title: "Advance Power API-P265 Specs (265.0W, 43.27V Voc)"
url: https://epri-peac.com/solar-equipment/modules/advance-power/advance-power-api-p265/
description: "CEC datasheet for Advance Power API-P265: 265.0W STC, 43.27V Voc, 31-panel 8kW sizing, and NEC 690.7 limits. Verified US government and CEC engineering data."
---

CEC PV Module

# Advance Power API-P265 — CEC Solar Module Specifications

Manufacturer: [**Advance Power**](https://epri-peac.com/solar-equipment/brands/advance-power/) Registry: **CEC Verified Engineering Specification**

Advance Power API-P265 is a 265.0 W STC (236.0 W PTC) Multi-c-Si solar module ranking #18,880 of 21,677 CEC listings (below all-CEC median; higher than 11.7% of peers). It delivers 13.58% efficiency, 43.27 V Voc at 25 C, and 48.33 V cold Voc at -10 C (12 panels max per 600 V string).

- **STC Wattage** : 265.0 W

- **PTC Wattage** : 236.0 W

- **Voc @ 25C** : 43.27 V

- **Efficiency** : 13.58%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Advance Power API-P265 Compare Against Peer CEC Listings?

How Advance Power Advance Power API-P265 handles rooftop heat (236.0 W PTC), 8 kW sizing, and cold winter string voltage.

For NEC string engineering, Advance Power API-P265 exhibits 7.95 A short-circuit current, requiring a 12.4 A (156%) conductor rating and 15 A OCPD under NEC 690.8. Ranked #18,880 of 21,677 (13.8 W below the 278.8 W Multi-c-Si median), this compact residential or specialty off-grid module covers 60.5 m2 for an 8 kW system (38 panels for 10 kW). Mid-range 43.27 V open-circuit voltage allows up to 12 panels per 600 V string at 14 F.

## Where Does Advance Power API-P265 Fall Across Listed CEC Models?

Where Advance Power API-P265 (265.0 W) sits inside the 21,677-panel CEC STC wattage curve relative to the 385.0 W median.

## What Dataset Percentiles Define Advance Power API-P265?

Percentile placement of Advance Power API-P265 across power density (135.8 W/m2), thermal retention, and nameplate STC wattage.

## What Do the Dataset Ranks Show for Advance Power API-P265?

Four critical engineering numbers homeowners and solar installers check first when reviewing Advance Power API-P265 specifications. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

Rank #18,880 / 21,677

### 265.0 W STC · Higher Than 11.7%

265.0 W STC (-120.0 W vs all-CEC median) vs 278.8 W Multi-c-Si median.

Eff #21,170

### 13.58% Aperture Efficiency

Power density 135.8 W/m2 (6.33 percentage points below 19.91% CEC median). PTC/STC ratio: 89.1% (rank #20,440).

NEC 690.7 Limit

### 12 Panels Max @ -10 C (600 V)

Cold Voc reaches 48.33 V at -10 C (580.0 V string) and 49.77 V at -20 C (12 max).

 8 kW Reference Array

### 31 Panels = 8,215 W STC

Occupies 60.5 m2 (651 sq ft) producing 7,316 W PTC; NEC 690.8 OCPD floor is 12.4 A (15 A breaker).

NEC 690.7(A) Cold-Temperature Voc & 690.8 OCPD Formula

Voc_cold = 43.27 * (1 + (-0.334/100) * (-10 - 25)) = 48.33 V | OCPD = 1.56 * 7.95 = 12.4 A

Inputs from CEC Modules.csv for Advance Power API-P265: Voc=43.27 V, beta_Voc=-0.334%/C, Isc=7.95 A, STC=265.0 W, Area=1.951 m2.

**Result:** 12 panels max on 600 V (580.0 V); 31 panels for 8 kW (651 sq ft).

## What Are the Published CEC Specifications for Advance Power API-P265?

Verified electrical STC and PTC ratings, open-circuit voltage, short-circuit current, and physical area published for Advance Power API-P265.

Official California Energy Commission (NREL SAM) test parameters for Advance Power API-P265.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Nameplate Power (STC)** | 265.0 W | Rated DC output under Standard Test Conditions (1000 W/m2, 25C cell) |
| **Real-World Output (PTC)** | 236.0 W (89.1% STC) | PVUSA Test Conditions rating used for utility interconnection |
| **Open-Circuit Voltage (Voc)** | 43.27 V | Primary cold-weather string sizing limit under NEC 690.7 |
| **Short-Circuit Current (Isc)** | 7.95 A | Determines 156% (1.25x1.25) OCPD fuse/breaker sizing under NEC 690.8 |
| **Max Power Voltage / Current** | 36.14 V / 7.33 A | Inverter MPPT operating window alignment |
| **Voc Temp Coefficient (beta_Voc)** | -0.334 %/C | Negative slope governing voltage rise below 25C |
| **Module Efficiency & Area** | 13.58% (1.951 m2) | Array roof footprint density |
| **Cell Count & Technology** | 72 cells (Multi-c-Si) | Monofacial backsheet |

## How Many Advance Power API-P265 Panels Build a 6 kW, 8 kW, or 10 kW Array?

Compare 6 kW, 8 kW, and 10 kW array footprints and Year-1 utility savings using Advance Power API-P265 (265.0 W).

Estimated panel count, roof square footage, and Year-1 bill offset across low, average, and high US utility tariffs (0% 25D).

| Target Array | Panels | Actual DC | Roof Area | US Avg ($/yr) | CA High ($/yr) |
|---|---|---|---|---|---|
| **6 kW Class** | 23 | 6.09 kW | 483 sq ft | $1,524 | $2,577 |
| **8 kW Class** | 31 | 8.21 kW | 651 sq ft | $2,055 | $3,475 |
| **10 kW Class** | 38 | 10.07 kW | 798 sq ft | $2,520 | $4,262 |

## Which Sibling Wattage & Trim Variants Belong to This Advance Power Series?

All closely matched Advance Power wattages and cosmetic trims sharing the Advance Power API-P265 architecture. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Sibling CEC listings grouped into the Advance Power API-P265 wattage tier to avoid duplicate 5W/trim datasheets.

| Model Variant | STC (W) | PTC (W) | Voc (V) | Vmp (V) | Eff (%) |
|---|---|---|---|---|---|
| **Advance Power API-P260** | 260.0 W | 231.5 W | 43.2 V | 35.93 V | 13.33% |
| **Advance Power API-P265** | 265.0 W | 236.0 W | 43.27 V | 36.14 V | 13.58% |

## How Many Advance Power API-P265 Modules Fit in a Cold-Weather String?

Maximum series module counts for Advance Power API-P265 from 25 C down to -20 C (-4 F) under NEC 690.7.

Computed from Voc=43.27V and beta_Voc=-0.334%/C across design ambient temperatures.

| Ambient Min Temp | Cold Voc / Panel | Max Panels (600 V) | 600 V String Voc | Max Panels (1000 V) |
|---|---|---|---|---|
| **-20 C (-4 F)** | 49.77 V | 12 panels | 597.2 V | 20 panels |
| **-10 C (14 F)** | 48.33 V | 12 panels | 580.0 V | 20 panels |
| **0 C (32 F)** | 46.88 V | 12 panels | 562.6 V | 21 panels |
| **25 C (77 F STC)** | 43.27 V | 13 panels | 562.5 V | 23 panels |

## Which Cross-Brand Solar Modules Compare Closest to Advance Power API-P265?

Alternative CEC solar modules from competing brands near Advance Power API-P265 (265.0 W), including Auxin Solar AXN6P610T265. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

Nearest CEC-listed competing brands by STC power and open-circuit voltage.

| Alternative Module | STC (W) | Delta vs This | Voc (V) | Eff (%) | PTC/STC |
|---|---|---|---|---|---|
| [**Auxin Solar AXN6P610T265**](https://epri-peac.com/solar-equipment/modules/auxin-solar/auxin-solar-axn6p610t265/) Auxin Solar | 265.0 W | Tie (0 W) | 43.27 V | 13.58% | 89.1% |
| [**BYD Company Limited BYD 265P6C-36**](https://epri-peac.com/solar-equipment/modules/byd-company-limited/byd-company-limited-byd-265p6c-36/) BYD Company Limited | 265.0 W | Tie (0 W) | 43.11 V | 13.66% | 90.9% |
| [**CSI Solar Co Ltd CS6X-265P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6x-265p/) CSI Solar Co Ltd | 265.0 W | Tie (0 W) | 43.9 V | 14.31% | 88.8% |
| [**Gintung Energy ASEC-265G6S**](https://epri-peac.com/solar-equipment/modules/gintung-energy/gintung-energy-asec-265g6s/) Gintung Energy | 265.0 W | Tie (0 W) | 44.12 V | 13.55% | 89.5% |

What to Check & Best-Fit Scenarios

## What Are the Design Limits and Best-Fit Uses for Advance Power API-P265?

Evaluate Advance Power API-P265 (265.0 W STC, 43.27 V Voc) against your roof geometry, winter climate, and inverter voltage ceiling before finalizing bids.

- Winter overvoltage boundary: at -20 C (-4 F), Advance Power API-P265 reaches 49.77 V per panel—exceeding 12 panels in series voids 600 V inverter warranties.
- Footprint constraint: 31 panels for an 8 kW build require 651 sq ft of unshaded roof plane — useful on tight dormer roofs or battery cabins, though 8 kW requires 31 panels (651 sq ft).
- 2026 tax credit baseline: cash residential installs of Advance Power API-P265 carry 0% federal 25D credit after 2025-12-31, making 18.54 c/kWh+ utility avoidance key.

### Advance Power API-P265 8 kW Residential Fit

Needs 31 modules (651 sq ft) with a 15 A string OCPD, offsetting ~$2,055/yr at US average tariffs.

### Cold-Climate String Design (-10 C / -20 C)

Cap 600 V series strings at 12 panels (-10 C) or 12 panels (-20 C), or compare Auxin Solar AXN6P610T265.

### Bifacial / High-Heat Roof Check

Monofacial backsheet sealing targets flush dark shingle rooftop mounts. Real-world output tracks 236.0 W PTC.

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Technical answers for Advance Power API-P265 by Advance Power grounded in CEC test data and NEC 690.7/690.8 limits.

### Why is Advance Power API-P265 PTC wattage (236.0 W) lower than STC (265.0 W)?

Laboratory STC tests at 25 C cell temperature, whereas real rooftop heat lowers voltage to 236.0 W PTC (89.1% retention) across Advance Power API-P265's 1.951 m2 aperture.

### Who should skip Advance Power API-P265 on a complex residential roof?

Homes with chopped dormers or heavy chimney shade should compare smaller modules or microinverters if 31 Advance Power API-P265 panels (651 sq ft) leave unusable roof gaps vs. Auxin Solar AXN6P610T265.

### What is the 1,000 V commercial string limit for Advance Power API-P265?

On 1,000 V commercial inverters at -10 C (48.33 V cold Voc), Advance Power API-P265 fits up to 20 panels per series string. Review current municipal Authority Having Jurisdiction (AHJ) code amendments affecting Advance Power API-P265.

## Related Pages

Compare Advance Power equipment, Auxin Solar AXN6P610T265 specs, utility payback rates, and NEC string calculators alongside Advance Power API-P265.

[All Advance Power Certified Solar Models](https://epri-peac.com/solar-equipment/brands/advance-power/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [Check NEC 705.12 120% Panel Busbar Backfeed Limit](https://epri-peac.com/tools/solar-busbar-120/)

## Sources

1. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- 6-10 kW Array Sizing
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Advance Power

- [All Advance Power Specs](https://epri-peac.com/solar-equipment/brands/advance-power/)
- [Advance Power API-M360](https://epri-peac.com/solar-equipment/modules/advance-power/advance-power-api-m360/)
- [Advance Power API-M340](https://epri-peac.com/solar-equipment/modules/advance-power/advance-power-api-m340/)
- [Advance Power API-P330](https://epri-peac.com/solar-equipment/modules/advance-power/advance-power-api-p330/)
- [Advance Power API-P310](https://epri-peac.com/solar-equipment/modules/advance-power/advance-power-api-p310/)
- [Advance Power API-M285](https://epri-peac.com/solar-equipment/modules/advance-power/advance-power-api-m285/)