title: "JA Solar JAM5(L)-72-190/SI Specs (190.0W, 45.38V Voc)"
url: https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam5-l-72-190-si/
description: "CEC datasheet for JA Solar JAM5(L)-72-190/SI: 190.0W STC, 45.38V Voc, 43-panel 8kW sizing, and NEC 690.7 limits. Verified US government and CEC engineering data."
---

CEC PV Module

# JA Solar JAM5(L)-72-190/SI — CEC Solar Module Specifications

Manufacturer: [**JA Solar**](https://epri-peac.com/solar-equipment/brands/ja-solar/) Registry: **CEC Verified Engineering Specification**

JA Solar JAM5(L)-72-190/SI is a 190.0 W STC (169.4 W PTC) Mono-c-Si solar module ranking #21,132 of 21,677 CEC listings (below all-CEC median; higher than 2.3% of peers). It delivers 14.88% efficiency, 45.38 V Voc at 25 C, and 50.99 V cold Voc at -10 C (11 panels max per 600 V string).

- **STC Wattage** : 190.0 W

- **PTC Wattage** : 169.4 W

- **Voc @ 25C** : 45.38 V

- **Efficiency** : 14.88%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does JA Solar JAM5(L)-72-190/SI Compare Against Peer CEC Listings?

CEC rank, roof space requirements, and NEC 690.7/690.8 limits for JA Solar JAM5(L)-72-190/SI (Mono-c-Si) residential solar systems.

Homeowners evaluating JA Solar JAM5(L)-72-190/SI need 32 panels for 6 kW or 43 panels (591 sq ft) for an 8 kW array—useful on tight dormer roofs or battery cabins, though 8 kW requires 43 panels (591 sq ft). Under NEC 690.7(A), beta_Voc (-0.353%/C) pushes open-circuit voltage to 50.99 V at 14 F and 52.59 V at -4 F. Monofacial backsheet sealing targets flush dark shingle rooftop mounts.

## Where Does JA Solar JAM5(L)-72-190/SI Fall Across Listed CEC Models?

Comparison of JA Solar JAM5(L)-72-190/SI (190.0 W STC) against all 21,677 California Energy Commission certified photovoltaic modules.

## What Dataset Percentiles Define JA Solar JAM5(L)-72-190/SI?

Relative ranking of JA Solar JAM5(L)-72-190/SI across nameplate watts, 89.2% PTC thermal ratio, and module aperture efficiency.

## What Do the Dataset Ranks Show for JA Solar JAM5(L)-72-190/SI?

Summary of JA Solar JAM5(L)-72-190/SI output rank, 8 kW array size (43 panels), efficiency rating, and 600 V string limit.

Rank #21,132 / 21,677

### 190.0 W STC · Higher Than 2.3%

190.0 W STC (-195.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.

Eff #19,900

### 14.88% Aperture Efficiency

Power density 148.8 W/m2 (5.03 percentage points below 19.91% CEC median). PTC/STC ratio: 89.2% (rank #20,311).

NEC 690.7 Limit

### 11 Panels Max @ -10 C (600 V)

Cold Voc reaches 50.99 V at -10 C (560.9 V string) and 52.59 V at -20 C (11 max).

 8 kW Reference Array

### 43 Panels = 8,170 W STC

Occupies 54.9 m2 (591 sq ft) producing 7,284 W PTC; NEC 690.8 OCPD floor is 8.7 A (15 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 45.38 * (1 + (-0.353/100) * (-10 - 25)) = 50.99 V | OCPD = 1.56 * 5.58 = 8.7 A

Inputs from CEC Modules.csv for JA Solar JAM5(L)-72-190/SI: Voc=45.38 V, beta_Voc=-0.353%/C, Isc=5.58 A, STC=190.0 W, Area=1.277 m2.

**Result:** 11 panels max on 600 V (560.9 V); 43 panels for 8 kW (591 sq ft).

## What Are the Published CEC Specifications for JA Solar JAM5(L)-72-190/SI?

Complete CEC test sheet for JA Solar JAM5(L)-72-190/SI including Isc (5.58 A), Voc (45.38 V), and thermal temperature coefficients.

Official California Energy Commission (NREL SAM) test parameters for JA Solar JAM5(L)-72-190/SI.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Nameplate Power (STC)** | 190.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| **Real-World Output (PTC)** | 169.4 W (89.2% STC) | PVUSA Test Conditions rating used for utility interconnection |
| **Open-Circuit Voltage (Voc)** | 45.38 V | Primary cold-weather string sizing limit under NEC 690.7 |
| **Short-Circuit Current (Isc)** | 5.58 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| **Max Power Voltage / Current** | 36.66 V / 5.18 A | Inverter MPPT operating window alignment |
| **Voc Temp Coefficient (beta_Voc)** | -0.353 %/C | Negative slope governing voltage rise below 25C |
| **Module Efficiency & Area** | 14.88% (1.277 m2) | Array roof footprint density |
| **Cell Count & Technology** | 72 cells (Mono-c-Si) | Monofacial backsheet |

## How Many JA Solar JAM5(L)-72-190/SI Panels Build a 6 kW, 8 kW, or 10 kW Array?

Residential array count and annual electric bill savings at 18.54 c/kWh US avg vs. California tariffs using JA Solar JAM5(L)-72-190/SI.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).

| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| **6 kW Class** | 32 | 6.08 kW | 440 sq ft | $1,522 | $2,573 |
| **8 kW Class** | 43 | 8.17 kW | 591 sq ft | $2,045 | $3,458 |
| **10 kW Class** | 53 | 10.07 kW | 729 sq ft | $2,520 | $4,262 |

## Which Sibling Wattage & Trim Variants Belong to This JA Solar Series?

Related JA Solar power steps and black/silver trims consolidated into this JA Solar JAM5(L)-72-190/SI series guide.

Sibling CEC listings grouped into the JA Solar JAM5(L)-72-190/SI wattage tier to avoid duplicate 5W/trim datasheets.

| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| **JA Solar JAM5(L)-72-180/SI** | 180.0 W | 160.2 W | 44.88 V | 36.42 V | 14.1% |
| **JA Solar JAM5(L)-72-185/SI** | 185.0 W | 164.8 W | 45.18 V | 36.54 V | 14.49% |
| **JA Solar JAM5(L)-72-190/SI** | 190.0 W | 169.4 W | 45.38 V | 36.66 V | 14.88% |
| **JA Solar JAM5(L)-72-195/SI** | 195.0 W | 173.9 W | 45.5 V | 36.96 V | 15.27% |

## How Many JA Solar JAM5(L)-72-190/SI Modules Fit in a Cold-Weather String?

Verify freezing-morning voltage rise for JA Solar JAM5(L)-72-190/SI (45.38 V STC) before wiring 600 V or 1,000 V strings.

Computed from Voc=45.38V and beta_Voc=-0.353%/C across design ambient temperatures.

| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| **-20 C (-4 F)** | 52.59 V | 11 panels | 578.5 V | 19 panels |
| **-10 C (14 F)** | 50.99 V | 11 panels | 560.9 V | 19 panels |
| **0 C (32 F)** | 49.38 V | 12 panels | 592.6 V | 20 panels |
| **25 C (77 F STC)** | 45.38 V | 13 panels | 589.9 V | 22 panels |

## Which Cross-Brand Solar Modules Compare Closest to JA Solar JAM5(L)-72-190/SI?

Four comparable CEC modules such as AXITEC AC-190M/125-72S (190.0 W) for side-by-side solar quote checks. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.

| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| [**AXITEC AC-190M/125-72S**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-190m-125-72s/) AXITEC | 190.0 W | Tie (0 W) | 45.23 V | 14.88% | 89.8% |
| [**Suntech Power STP190S-24/Ad**](https://epri-peac.com/solar-equipment/modules/suntech-power/suntech-power-stp190s-24-ad/) Suntech Power | 190.0 W | Tie (0 W) | 45.2 V | 14.88% | 90.3% |
| [**Suntech Power STP190S-24/Adb**](https://epri-peac.com/solar-equipment/modules/suntech-power/suntech-power-stp190s-24-adb/) Suntech Power | 190.0 W | Tie (0 W) | 45.2 V | 14.88% | 90.4% |
| [**Seraphim Solar System CoLtd SRP-190-5MB**](https://epri-peac.com/solar-equipment/modules/seraphim-solar-system-coltd/seraphim-solar-system-coltd-srp-190-5mb/) Seraphim Solar System CoLtd | 190.0 W | Tie (0 W) | 45.1 V | 14.88% | 90.3% |

What to Check & Best-Fit Scenarios

## What Are the Design Limits and Best-Fit Uses for JA Solar JAM5(L)-72-190/SI?

Evaluate JA Solar JAM5(L)-72-190/SI (190.0 W STC, 45.38 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

- Winter overvoltage boundary: at -20 C (-4 F), JA Solar JAM5(L)-72-190/SI reaches 52.59 V per panel—exceeding 11 panels in series voids 600 V inverter warranties.
- Footprint constraint: 43 panels for an 8 kW build require 591 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 43 panels (591 sq ft).
- 2026 tax credit baseline: cash residential installs of JA Solar JAM5(L)-72-190/SI carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

### JA Solar JAM5(L)-72-190/SI 8 kW Residential Fit

Needs 43 modules (591 sq ft) with a 15 A string OCPD, offsetting ~$2,045/yr at US average tariffs.

### Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 11 panels (-10 C) or 11 panels (-20 C), or compare AXITEC AC-190M/125-72S.

### Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 169.4 W PTC.

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for JA Solar JAM5(L)-72-190/SI by JA Solar grounded in CEC test data and NEC 690.7/690.8 limits.

### Why is JA Solar JAM5(L)-72-190/SI PTC wattage (169.4 W) lower than STC (190.0 W)?

Laboratory STC tests at 25 C cell temperature, whereas real rooftop heat lowers voltage to 169.4 W PTC (89.2% retention) across JA Solar JAM5(L)-72-190/SI's 1.277 m2 aperture.

### Who should skip JA Solar JAM5(L)-72-190/SI on a complex residential roof?

Homes with chopped dormers or heavy chimney shade should compare smaller modules or microinverters if 43 JA Solar JAM5(L)-72-190/SI panels (591 sq ft) leave unusable roof gaps vs. AXITEC AC-190M/125-72S.

### What is the 1,000 V commercial string limit for JA Solar JAM5(L)-72-190/SI?

On 1,000 V commercial inverters at -10 C (50.99 V cold Voc), JA Solar JAM5(L)-72-190/SI fits up to 19 panels per series string.

## Related Pages

Compare JA Solar equipment, AXITEC AC-190M/125-72S specs, utility payback rates, and NEC string calculators alongside JA Solar JAM5(L)-72-190/SI.

[All JA Solar Certified Solar Models](https://epri-peac.com/solar-equipment/brands/ja-solar/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [Check NEC 705.12 120% Panel Busbar Backfeed Limit](https://epri-peac.com/tools/solar-busbar-120/)

## Sources

1. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- 6-10 kW Array Sizing
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From JA Solar

- [All JA Solar Specs](https://epri-peac.com/solar-equipment/brands/ja-solar/)
- [JA Solar JAM66D45-635/LB](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam66d45-635-lb/)
- [JA Solar JAM66D45-610/LB](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam66d45-610-lb/)
- [JA Solar JAM78D30-605/MB](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam78d30-605-mb/)
- [JA Solar JAM72D40-600/MB](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam72d40-600-mb/)
- [JA Solar JAM72D40-600/MB-US](https://epri-peac.com/solar-equipment/modules/ja-solar/ja-solar-jam72d40-600-mb-us/)