title: "Arka Energy Inc AEP-821-00015-A Specs (88.0W, 8.84V Voc)"
url: https://epri-peac.com/solar-equipment/modules/arka-energy-inc/arka-energy-inc-aep-821-00015-a/
description: "CEC datasheet for Arka Energy Inc AEP-821-00015-A: 88.0W STC, 8.84V Voc, 91-panel 8kW sizing, and NEC 690.7 limits. Source-verified US engineering data."
---

CEC PV Module

# Arka Energy Inc AEP-821-00015-A — CEC Solar Module Specifications

Manufacturer: [**Arka Energy Inc**](https://epri-peac.com/solar-equipment/brands/arka-energy-inc/) Registry: **CEC Verified Engineering Specification**

Arka Energy Inc AEP-821-00015-A is a 88.0 W STC (80.5 W PTC) Mono-c-Si solar module ranking #21,598 of 21,677 CEC listings (below all-CEC median; higher than 0.4% of peers). It delivers 14.92% efficiency, 8.84 V Voc at 25 C, and 9.73 V cold Voc at -10 C (61 panels max per 600 V string).

- **STC Wattage** : 88.0 W

- **PTC Wattage** : 80.5 W

- **Voc @ 25C** : 8.84 V

- **Efficiency** : 14.92%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Arka Energy Inc AEP-821-00015-A Compare Against Peer CEC Listings?

How Arka Energy Inc Arka Energy Inc AEP-821-00015-A handles rooftop heat (80.5 W PTC), 8 kW sizing, and cold winter string voltage.

Arka Energy Inc builds the Arka Energy Inc AEP-821-00015-A (Mono-c-Si) as a compact residential or specialty off-grid module delivering 149.2 W/m2 (4.99 percentage points below 19.91% CEC median). Compared against Luma Resources LLC LRSS28-95A (95.0 W), this model holds strong 91.5% PTC-to-STC heat retention (#15,584 of 21,677). Lower 8.84 V string voltage fits 61 panels in series at 14 F and pairs easily with microinverters, while NEC 690.8 sets a 20.97 A overcurrent floor served by a 25 A breaker.

## Where Does Arka Energy Inc AEP-821-00015-A Fall Across Listed CEC Models?

Where Arka Energy Inc AEP-821-00015-A (88.0 W) sits inside the 21,677-panel CEC STC wattage curve relative to the 385.0 W median.

## What Dataset Percentiles Define Arka Energy Inc AEP-821-00015-A?

Percentile placement of Arka Energy Inc AEP-821-00015-A across power density (149.2 W/m2), thermal retention, and nameplate STC wattage.

## What Do the Dataset Ranks Show for Arka Energy Inc AEP-821-00015-A?

Four critical engineering numbers homeowners and solar installers check first when reviewing Arka Energy Inc AEP-821-00015-A specifications. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

Rank #21,598 / 21,677

### 88.0 W STC · Higher Than 0.4%

88.0 W STC (-297.0 W vs all-CEC median) vs 410.0 W Mono-c-Si median.

Eff #19,877

### 14.92% Aperture Efficiency

Power density 149.2 W/m2 (4.99 percentage points below 19.91% CEC median). PTC/STC ratio: 91.5% (rank #15,584).

NEC 690.7 Limit

### 61 Panels Max @ -10 C (600 V)

Cold Voc reaches 9.73 V at -10 C (593.5 V string) and 9.99 V at -20 C (60 max).

 8 kW Reference Array

### 91 Panels = 8,008 W STC

Occupies 53.7 m2 (578 sq ft) producing 7,326 W PTC; NEC 690.8 OCPD floor is 20.97 A (25 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 8.84 * (1 + (-0.288/100) * (-10 - 25)) = 9.73 V | OCPD = 1.56 * 13.44 = 20.97 A

Inputs from CEC Modules.csv for Arka Energy Inc AEP-821-00015-A: Voc=8.84 V, beta_Voc=-0.288%/C, Isc=13.44 A, STC=88.0 W, Area=0.59 m2.

**Result:** 61 panels max on 600 V (593.5 V); 91 panels for 8 kW (578 sq ft).

## What Are the Published CEC Specifications for Arka Energy Inc AEP-821-00015-A?

Verified electrical STC and PTC ratings, open-circuit voltage, short-circuit current, and physical area published for Arka Energy Inc AEP-821-00015-A.

Official California Energy Commission (NREL SAM) test parameters for Arka Energy Inc AEP-821-00015-A.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Nameplate Power (STC)** | 88.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| **Real-World Output (PTC)** | 80.5 W (91.5% STC) | PVUSA Test Conditions rating used for utility interconnection |
| **Open-Circuit Voltage (Voc)** | 8.84 V | Primary cold-weather string sizing limit under NEC 690.7 |
| **Short-Circuit Current (Isc)** | 13.44 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| **Max Power Voltage / Current** | 7.4 V / 11.9 A | Inverter MPPT operating window alignment |
| **Voc Temp Coefficient (beta_Voc)** | -0.288 %/C | Negative slope governing voltage rise below 25C |
| **Module Efficiency & Area** | 14.92% (0.59 m2) | Array roof footprint density |
| **Cell Count & Technology** | 13 cells (Mono-c-Si) | Monofacial backsheet |

## How Many Arka Energy Inc AEP-821-00015-A Panels Build a 6 kW, 8 kW, or 10 kW Array?

Compare 6 kW, 8 kW, and 10 kW array footprints and Year-1 utility savings using Arka Energy Inc AEP-821-00015-A (88.0 W).

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).

| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| **6 kW Class** | 69 | 6.07 kW | 438 sq ft | $1,519 | $2,569 |
| **8 kW Class** | 91 | 8.01 kW | 578 sq ft | $2,005 | $3,390 |
| **10 kW Class** | 114 | 10.03 kW | 724 sq ft | $2,510 | $4,245 |

## How Many Arka Energy Inc AEP-821-00015-A Modules Fit in a Cold-Weather String?

Maximum series module counts for Arka Energy Inc AEP-821-00015-A from 25 C down to -20 C (-4 F) under NEC 690.7.

Computed from Voc=8.84V and beta_Voc=-0.288%/C across design ambient temperatures.

| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| **-20 C (-4 F)** | 9.99 V | 60 panels | 599.4 V | 100 panels |
| **-10 C (14 F)** | 9.73 V | 61 panels | 593.5 V | 102 panels |
| **0 C (32 F)** | 9.48 V | 63 panels | 597.2 V | 105 panels |
| **25 C (77 F STC)** | 8.84 V | 67 panels | 592.3 V | 113 panels |

## Which Cross-Brand Solar Modules Compare Closest to Arka Energy Inc AEP-821-00015-A?

Alternative CEC solar modules from competing brands near Arka Energy Inc AEP-821-00015-A (88.0 W), including Luma Resources LLC LRSS28-95A.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.

| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| [**Luma Resources LLC LRSS28-95A**](https://epri-peac.com/solar-equipment/modules/luma-resources-llc/luma-resources-llc-lrss28-95a/) Luma Resources LLC | 95.0 W | +7.0 W | 9.54 V | 16.38% | 98.9% |
| [**LUMA Resources LRSS**](https://epri-peac.com/solar-equipment/modules/luma-resources/luma-resources-lrss/) LUMA Resources | 80.0 W | -8.0 W | 10.43 V | 16.0% | 90.0% |
| [**Luma Resources LLC LRSS28-100A**](https://epri-peac.com/solar-equipment/modules/luma-resources-llc/luma-resources-llc-lrss28-100a/) Luma Resources LLC | 100.0 W | +12.0 W | 9.73 V | 17.24% | 98.9% |
| [**CertainTeed Apollo II - 75x**](https://epri-peac.com/solar-equipment/modules/certainteed/certainteed-apollo-ii-75x/) CertainTeed | 75.0 W | -13.0 W | 9.92 V | 14.15% | 85.6% |

What to Check & Best-Fit Scenarios

## What Are the Design Limits and Best-Fit Uses for Arka Energy Inc AEP-821-00015-A?

Evaluate Arka Energy Inc AEP-821-00015-A (88.0 W STC, 8.84 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

- Winter overvoltage boundary: at -20 C (-4 F), Arka Energy Inc AEP-821-00015-A reaches 9.99 V per panel—exceeding 60 panels in series voids 600 V inverter warranties.
- Footprint constraint: 91 panels for an 8 kW build require 578 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 91 panels (578 sq ft).
- 2026 tax credit baseline: cash residential installs of Arka Energy Inc AEP-821-00015-A carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

### Arka Energy Inc AEP-821-00015-A 8 kW Residential Fit

Needs 91 modules (578 sq ft) with a 25 A string OCPD, offsetting ~$2,005/yr at US average tariffs.

### Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 61 panels (-10 C) or 60 panels (-20 C), or compare Luma Resources LLC LRSS28-95A.

### Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 80.5 W PTC.

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for Arka Energy Inc AEP-821-00015-A by Arka Energy Inc grounded in CEC test data and NEC 690.7/690.8 limits.

### What fuse or breaker size does NEC 690.8 require for Arka Energy Inc AEP-821-00015-A?

Multiplying Arka Energy Inc AEP-821-00015-A's 13.44 A short-circuit current by 1.56 equals 20.97 A minimum ampacity, requiring at least a 25 A overcurrent fuse or breaker.

### Can Arka Energy Inc AEP-821-00015-A pair with microinverters instead of a 600 V string inverter?

Yes—if the microinverter DC input ceiling exceeds 9.73 V cold Voc at 14 F and handles 13.44 A Isc; string inverters cap Arka Energy Inc AEP-821-00015-A at 61 panels on 600 V.

### Is Arka Energy Inc AEP-821-00015-A eligible for the 30% federal 25D solar credit in 2026?

No. Federal Section 25D expired December 31, 2025 under Public Law 119-21, so 2026 cash installs of Arka Energy Inc AEP-821-00015-A rely on utility bill offset (~$2,005/yr at 8 kW) rather than 25D.

## Related Pages

Compare Arka Energy Inc equipment, Luma Resources LLC LRSS28-95A specs, utility payback rates, and NEC string calculators alongside Arka Energy Inc AEP-821-00015-A.

[All Arka Energy Inc Certified Solar Models](https://epri-peac.com/solar-equipment/brands/arka-energy-inc/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [Check NEC 705.12 120% Panel Busbar Backfeed Limit](https://epri-peac.com/tools/solar-busbar-120/)

## Sources

1. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- 6-10 kW Array Sizing
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)
