title: "JA Solar JAM60S01-290/PR Specs (290.0W, 39.46V Voc)"
url: https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam60s01-290-pr/
description: "CEC datasheet for JA Solar JAM60S01-290/PR: 290.0W STC, 39.46V Voc, 28-panel 8kW sizing, and NEC 690.7 limits. Verified US government and CEC engineering data."
---

CEC PV Module

# JA Solar JAM60S01-290/PR — CEC Solar Module Specifications

Manufacturer: [**JA Solar**](https://epri-peac.com/solar-equipment/brands/ja-solar/) Registry: **CEC Verified Engineering Specification**

JA Solar JAM60S01-290/PR is a 290.0 W STC (268.1 W PTC) Mono-c-Si solar module ranking #17,253 of 21,677 CEC listings (below all-CEC median; higher than 18.8% of peers). It delivers 18.32% efficiency, 39.46 V Voc at 25 C, and 43.34 V cold Voc at -10 C (13 panels max per 600 V string).

- **STC Wattage** : 290.0 W

- **PTC Wattage** : 268.1 W

- **Voc @ 25C** : 39.46 V

- **Efficiency** : 18.32%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does JA Solar JAM60S01-290/PR Compare Against Peer CEC Listings?

Solar engineering breakdown for JA Solar JAM60S01-290/PR: PTC thermal retention, roof footprint, and cold Voc string bounds.

Across 5,889 Mono-c-Si listings from JA Solar and peers, JA Solar JAM60S01-290/PR stands 120.0 W below the 410.0 W Mono-c-Si median and strong 92.4% PTC-to-STC heat retention (#12,969 of 21,677). Sizing 6 kW (21 panels) to 10 kW (35 panels) yields $1,524-$2,540/yr in baseline US bill offset. Lower 39.46 V string voltage fits 13 panels in series at 14 F and pairs easily with microinverters.

## Where Does JA Solar JAM60S01-290/PR Fall Across Listed CEC Models?

Distribution marker showing JA Solar JAM60S01-290/PR (290.0 W) relative to the 385.0 W all-CEC solar panel median.

## What Dataset Percentiles Define JA Solar JAM60S01-290/PR?

Dataset percentiles tracking JA Solar JAM60S01-290/PR power output, thermal retention ratio, and aperture efficiency against 21,677 models.

## What Do the Dataset Ranks Show for JA Solar JAM60S01-290/PR?

Benchmark highlights for JA Solar JAM60S01-290/PR covering STC output, efficiency, 8 kW footprint, and OCPD breaker size.

Rank #17,253 / 21,677

### 290.0 W STC · Higher Than 18.8%

290.0 W STC (-95.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.

Eff #14,632

### 18.32% Aperture Efficiency

Power density 183.2 W/m2 (1.59 percentage points below 19.91% CEC median). PTC/STC ratio: 92.4% (rank #12,969).

NEC 690.7 Limit

### 13 Panels Max @ -10 C (600 V)

Cold Voc reaches 43.34 V at -10 C (563.4 V string) and 44.45 V at -20 C (13 max).

 8 kW Reference Array

### 28 Panels = 8,120 W STC

Occupies 44.3 m2 (477 sq ft) producing 7,507 W PTC; NEC 690.8 OCPD floor is 14.93 A (15 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 39.46 * (1 + (-0.281/100) * (-10 - 25)) = 43.34 V | OCPD = 1.56 * 9.57 = 14.93 A

Inputs from CEC Modules.csv for JA Solar JAM60S01-290/PR: Voc=39.46 V, beta_Voc=-0.281%/C, Isc=9.57 A, STC=290.0 W, Area=1.583 m2.

**Result:** 13 panels max on 600 V (563.4 V); 28 panels for 8 kW (477 sq ft).

## What Are the Published CEC Specifications for JA Solar JAM60S01-290/PR?

Official CEC datasheet figures for JA Solar JAM60S01-290/PR (Mono-c-Si) used in utility interconnection and permit reviews. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Official California Energy Commission (NREL SAM) test parameters for JA Solar JAM60S01-290/PR.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Nameplate Power (STC)** | 290.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| **Real-World Output (PTC)** | 268.1 W (92.4% STC) | PVUSA Test Conditions rating used for utility interconnection |
| **Open-Circuit Voltage (Voc)** | 39.46 V | Primary cold-weather string sizing limit under NEC 690.7 |
| **Short-Circuit Current (Isc)** | 9.57 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| **Max Power Voltage / Current** | 31.8 V / 9.12 A | Inverter MPPT operating window alignment |
| **Voc Temp Coefficient (beta_Voc)** | -0.281 %/C | Negative slope governing voltage rise below 25C |
| **Module Efficiency & Area** | 18.32% (1.583 m2) | Array roof footprint density |
| **Cell Count & Technology** | 60 cells (Mono-c-Si) | Monofacial backsheet |

## How Many JA Solar JAM60S01-290/PR Panels Build a 6 kW, 8 kW, or 10 kW Array?

How many JA Solar JAM60S01-290/PR modules and square feet are required for 6 kW, 8 kW, and 10 kW home solar arrays.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).

| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| **6 kW Class** | 21 | 6.09 kW | 358 sq ft | $1,524 | $2,577 |
| **8 kW Class** | 28 | 8.12 kW | 477 sq ft | $2,032 | $3,437 |
| **10 kW Class** | 35 | 10.15 kW | 596 sq ft | $2,540 | $4,296 |

## Which Sibling Wattage & Trim Variants Belong to This JA Solar Series?

Consolidated JA Solar wattage variants sharing the JA Solar JAM60S01-290/PR mechanical and cell layout. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Sibling CEC listings grouped into the JA Solar JAM60S01-290/PR wattage tier to avoid duplicate 5W/trim datasheets.

| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| **JA Solar JAM60S01-280/PR** | 280.0 W | 258.7 W | 39.05 V | 31.6 V | 17.69% |
| **JA Solar JAM60S01-285/PR** | 285.0 W | 263.4 W | 39.25 V | 31.7 V | 18.0% |
| **JA Solar JAM60S01-290/PR** | 290.0 W | 268.1 W | 39.46 V | 31.8 V | 18.32% |
| **JA Solar JAM60S01-295/PR** | 295.0 W | 272.9 W | 39.64 V | 32.03 V | 18.64% |

## How Many JA Solar JAM60S01-290/PR Modules Fit in a Cold-Weather String?

NEC 690.7(A) winter string table preventing overvoltage trips on JA Solar JAM60S01-290/PR (43.34 V at 14 F).

Computed from Voc=39.46V and beta_Voc=-0.281%/C across design ambient temperatures.

| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| **-20 C (-4 F)** | 44.45 V | 13 panels | 577.9 V | 22 panels |
| **-10 C (14 F)** | 43.34 V | 13 panels | 563.4 V | 23 panels |
| **0 C (32 F)** | 42.23 V | 14 panels | 591.2 V | 23 panels |
| **25 C (77 F STC)** | 39.46 V | 15 panels | 591.9 V | 25 panels |

## Which Cross-Brand Solar Modules Compare Closest to JA Solar JAM60S01-290/PR?

Competing CEC solar panels closest to JA Solar JAM60S01-290/PR in nameplate wattage and Voc, starting with AXITEC AC-290M/60S.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.

| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| [**AXITEC AC-290M/60S**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-290m-60s/) AXITEC | 290.0 W | Tie (0 W) | 39.42 V | 17.79% | 91.1% |
| [**AXITEC AC-290M/60V**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-290m-60v/) AXITEC | 290.0 W | Tie (0 W) | 39.42 V | 17.79% | 91.1% |
| [**DualSun SAS DualSun 290M-60-00**](https://epri-peac.com/solar-equipment/modules/dualsun-sas/dualsun-sas-dualsun-290m-60-00/) DualSun SAS | 290.0 W | Tie (0 W) | 39.7 V | 17.68% | 90.9% |
| [**CertainTeed CT290M10-02**](https://epri-peac.com/solar-equipment/modules/certainteed/certainteed-ct290m10-02/) CertainTeed | 290.0 W | Tie (0 W) | 39.77 V | 17.83% | 91.8% |

What to Check & Best-Fit Scenarios

## What Are the Design Limits and Best-Fit Uses for JA Solar JAM60S01-290/PR?

Evaluate JA Solar JAM60S01-290/PR (290.0 W STC, 39.46 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

- Winter overvoltage boundary: at -20 C (-4 F), JA Solar JAM60S01-290/PR reaches 44.45 V per panel—exceeding 13 panels in series voids 600 V inverter warranties.
- Footprint constraint: 28 panels for an 8 kW build require 477 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 28 panels (477 sq ft).
- 2026 tax credit baseline: cash residential installs of JA Solar JAM60S01-290/PR carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

### JA Solar JAM60S01-290/PR 8 kW Residential Fit

Needs 28 modules (477 sq ft) with a 15 A string OCPD, offsetting ~$2,032/yr at US average tariffs.

### Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 13 panels (-10 C) or 13 panels (-20 C), or compare AXITEC AC-290M/60S.

### Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 268.1 W PTC.

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for JA Solar JAM60S01-290/PR by JA Solar grounded in CEC test data and NEC 690.7/690.8 limits.

### What fuse or breaker size does NEC 690.8 require for JA Solar JAM60S01-290/PR?

Multiplying JA Solar JAM60S01-290/PR's 9.57 A short-circuit current by 1.56 equals 14.93 A minimum ampacity, requiring at least a 15 A overcurrent fuse or breaker.

### Can JA Solar JAM60S01-290/PR pair with microinverters instead of a 600 V string inverter?

Yes—if the microinverter DC input ceiling exceeds 43.34 V cold Voc at 14 F and handles 9.57 A Isc; string inverters cap JA Solar JAM60S01-290/PR at 13 panels on 600 V.

### Is JA Solar JAM60S01-290/PR eligible for the 30% federal 25D solar credit in 2026?

No. Federal Section 25D expired December 31, 2025 under Public Law 119-21, so 2026 cash installs of JA Solar JAM60S01-290/PR rely on utility bill offset (~$2,032/yr at 8 kW) rather than 25D.

## Related Pages

Compare JA Solar equipment, AXITEC AC-290M/60S specs, utility payback rates, and NEC string calculators alongside JA Solar JAM60S01-290/PR.

[All JA Solar Certified Solar Models](https://epri-peac.com/solar-equipment/brands/ja-solar/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [Check NEC 705.12 120% Panel Busbar Backfeed Limit](https://epri-peac.com/tools/solar-busbar-120/)

## Sources

1. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- 6-10 kW Array Sizing
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From JA Solar

- [All JA Solar Specs](https://epri-peac.com/solar-equipment/brands/ja-solar/)
- [JA Solar JAM66D45-635/LB](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam66d45-635-lb/)
- [JA Solar JAM66D45-610/LB](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam66d45-610-lb/)
- [JA Solar JAM78D30-605/MB](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam78d30-605-mb/)
- [JA Solar JAM72D40-600/MB](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam72d40-600-mb/)
- [JA Solar JAM72D40-600/MB-US](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam72d40-600-mb-us/)