 18.49% |
| **LONGi Green Energy Technology Co Ltd LR4-60HPB-340M** | 340.0 W | 316.8 W | 40.1 V | 32.9 V | 18.76% |
| **LONGi Green Energy Technology Co Ltd LR4-60HPB-345M** | 345.0 W | 322.0 W | 40.2 V | 34.2 V | 19.49% |

## How Many LONGi Green Energy Technology Co Ltd LR4-60HPB-340M Modules Fit in a Cold-Weather String?

Cold-weather Voc escalation for LONGi Green Energy Technology Co Ltd LR4-60HPB-340M (beta_Voc -0.269%/C) across 600 V residential and 1,000 V commercial inverters.

Computed from Voc=40.1V and beta_Voc=-0.269%/C across design ambient temperatures.

| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| **-20 C (-4 F)** | 44.95 V | 13 panels | 584.4 V | 22 panels |
| **-10 C (14 F)** | 43.88 V | 13 panels | 570.4 V | 22 panels |
| **0 C (32 F)** | 42.8 V | 14 panels | 599.2 V | 23 panels |
| **25 C (77 F STC)** | 40.1 V | 14 panels | 561.4 V | 24 panels |

## Which Cross-Brand Solar Modules Compare Closest to LONGi Green Energy Technology Co Ltd LR4-60HPB-340M?

Closest cross-brand CEC competitors to LONGi Green Energy Technology Co Ltd LR4-60HPB-340M matched near 340.0 W STC and 40.1 V Voc, led by DualSun SAS DualSun 340M-120-00.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.

| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| [**DualSun SAS DualSun 340M-120-00**](https://epri-peac.com/solar-equipment/modules/dualsun-sas/dualsun-sas-dualsun-340m-120-00/) DualSun SAS | 340.0 W | Tie (0 W) | 40.1 V | 18.78% | 93.2% |
| [**Caterpillar Inc PVC345MP03HA**](https://epri-peac.com/solar-equipment/modules/caterpillar-inc/caterpillar-inc-pvc345mp03ha/) Caterpillar Inc | 345.0 W | +5.0 W | 40.2 V | 19.49% | 93.3% |
| [**ELITE Solar ET-M660BH345BB**](https://epri-peac.com/solar-equipment/modules/elite-solar/elite-solar-et-m660bh345bb/) ELITE Solar | 345.0 W | +5.0 W | 39.9 V | 19.17% | 93.5% |
| [**CSI Solar Co Ltd CS3L-345MS**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs3l-345ms/) CSI Solar Co Ltd | 345.0 W | +5.0 W | 39.8 V | 19.27% | 92.9% |

What to Check & Best-Fit Scenarios

## What Are the Design Limits and Best-Fit Uses for LONGi Green Energy Technology Co Ltd LR4-60HPB-340M?

Evaluate LONGi Green Energy Technology Co Ltd LR4-60HPB-340M (340.0 W STC, 40.1 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

- Winter overvoltage boundary: at -20 C (-4 F), LONGi Green Energy Technology Co Ltd LR4-60HPB-340M reaches 44.95 V per panel—exceeding 13 panels in series voids 600 V inverter warranties.
- Footprint constraint: 24 panels for an 8 kW build require 468 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 24 panels (468 sq ft).
- 2026 tax credit baseline: cash residential installs of LONGi Green Energy Technology Co Ltd LR4-60HPB-340M carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

### LONGi Green Energy Technology Co Ltd LR4-60HPB-340M 8 kW Residential Fit

Needs 24 modules (468 sq ft) with a 20 A string OCPD, offsetting ~$2,042/yr at US average tariffs.

### Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 13 panels (-10 C) or 13 panels (-20 C), or compare DualSun SAS DualSun 340M-120-00.

### Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 316.8 W PTC.

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for LONGi Green Energy Technology Co Ltd LR4-60HPB-340M by LONGi Green Energy Technology Co Ltd grounded in CEC test data and NEC 690.7/690.8 limits.

### What fuse or breaker size does NEC 690.8 require for LONGi Green Energy Technology Co Ltd LR4-60HPB-340M?

Multiplying LONGi Green Energy Technology Co Ltd LR4-60HPB-340M's 10.84 A short-circuit current by 1.56 equals 16.91 A minimum ampacity, requiring at least a 20 A overcurrent fuse or breaker.

### Can LONGi Green Energy Technology Co Ltd LR4-60HPB-340M pair with microinverters instead of a 600 V string inverter?

Yes—if the microinverter DC input ceiling exceeds 43.88 V cold Voc at 14 F and handles 10.84 A Isc; string inverters cap LONGi Green Energy Technology Co Ltd LR4-60HPB-340M at 13 panels on 600 V.

### Is LONGi Green Energy Technology Co Ltd LR4-60HPB-340M eligible for the 30% federal 25D solar credit in 2026?

No. Federal Section 25D expired December 31, 2025 under Public Law 119-21, so 2026 cash installs of LONGi Green Energy Technology Co Ltd LR4-60HPB-340M rely on utility bill offset (~$2,042/yr at 8 kW) rather than 25D.

## Related Pages

Compare LONGi Green Energy Technology Co Ltd equipment, DualSun SAS DualSun 340M-120-00 specs, utility payback rates, and NEC string calculators alongside LONGi Green Energy Technology Co Ltd LR4-60HPB-340M.

[All LONGi Green Energy Technology Co Ltd Certified Solar Models](https://epri-peac.com/solar-equipment/brands/longi-green-energy-technology-co-ltd/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [Check NEC 705.12 120% Panel Busbar Backfeed Limit](https://epri-peac.com/tools/solar-busbar-120/)

## Sources

1. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- 6-10 kW Array Sizing
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From LONGi Green Energy Technology Co Ltd

- [All LONGi Green Energy Technology Co Ltd Specs](https://epri-peac.com/solar-equipment/brands/longi-green-energy-technology-co-ltd/)
- [LONGi Green Energy Technology Co Ltd LR5-78HBD-605M](https://epri-peac.com/solar-equipment/modules/longi-green-energy-technology-co-ltd/longi-green-energy-technology-co-ltd-lr5-78hbd-605m/)
- [LONGi Green Energy Technology Co Ltd LR5-78HBD-585M](https://epri-peac.com/solar-equipment/modules/longi-green-energy-technology-co-ltd/longi-green-energy-technology-co-ltd-lr5-78hbd-585m/)
- [LONGi Green Energy Technology Co Ltd LR5-72HBD-560M](https://epri-peac.com/solar-equipment/modules/longi-green-energy-technology-co-ltd/longi-green-energy-technology-co-ltd-lr5-72hbd-560m/)
- [LONGi Green Energy Technology Co Ltd LR5-72HPH-560M](https://epri-peac.com/solar-equipment/modules/longi-green-energy-technology-co-ltd/longi-green-energy-technology-co-ltd-lr5-72hph-560m/)
- [LONGi Green Energy Technology Co Ltd LR5-72HPH-540M](https://epri-peac.com/solar-equipment/modules/longi-green-energy-technology-co-ltd/longi-green-energy-technology-co-ltd-lr5-72hph-540m/)