title: "CertainTeed CT355M10-01 Specs (355.0W, 47.3V Voc)"
url: https://epri-peac.com/solar-equipment/modules/certainteed/certainteed-ct355m10-01/
description: "CEC datasheet for CertainTeed CT355M10-01: 355.0W STC, 47.3V Voc, 23-panel 8kW sizing, and NEC 690.7 limits. Verified US government and CEC engineering data."
---

CEC PV Module

# CertainTeed CT355M10-01 — CEC Solar Module Specifications

Manufacturer: [**CertainTeed**](https://epri-peac.com/solar-equipment/brands/certainteed/) Registry: **CEC Verified Engineering Specification**

CertainTeed CT355M10-01 is a 355.0 W STC (326.6 W PTC) Mono-c-Si solar module ranking #12,724 of 21,677 CEC listings (below all-CEC median; higher than 39.9% of peers). It delivers 19.61% efficiency, 47.3 V Voc at 25 C, and 52.1 V cold Voc at -10 C (11 panels max per 600 V string).

- **STC Wattage** : 355.0 W

- **PTC Wattage** : 326.6 W

- **Voc @ 25C** : 47.3 V

- **Efficiency** : 19.61%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does CertainTeed CT355M10-01 Compare Against Peer CEC Listings?

How CertainTeed CertainTeed CT355M10-01 handles rooftop heat (326.6 W PTC), 8 kW sizing, and cold winter string voltage.

For NEC string engineering, CertainTeed CT355M10-01 exhibits 9.7 A short-circuit current, requiring a 15.13 A (156%) conductor rating and 20 A OCPD under NEC 690.8. Ranked #12,724 of 21,677 (55.0 W below the 410.0 W Mono-c-Si median), this compact residential or specialty off-grid module covers 41.6 m2 for an 8 kW system (29 panels for 10 kW). Mid-range 47.3 V open-circuit voltage allows up to 11 panels per 600 V string at 14 F.

## Where Does CertainTeed CT355M10-01 Fall Across Listed CEC Models?

Where CertainTeed CT355M10-01 (355.0 W) sits inside the 21,677-panel CEC STC wattage curve relative to the 385.0 W median.

## What Dataset Percentiles Define CertainTeed CT355M10-01?

Percentile placement of CertainTeed CT355M10-01 across power density (196.1 W/m2), thermal retention, and nameplate STC wattage. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

## What Do the Dataset Ranks Show for CertainTeed CT355M10-01?

Four critical engineering numbers homeowners and solar installers check first when reviewing CertainTeed CT355M10-01 specifications. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Rank #12,724 / 21,677

### 355.0 W STC · Higher Than 39.9%

355.0 W STC (-30.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.

Eff #11,817

### 19.61% Aperture Efficiency

Power density 196.1 W/m2 (0.30 percentage points below 19.91% CEC median). PTC/STC ratio: 92.0% (rank #14,141).

NEC 690.7 Limit

### 11 Panels Max @ -10 C (600 V)

Cold Voc reaches 52.1 V at -10 C (573.1 V string) and 53.47 V at -20 C (11 max).

 8 kW Reference Array

### 23 Panels = 8,165 W STC

Occupies 41.6 m2 (448 sq ft) producing 7,512 W PTC; NEC 690.8 OCPD floor is 15.13 A (20 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 47.3 * (1 + (-0.29/100) * (-10 - 25)) = 52.1 V | OCPD = 1.56 * 9.7 = 15.13 A

Inputs from CEC Modules.csv for CertainTeed CT355M10-01: Voc=47.3 V, beta_Voc=-0.29%/C, Isc=9.7 A, STC=355.0 W, Area=1.81 m2.

**Result:** 11 panels max on 600 V (573.1 V); 23 panels for 8 kW (448 sq ft).

## What Are the Published CEC Specifications for CertainTeed CT355M10-01?

Verified electrical STC and PTC ratings, open-circuit voltage, short-circuit current, and physical area published for CertainTeed CT355M10-01. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Official California Energy Commission (NREL SAM) test parameters for CertainTeed CT355M10-01.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Nameplate Power (STC)** | 355.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| **Real-World Output (PTC)** | 326.6 W (92.0% STC) | PVUSA Test Conditions rating used for utility interconnection |
| **Open-Circuit Voltage (Voc)** | 47.3 V | Primary cold-weather string sizing limit under NEC 690.7 |
| **Short-Circuit Current (Isc)** | 9.7 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| **Max Power Voltage / Current** | 38.9 V / 9.1 A | Inverter MPPT operating window alignment |
| **Voc Temp Coefficient (beta_Voc)** | -0.29 %/C | Negative slope governing voltage rise below 25C |
| **Module Efficiency & Area** | 19.61% (1.81 m2) | Array roof footprint density |
| **Cell Count & Technology** | 72 cells (Mono-c-Si) | Monofacial backsheet |

## How Many CertainTeed CT355M10-01 Panels Build a 6 kW, 8 kW, or 10 kW Array?

Compare 6 kW, 8 kW, and 10 kW array footprints and Year-1 utility savings using CertainTeed CT355M10-01 (355.0 W).

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).

| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| **6 kW Class** | 17 | 6.04 kW | 331 sq ft | $1,512 | $2,556 |
| **8 kW Class** | 23 | 8.16 kW | 448 sq ft | $2,042 | $3,454 |
| **10 kW Class** | 29 | 10.29 kW | 565 sq ft | $2,575 | $4,355 |

## Which Sibling Wattage & Trim Variants Belong to This CertainTeed Series?

All closely matched CertainTeed wattages and cosmetic trims sharing the CertainTeed CT355M10-01 architecture. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Sibling CEC listings grouped into the CertainTeed CT355M10-01 wattage tier to avoid duplicate 5W/trim datasheets.

| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| **CertainTeed CT350M10-01** | 350.0 W | 321.8 W | 47.1 V | 38.7 V | 19.34% |
| **CertainTeed CT355M10-01** | 355.0 W | 326.6 W | 47.3 V | 38.9 V | 19.61% |
| **CertainTeed CT360M10-01** | 360.0 W | 331.3 W | 47.4 V | 39.1 V | 19.89% |

## How Many CertainTeed CT355M10-01 Modules Fit in a Cold-Weather String?

Maximum series module counts for CertainTeed CT355M10-01 from 25 C down to -20 C (-4 F) under NEC 690.7.

Computed from Voc=47.3V and beta_Voc=-0.29%/C across design ambient temperatures.

| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| **-20 C (-4 F)** | 53.47 V | 11 panels | 588.2 V | 18 panels |
| **-10 C (14 F)** | 52.1 V | 11 panels | 573.1 V | 19 panels |
| **0 C (32 F)** | 50.73 V | 11 panels | 558.0 V | 19 panels |
| **25 C (77 F STC)** | 47.3 V | 12 panels | 567.6 V | 21 panels |

## Which Cross-Brand Solar Modules Compare Closest to CertainTeed CT355M10-01?

Alternative CEC solar modules from competing brands near CertainTeed CT355M10-01 (355.0 W), including Boviet Solar Technology Co Ltd BVM6612P-355.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.

| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| [**Boviet Solar Technology Co Ltd BVM6612P-355**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm6612p-355/) Boviet Solar Technology Co Ltd | 355.0 W | Tie (0 W) | 47.3 V | 18.3% | 92.6% |
| [**AXITEC AC-355M/156-72S**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-355m-156-72s/) AXITEC | 355.0 W | Tie (0 W) | 47.4 V | 18.3% | 91.5% |
| [**Bluesun Solar Energy Tech CoLtd BSM355P-72**](https://epri-peac.com/solar-equipment/modules/bluesun-solar-energy-tech-coltd/bluesun-solar-energy-tech-coltd-bsm355p-72/) Bluesun Solar Energy Tech CoLtd | 355.0 W | Tie (0 W) | 47.52 V | 18.32% | 91.6% |
| [**AXITEC AC-360M/72S**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-360m-72s/) AXITEC | 360.0 W | +5.0 W | 47.44 V | 18.55% | 91.2% |

What to Check & Best-Fit Scenarios

## What Are the Design Limits and Best-Fit Uses for CertainTeed CT355M10-01?

Evaluate CertainTeed CT355M10-01 (355.0 W STC, 47.3 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

- Winter overvoltage boundary: at -20 C (-4 F), CertainTeed CT355M10-01 reaches 53.47 V per panel—exceeding 11 panels in series voids 600 V inverter warranties.
- Footprint constraint: 23 panels for an 8 kW build require 448 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 23 panels (448 sq ft).
- 2026 tax credit baseline: cash residential installs of CertainTeed CT355M10-01 carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

### CertainTeed CT355M10-01 8 kW Residential Fit

Needs 23 modules (448 sq ft) with a 20 A string OCPD, offsetting ~$2,042/yr at US average tariffs.

### Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 11 panels (-10 C) or 11 panels (-20 C), or compare Boviet Solar Technology Co Ltd BVM6612P-355.

### Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 326.6 W PTC.

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for CertainTeed CT355M10-01 by CertainTeed grounded in CEC test data and NEC 690.7/690.8 limits. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

### Why is CertainTeed CT355M10-01 PTC wattage (326.6 W) lower than STC (355.0 W)?

Laboratory STC tests at 25 C cell temperature, whereas real rooftop heat lowers voltage to 326.6 W PTC (92.0% retention) across CertainTeed CT355M10-01's 1.81 m2 aperture.

### Who should skip CertainTeed CT355M10-01 on a complex residential roof?

Homes with chopped dormers or heavy chimney shade should compare smaller modules or microinverters if 23 CertainTeed CT355M10-01 panels (448 sq ft) leave unusable roof gaps vs. Boviet Solar Technology Co Ltd BVM6612P-355.

### What is the 1,000 V commercial string limit for CertainTeed CT355M10-01?

On 1,000 V commercial inverters at -10 C (52.1 V cold Voc), CertainTeed CT355M10-01 fits up to 19 panels per series string. Review current municipal Authority Having Jurisdiction (AHJ) code amendments affecting CertainTeed CT355M10-01.

## Related Pages

Compare CertainTeed equipment, Boviet Solar Technology Co Ltd BVM6612P-355 specs, utility payback rates, and NEC string calculators alongside CertainTeed CT355M10-01.

[All CertainTeed Certified Solar Models](https://epri-peac.com/solar-equipment/brands/certainteed/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [Check NEC 705.12 120% Panel Busbar Backfeed Limit](https://epri-peac.com/tools/solar-busbar-120/)

## Sources

1. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- 6-10 kW Array Sizing
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From CertainTeed

- [All CertainTeed Specs](https://epri-peac.com/solar-equipment/brands/certainteed/)
- [CertainTeed CTM10455HC11-06](https://epri-peac.com/solar-equipment/modules/certainteed/certainteed-ctm10455hc11-06/)
- [CertainTeed CTTC455HC12-08](https://epri-peac.com/solar-equipment/modules/certainteed/certainteed-cttc455hc12-08/)
- [CertainTeed CTM10450HC11-06](https://epri-peac.com/solar-equipment/modules/certainteed/certainteed-ctm10450hc11-06/)
- [CertainTeed CTM10445HC11-06](https://epri-peac.com/solar-equipment/modules/certainteed/certainteed-ctm10445hc11-06/)
- [CertainTeed CTM10440HC11-06](https://epri-peac.com/solar-equipment/modules/certainteed/certainteed-ctm10440hc11-06/)