title: "Gintung Energy ASEC-180G6S Specs (180.0W, 29.73V Voc)"
url: https://epri-peac.com/solar-equipment/modules/gintung-energy/gintung-energy-asec-180g6s/
description: "CEC datasheet for Gintung Energy ASEC-180G6S: 180.0W STC, 29.73V Voc, 45-panel 8kW sizing, and NEC 690.7 limits. Verified US government and CEC engineering data."
---

CEC PV Module

# Gintung Energy ASEC-180G6S — CEC Solar Module Specifications

Manufacturer: [**Gintung Energy**](https://epri-peac.com/solar-equipment/brands/gintung-energy/) Registry: **CEC Verified Engineering Specification**

Gintung Energy ASEC-180G6S is a 180.0 W STC (159.7 W PTC) Mono-c-Si solar module ranking #21,232 of 21,677 CEC listings (below all-CEC median; higher than 1.8% of peers). It delivers 13.8% efficiency, 29.73 V Voc at 25 C, and 33.44 V cold Voc at -10 C (17 panels max per 600 V string).

- **STC Wattage** : 180.0 W

- **PTC Wattage** : 159.7 W

- **Voc @ 25C** : 29.73 V

- **Efficiency** : 13.8%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Gintung Energy ASEC-180G6S Compare Against Peer CEC Listings?

CEC rank, roof space requirements, and NEC 690.7/690.8 limits for Gintung Energy ASEC-180G6S (Mono-c-Si) residential solar systems.

Homeowners evaluating Gintung Energy ASEC-180G6S need 34 panels for 6 kW or 45 panels (632 sq ft) for an 8 kW array—useful on tight dormer roofs or battery cabins, though 8 kW requires 45 panels (632 sq ft). Under NEC 690.7(A), beta_Voc (-0.357%/C) pushes open-circuit voltage to 33.44 V at 14 F and 34.51 V at -4 F. Monofacial backsheet sealing targets flush dark shingle rooftop mounts.

## Where Does Gintung Energy ASEC-180G6S Fall Across Listed CEC Models?

Comparison of Gintung Energy ASEC-180G6S (180.0 W STC) against all 21,677 California Energy Commission certified photovoltaic modules. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

## What Dataset Percentiles Define Gintung Energy ASEC-180G6S?

Relative ranking of Gintung Energy ASEC-180G6S across nameplate watts, 88.7% PTC thermal ratio, and module aperture efficiency. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

## What Do the Dataset Ranks Show for Gintung Energy ASEC-180G6S?

Summary of Gintung Energy ASEC-180G6S output rank, 8 kW array size (45 panels), efficiency rating, and 600 V string limit.

Rank #21,232 / 21,677

### 180.0 W STC · Higher Than 1.8%

180.0 W STC (-205.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.

Eff #21,044

### 13.8% Aperture Efficiency

Power density 138.0 W/m2 (6.11 percentage points below 19.91% CEC median). PTC/STC ratio: 88.7% (rank #21,046).

NEC 690.7 Limit

### 17 Panels Max @ -10 C (600 V)

Cold Voc reaches 33.44 V at -10 C (568.5 V string) and 34.51 V at -20 C (17 max).

 8 kW Reference Array

### 45 Panels = 8,100 W STC

Occupies 58.7 m2 (632 sq ft) producing 7,186 W PTC; NEC 690.8 OCPD floor is 12.95 A (15 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 29.73 * (1 + (-0.357/100) * (-10 - 25)) = 33.44 V | OCPD = 1.56 * 8.3 = 12.95 A

Inputs from CEC Modules.csv for Gintung Energy ASEC-180G6S: Voc=29.73 V, beta_Voc=-0.357%/C, Isc=8.3 A, STC=180.0 W, Area=1.304 m2.

**Result:** 17 panels max on 600 V (568.5 V); 45 panels for 8 kW (632 sq ft).

## What Are the Published CEC Specifications for Gintung Energy ASEC-180G6S?

Complete CEC test sheet for Gintung Energy ASEC-180G6S including Isc (8.3 A), Voc (29.73 V), and thermal temperature coefficients.

Official California Energy Commission (NREL SAM) test parameters for Gintung Energy ASEC-180G6S.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Nameplate Power (STC)** | 180.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| **Real-World Output (PTC)** | 159.7 W (88.7% STC) | PVUSA Test Conditions rating used for utility interconnection |
| **Open-Circuit Voltage (Voc)** | 29.73 V | Primary cold-weather string sizing limit under NEC 690.7 |
| **Short-Circuit Current (Isc)** | 8.3 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| **Max Power Voltage / Current** | 23.82 V / 7.58 A | Inverter MPPT operating window alignment |
| **Voc Temp Coefficient (beta_Voc)** | -0.357 %/C | Negative slope governing voltage rise below 25C |
| **Module Efficiency & Area** | 13.8% (1.304 m2) | Array roof footprint density |
| **Cell Count & Technology** | 48 cells (Mono-c-Si) | Monofacial backsheet |

## How Many Gintung Energy ASEC-180G6S Panels Build a 6 kW, 8 kW, or 10 kW Array?

Residential array count and annual electric bill savings at 18.54 c/kWh US avg vs. California tariffs using Gintung Energy ASEC-180G6S.

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).

| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| **6 kW Class** | 34 | 6.12 kW | 477 sq ft | $1,532 | $2,590 |
| **8 kW Class** | 45 | 8.1 kW | 632 sq ft | $2,027 | $3,428 |
| **10 kW Class** | 56 | 10.08 kW | 786 sq ft | $2,523 | $4,266 |

## Which Sibling Wattage & Trim Variants Belong to This Gintung Energy Series?

Related Gintung Energy power steps and black/silver trims consolidated into this Gintung Energy ASEC-180G6S series guide. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Sibling CEC listings grouped into the Gintung Energy ASEC-180G6S wattage tier to avoid duplicate 5W/trim datasheets.

| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| **Gintung Energy ASEC-175G6S** | 175.0 W | 155.2 W | 29.57 V | 23.51 V | 13.42% |
| **Gintung Energy ASEC-180G6S** | 180.0 W | 159.7 W | 29.73 V | 23.82 V | 13.8% |
| **Gintung Energy ASEC-185G6S** | 185.0 W | 164.3 W | 29.9 V | 24.28 V | 14.18% |

## How Many Gintung Energy ASEC-180G6S Modules Fit in a Cold-Weather String?

Verify freezing-morning voltage rise for Gintung Energy ASEC-180G6S (29.73 V STC) before wiring 600 V or 1,000 V strings.

Computed from Voc=29.73V and beta_Voc=-0.357%/C across design ambient temperatures.

| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| **-20 C (-4 F)** | 34.51 V | 17 panels | 586.7 V | 28 panels |
| **-10 C (14 F)** | 33.44 V | 17 panels | 568.5 V | 29 panels |
| **0 C (32 F)** | 32.38 V | 18 panels | 582.8 V | 30 panels |
| **25 C (77 F STC)** | 29.73 V | 20 panels | 594.6 V | 33 panels |

## Which Cross-Brand Solar Modules Compare Closest to Gintung Energy ASEC-180G6S?

Four comparable CEC modules such as APOS Energy AP180 (180.0 W) for side-by-side solar quote checks. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.

| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| [**APOS Energy AP180**](https://epri-peac.com/solar-equipment/modules/apos-energy/apos-energy-ap180/) APOS Energy | 180.0 W | Tie (0 W) | 29.72 V | 13.42% | 88.9% |
| [**Lightway Green New Energy LW180(23)P1310x990**](https://epri-peac.com/solar-equipment/modules/lightway-green-new-energy/lightway-green-new-energy-lw180-23-p1310x990/) Lightway Green New Energy | 180.0 W | Tie (0 W) | 29.5 V | 14.02% | 89.5% |
| [**Yingli Energy (China) YL180P-23b**](https://epri-peac.com/solar-equipment/modules/yingli-energy-china/yingli-energy-china-yl180p-23b/) Yingli Energy (China) | 180.0 W | Tie (0 W) | 29.5 V | 14.02% | 90.8% |
| [**Guangdong Golden Glass Technologies GG180M2-24/1324x992**](https://epri-peac.com/solar-equipment/modules/guangdong-golden-glass-technologies/guangdong-golden-glass-technologies-gg180m2-24-1324x992/) Guangdong Golden Glass Technologies | 180.0 W | Tie (0 W) | 29.4 V | 13.7% | 89.9% |

What to Check & Best-Fit Scenarios

## What Are the Design Limits and Best-Fit Uses for Gintung Energy ASEC-180G6S?

Evaluate Gintung Energy ASEC-180G6S (180.0 W STC, 29.73 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

- Winter overvoltage boundary: at -20 C (-4 F), Gintung Energy ASEC-180G6S reaches 34.51 V per panel—exceeding 17 panels in series voids 600 V inverter warranties.
- Footprint constraint: 45 panels for an 8 kW build require 632 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 45 panels (632 sq ft).
- 2026 tax credit baseline: cash residential installs of Gintung Energy ASEC-180G6S carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

### Gintung Energy ASEC-180G6S 8 kW Residential Fit

Needs 45 modules (632 sq ft) with a 15 A string OCPD, offsetting ~$2,027/yr at US average tariffs.

### Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 17 panels (-10 C) or 17 panels (-20 C), or compare APOS Energy AP180.

### Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 159.7 W PTC.

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for Gintung Energy ASEC-180G6S by Gintung Energy grounded in CEC test data and NEC 690.7/690.8 limits.

### Why is Gintung Energy ASEC-180G6S PTC wattage (159.7 W) lower than STC (180.0 W)?

Laboratory STC tests at 25 C cell temperature, whereas real rooftop heat lowers voltage to 159.7 W PTC (88.7% retention) across Gintung Energy ASEC-180G6S's 1.304 m2 aperture.

### Who should skip Gintung Energy ASEC-180G6S on a complex residential roof?

Homes with chopped dormers or heavy chimney shade should compare smaller modules or microinverters if 45 Gintung Energy ASEC-180G6S panels (632 sq ft) leave unusable roof gaps vs. APOS Energy AP180.

### What is the 1,000 V commercial string limit for Gintung Energy ASEC-180G6S?

On 1,000 V commercial inverters at -10 C (33.44 V cold Voc), Gintung Energy ASEC-180G6S fits up to 29 panels per series string. Review current municipal Authority Having Jurisdiction (AHJ) code amendments affecting Gintung Energy ASEC-180G6S.

## Related Pages

Compare Gintung Energy equipment, APOS Energy AP180 specs, utility payback rates, and NEC string calculators alongside Gintung Energy ASEC-180G6S.

[All Gintung Energy Certified Solar Models](https://epri-peac.com/solar-equipment/brands/gintung-energy/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [Check NEC 705.12 120% Panel Busbar Backfeed Limit](https://epri-peac.com/tools/solar-busbar-120/)

## Sources

1. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- 6-10 kW Array Sizing
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Gintung Energy

- [All Gintung Energy Specs](https://epri-peac.com/solar-equipment/brands/gintung-energy/)
- [Gintung Energy ASEC-325G6M](https://epri-peac.com/solar-equipment/modules/gintung-energy/gintung-energy-asec-325g6m/)
- [Gintung Energy ASEC-325G6S](https://epri-peac.com/solar-equipment/modules/gintung-energy/gintung-energy-asec-325g6s/)
- [Gintung Energy GTEC-325G6M](https://epri-peac.com/solar-equipment/modules/gintung-energy/gintung-energy-gtec-325g6m/)
- [Gintung Energy GTEC-325G6S](https://epri-peac.com/solar-equipment/modules/gintung-energy/gintung-energy-gtec-325g6s/)
- [Gintung Energy ASEC-310G6M](https://epri-peac.com/solar-equipment/modules/gintung-energy/gintung-energy-asec-310g6m/)