CEC PV Module

# JA Solar JAP6-72-290/MP — CEC Solar Module Specifications

Manufacturer: [**JA Solar**](https://epri-peac.com/solar-equipment/brands/ja-solar/) Registry: **CEC Verified Engineering Specification**

JA Solar JAP6-72-290/MP is a 290.0 W STC (256.2 W PTC) Multi-c-Si solar module ranking #17,253 of 21,677 CEC listings (below all-CEC median; higher than 18.8% of peers). It delivers 14.96% efficiency, 45.5 V Voc at 25 C, and 50.98 V cold Voc at -10 C (11 panels max per 600 V string).

- **STC Wattage** : 290.0 W

- **PTC Wattage** : 256.2 W

- **Voc @ 25C** : 45.5 V

- **Efficiency** : 14.96%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does JA Solar JAP6-72-290/MP Compare Against Peer CEC Listings?

Solar engineering breakdown for JA Solar JAP6-72-290/MP: PTC thermal retention, roof footprint, and cold Voc string bounds.

Across 1,407 Multi-c-Si listings from JA Solar and peers, JA Solar JAP6-72-290/MP stands 11.2 W above the 278.8 W Multi-c-Si median and typical 88.3% PTC-to-STC thermal output (256.2 W real-world rating). Sizing 6 kW (21 panels) to 10 kW (35 panels) yields $1,524-$2,540/yr in baseline US bill offset. Mid-range 45.5 V open-circuit voltage allows up to 11 panels per 600 V string at 14 F.

## Where Does JA Solar JAP6-72-290/MP Fall Across Listed CEC Models?

Distribution marker showing JA Solar JAP6-72-290/MP (290.0 W) relative to the 385.0 W all-CEC solar panel median.

## What Dataset Percentiles Define JA Solar JAP6-72-290/MP?

Dataset percentiles tracking JA Solar JAP6-72-290/MP power output, thermal retention ratio, and aperture efficiency against 21,677 models.

## What Do the Dataset Ranks Show for JA Solar JAP6-72-290/MP?

Benchmark highlights for JA Solar JAP6-72-290/MP covering STC output, efficiency, 8 kW footprint, and OCPD breaker size.

Rank #17,253 / 21,677

### 290.0 W STC · Higher Than 18.8%

290.0 W STC (-95.0 W vs all-CEC median) vs 278.8 W Multi-c-Si median.

Eff #19,793

### 14.96% Aperture Efficiency

Power density 149.6 W/m2 (4.95 percentage points below 19.91% CEC median). PTC/STC ratio: 88.3% (rank #21,245).

NEC 690.7 Limit

### 11 Panels Max @ -10 C (600 V)

Cold Voc reaches 50.98 V at -10 C (560.8 V string) and 52.54 V at -20 C (11 max).

 8 kW Reference Array

### 28 Panels = 8,120 W STC

Occupies 54.3 m2 (584 sq ft) producing 7,174 W PTC; NEC 690.8 OCPD floor is 13.48 A (15 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 45.5 * (1 + (-0.344/100) * (-10 - 25)) = 50.98 V | OCPD = 1.56 * 8.64 = 13.48 A

Inputs from CEC Modules.csv for JA Solar JAP6-72-290/MP: Voc=45.5 V, beta_Voc=-0.344%/C, Isc=8.64 A, STC=290.0 W, Area=1.938 m2.

**Result:** 11 panels max on 600 V (560.8 V); 28 panels for 8 kW (584 sq ft).

## What Are the Published CEC Specifications for JA Solar JAP6-72-290/MP?

Official CEC datasheet figures for JA Solar JAP6-72-290/MP (Multi-c-Si) used in utility interconnection and permit reviews. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Official California Energy Commission (NREL SAM) test parameters for JA Solar JAP6-72-290/MP.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Nameplate Power (STC)** | 290.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| **Real-World Output (PTC)** | 256.2 W (88.3% STC) | PVUSA Test Conditions rating used for utility interconnection |
| **Open-Circuit Voltage (Voc)** | 45.5 V | Primary cold-weather string sizing limit under NEC 690.7 |
| **Short-Circuit Current (Isc)** | 8.64 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| **Max Power Voltage / Current** | 36.34 V / 7.98 A | Inverter MPPT operating window alignment |
| **Voc Temp Coefficient (beta_Voc)** | -0.344 %/C | Negative slope governing voltage rise below 25C |
| **Module Efficiency & Area** | 14.96% (1.938 m2) | Array roof footprint density |
| **Cell Count & Technology** | 72 cells (Multi-c-Si) | Monofacial backsheet |

## How Many JA Solar JAP6-72-290/MP Panels Build a 6 kW, 8 kW, or 10 kW Array?

How many JA Solar JAP6-72-290/MP modules and square feet are required for 6 kW, 8 kW, and 10 kW home solar arrays.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).

| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| **6 kW Class** | 21 | 6.09 kW | 438 sq ft | $1,524 | $2,577 |
| **8 kW Class** | 28 | 8.12 kW | 584 sq ft | $2,032 | $3,437 |
| **10 kW Class** | 35 | 10.15 kW | 730 sq ft | $2,540 | $4,296 |

## Which Sibling Wattage & Trim Variants Belong to This JA Solar Series?

Consolidated JA Solar wattage variants sharing the JA Solar JAP6-72-290/MP mechanical and cell layout. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Sibling CEC listings grouped into the JA Solar JAP6-72-290/MP wattage tier to avoid duplicate 5W/trim datasheets.

| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| **JA Solar JAP6-72-280/MP** | 280.0 W | 247.1 W | 45.33 V | 35.81 V | 14.44% |
| **JA Solar JAP6-72-285/MP** | 285.0 W | 251.6 W | 45.42 V | 36.08 V | 14.7% |
| **JA Solar JAP6-72-290/MP** | 290.0 W | 256.2 W | 45.5 V | 36.34 V | 14.96% |
| **JA Solar JAP6-72-295/MP** | 295.0 W | 260.7 W | 45.59 V | 36.56 V | 15.22% |

## How Many JA Solar JAP6-72-290/MP Modules Fit in a Cold-Weather String?

NEC 690.7(A) winter string table preventing overvoltage trips on JA Solar JAP6-72-290/MP (50.98 V at 14 F).

Computed from Voc=45.5V and beta_Voc=-0.344%/C across design ambient temperatures.

| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| **-20 C (-4 F)** | 52.54 V | 11 panels | 577.9 V | 19 panels |
| **-10 C (14 F)** | 50.98 V | 11 panels | 560.8 V | 19 panels |
| **0 C (32 F)** | 49.41 V | 12 panels | 592.9 V | 20 panels |
| **25 C (77 F STC)** | 45.5 V | 13 panels | 591.5 V | 21 panels |

## Which Cross-Brand Solar Modules Compare Closest to JA Solar JAP6-72-290/MP?

Competing CEC solar panels closest to JA Solar JAP6-72-290/MP in nameplate wattage and Voc, starting with AXITEC AC-290M/156-72S.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.

| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| [**AXITEC AC-290M/156-72S**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-290m-156-72s/) AXITEC | 290.0 W | Tie (0 W) | 44.98 V | 14.95% | 90.6% |
| [**Gintung Energy GTEC-290G6S**](https://epri-peac.com/solar-equipment/modules/gintung-energy/gintung-energy-gtec-290g6s/) Gintung Energy | 290.0 W | Tie (0 W) | 44.84 V | 14.83% | 89.7% |
| [**Gintung Energy GTEC-290G6M**](https://epri-peac.com/solar-equipment/modules/gintung-energy/gintung-energy-gtec-290g6m/) Gintung Energy | 290.0 W | Tie (0 W) | 44.61 V | 14.83% | 89.6% |
| [**Centrosolar America DM72 290**](https://epri-peac.com/solar-equipment/modules/centrosolar-america/centrosolar-america-dm72-290/) Centrosolar America | 290.0 W | Tie (0 W) | 44.4 V | 14.92% | 90.6% |

What to Check & Best-Fit Scenarios

## What Are the Design Limits and Best-Fit Uses for JA Solar JAP6-72-290/MP?

Evaluate JA Solar JAP6-72-290/MP (290.0 W STC, 45.5 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

- Winter overvoltage boundary: at -20 C (-4 F), JA Solar JAP6-72-290/MP reaches 52.54 V per panel—exceeding 11 panels in series voids 600 V inverter warranties.
- Footprint constraint: 28 panels for an 8 kW build require 584 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 28 panels (584 sq ft).
- 2026 tax credit baseline: cash residential installs of JA Solar JAP6-72-290/MP carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

### JA Solar JAP6-72-290/MP 8 kW Residential Fit

Needs 28 modules (584 sq ft) with a 15 A string OCPD, offsetting ~$2,032/yr at US average tariffs.

### Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 11 panels (-10 C) or 11 panels (-20 C), or compare AXITEC AC-290M/156-72S.

### Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 256.2 W PTC.

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for JA Solar JAP6-72-290/MP by JA Solar grounded in CEC test data and NEC 690.7/690.8 limits.

### What fuse or breaker size does NEC 690.8 require for JA Solar JAP6-72-290/MP?

Multiplying JA Solar JAP6-72-290/MP's 8.64 A short-circuit current by 1.56 equals 13.48 A minimum ampacity, requiring at least a 15 A overcurrent fuse or breaker.

### Can JA Solar JAP6-72-290/MP pair with microinverters instead of a 600 V string inverter?

Yes—if the microinverter DC input ceiling exceeds 50.98 V cold Voc at 14 F and handles 8.64 A Isc; string inverters cap JA Solar JAP6-72-290/MP at 11 panels on 600 V.

### Is JA Solar JAP6-72-290/MP eligible for the 30% federal 25D solar credit in 2026?

No. Federal Section 25D expired December 31, 2025 under Public Law 119-21, so 2026 cash installs of JA Solar JAP6-72-290/MP rely on utility bill offset (~$2,032/yr at 8 kW) rather than 25D.

## Related Pages

Compare JA Solar equipment, AXITEC AC-290M/156-72S specs, utility payback rates, and NEC string calculators alongside JA Solar JAP6-72-290/MP.

[All JA Solar Certified Solar Models](https://epri-peac.com/solar-equipment/brands/ja-solar/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [Check NEC 705.12 120% Panel Busbar Backfeed Limit](https://epri-peac.com/tools/solar-busbar-120/)

## Sources

1. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- 6-10 kW Array Sizing
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From JA Solar

- [All JA Solar Specs](https://epri-peac.com/solar-equipment/brands/ja-solar/)
- [JA Solar JAM66D45-635/LB](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam66d45-635-lb/)
- [JA Solar JAM66D45-610/LB](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam66d45-610-lb/)
- [JA Solar JAM78D30-605/MB](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam78d30-605-mb/)
- [JA Solar JAM72D40-600/MB](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam72d40-600-mb/)
- [JA Solar JAM72D40-600/MB-US](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam72d40-600-mb-us/)