title: "Yaskawa Solectria Solar: XGI 1500 Inverter (225,000W)"
url: https://epri-peac.com/solar-equipment/inverters/yaskawa-solectria-solar/yaskawa-solectria-solar-xgi-1500-225-600-600v/
description: "CEC specs for Yaskawa Solectria Solar: XGI 1500 225-600 {600V}: 225,000W AC, 600V, 300A OCPD, and NEC 705.12 checks. Source-verified US engineering data."
---

CEC Grid-Support Inverter

# Yaskawa Solectria Solar: XGI 1500 225-600 {600V} — CEC Inverter Specifications

Manufacturer: [**Yaskawa Solectria Solar**](https://epri-peac.com/solar-equipment/brands/yaskawa-solectria-solar/) Registry: **CEC Verified Engineering Specification**

Yaskawa Solectria Solar: XGI 1500 225-600 {600V} outputs 225,000 W AC at 600 V, 3-phase (216.5 A continuous, 300 A OCPD), ranking #210 of 2,343 CEC inverters at 98.26% efficiency with a 860-1,250 V MPPT window and 1,250 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 225,000 W

- **AC Voltage** : 600 V, 3-phase

- **Min PV Breaker** : 300 A (parallel Cu feeders)

- **CEC Efficiency** : 98.26%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Yaskawa Solectria Solar: XGI 1500 225-600 {600V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 600 V, 3-phase grid-support overview for Yaskawa Solectria Solar: XGI 1500 225-600 {600V}.

Rated at 225,000 W AC (216.5 A continuous), Yaskawa Solectria Solar: XGI 1500 225-600 {600V} ranks #210 of 2,343 CEC units at 98.26% efficiency (-0.02 pts vs the 98.28% 600 V median). Minimum 75 C copper conductor sizing for its 300 A circuit is parallel Cu feeders per NEC Table 310.16. Cold-weather string Voc must remain under 1,250 V DC at record local winter lows.

## Where Does Yaskawa Solectria Solar: XGI 1500 225-600 {600V} Fall Across Listed CEC Models?

Marks Yaskawa Solectria Solar: XGI 1500 225-600 {600V} (225,000 W AC) across the California Energy Commission inverter AC capacity distribution.

## What Dataset Percentiles Define Yaskawa Solectria Solar: XGI 1500 225-600 {600V}?

Benchmarks Yaskawa Solectria Solar: XGI 1500 225-600 {600V} continuous AC output, 98.26% CEC weighted efficiency, and 300 A OCPD breaker demand.

## What Do the Dataset Ranks Show for Yaskawa Solectria Solar: XGI 1500 225-600 {600V}?

Four key NEC 705.12 and California Energy Commission metrics defining Yaskawa Solectria Solar: XGI 1500 225-600 {600V} by Yaskawa Solectria Solar.

Eff #210 / 2,343

### 98.26% CEC Weighted Efficiency

-0.02 pts vs the 98.28% 600 V median; overall power rank #238 (225,000 W, top 10.2%; higher than 89.8% of peers).

NEC 705.12 Check

### 300 A Required Backfeed OCPD

125% x 216.5 A = 270.6 A -> 300 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 860 V - 1,250 V (Max 1,250 V DC)

Tracking span of 390.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 225000.0W / 600 V 3-phase -> 216.5 A | Breaker >= 1.25 * 216.5 = 270.6 A -> 300 A

CEC Inverters.csv for Yaskawa Solectria Solar: XGI 1500 225-600 {600V}: Paco=225000.0 W, Vac=600 V, Vdcmax=1250.0 V, Eff=98.26%.

**Result:** Min 300 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (600V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for Yaskawa Solectria Solar: XGI 1500 225-600 {600V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Yaskawa Solectria Solar: XGI 1500 225-600 {600V}.

Official California Energy Commission (NREL SAM) test parameters for Yaskawa Solectria Solar: XGI 1500 225-600 {600V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 225,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 600 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,250 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 860 V - 1,250 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 208.158 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.26% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to Yaskawa Solectria Solar: XGI 1500 225-600 {600V} (600 V, 3-phase)?

Evaluates Yaskawa Solectria Solar: XGI 1500 225-600 {600V} (300 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates Yaskawa Solectria Solar: XGI 1500 225-600 {600V} (300 A required OCPD at 600 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (600V)** | 40 A | 300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (600V)** | 80 A | 300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (600V)** | 120 A | 300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (600V)** | 160 A | 300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (600V)** | 240 A | 300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which CEC PV Module Strings Pair With Yaskawa Solectria Solar: XGI 1500 225-600 {600V}?

Sample PV string lengths aligned within 860-1,250 V MPPT and 1,250 V DC max at -10 C. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

Sampled CEC PV modules aligned within 860.0-1250.0 V MPPT and 1250.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 21 to 22 panels | 12.98 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 26 to 29 panels | 12.76 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 25 to 27 panels | 11.47 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 30 panels (fixed) | 6.0 kW |

## Which Competing Grid-Support Inverters Compare to Yaskawa Solectria Solar: XGI 1500 225-600 {600V}?

Competing CEC grid-support inverters near 225,000 W AC and 600 V, 3-phase, led by Ginlong Technologies Co Ltd: S6-GU250K-EHV-US-M12 {600V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Ginlong Technologies Co Ltd: S6-GU250K-EHV-US-M12 {600V}**](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-s6-gu250k-ehv-us-m12-600v/) Ginlong Technologies Co Ltd | 248,751 W | +23751 W | 600.0 V | 1300.0 V | 98.62% |
| [**Sungrow Power Supply Co Ltd: SG200HX-US {600V}**](https://epri-peac.com/solar-equipment/inverters/sungrow-power-supply-co-ltd/sungrow-power-supply-co-ltd-sg200hx-us-600v/) Sungrow Power Supply Co Ltd | 200,444 W | -24556 W | 600.0 V | 1300.0 V | 98.23% |
| [**SolarEdge Technologies Ltd: SE250KUS {600V}**](https://epri-peac.com/solar-equipment/inverters/solaredge-technologies-ltd/solaredge-technologies-ltd-se250kus-600v/) SolarEdge Technologies Ltd | 249,907 W | +24907 W | 600.0 V | 1320.0 V | 98.7% |
| [**Chint Power Systems America: SCH250K-T-US-600 {600V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-sch250k-t-us-600-600v/) Chint Power Systems America | 250,000 W | +25000 W | 600.0 V | 1300.0 V | 98.21% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Yaskawa Solectria Solar: XGI 1500 225-600 {600V}?

Check Yaskawa Solectria Solar: XGI 1500 225-600 {600V} (225,000 W AC, 300 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,250 V DC on Yaskawa Solectria Solar: XGI 1500 225-600 {600V}.

### Yaskawa Solectria Solar: XGI 1500 225-600 {600V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 300 A OCPD breaker (216.5 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.26%) and MPPT window (860-1,250 V) directly against Ginlong Technologies Co Ltd: S6-GU250K-EHV-US-M12 {600V} (248,751 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Yaskawa Solectria Solar: XGI 1500 225-600 {600V} by Yaskawa Solectria Solar covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.

### What breaker and wire size does Yaskawa Solectria Solar: XGI 1500 225-600 {600V} require?

At 225,000 W continuous AC (600 V, 3-phase), continuous current is 216.5 A; 125% NEC 690.8/705.12 sizing requires a 300 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does Yaskawa Solectria Solar: XGI 1500 225-600 {600V} require?

At 225,000 W AC and 600 V, 3-phase, continuous line current is 216.5 A, requiring a 300 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.

### How does Yaskawa Solectria Solar: XGI 1500 225-600 {600V} compare to Ginlong Technologies Co Ltd: S6-GU250K-EHV-US-M12 {600V}?

Yaskawa Solectria Solar: XGI 1500 225-600 {600V} delivers 225,000 W AC at 98.26% CEC efficiency with a 1,250 V DC ceiling, while Ginlong Technologies Co Ltd: S6-GU250K-EHV-US-M12 {600V} outputs 248,751 W at 600 V, 3-phase.

## Related Pages

Explore Yaskawa Solectria Solar hardware, Ginlong Technologies Co Ltd: S6-GU250K-EHV-US-M12 {600V}, utility rates, and NEC 705.12 sizing calculators alongside Yaskawa Solectria Solar: XGI 1500 225-600 {600V}.

[All Yaskawa Solectria Solar Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/yaskawa-solectria-solar/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Yaskawa Solectria Solar

- [All Yaskawa Solectria Solar Specs](https://epri-peac.com/solar-equipment/brands/yaskawa-solectria-solar/)
- [Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V}](https://epri-peac.com/solar-equipment/inverters/yaskawa-solectria-solar/yaskawa-solectria-solar-xgi-1500-1mw-600-600v/)
- [Yaskawa Solectria Solar: XGI 1500-099MW-600 {600V}](https://epri-peac.com/solar-equipment/inverters/yaskawa-solectria-solar/yaskawa-solectria-solar-xgi-1500-099mw-600-600v/)
- [Yaskawa Solectria Solar: XGI 1500-085MW-600 {600V}](https://epri-peac.com/solar-equipment/inverters/yaskawa-solectria-solar/yaskawa-solectria-solar-xgi-1500-085mw-600-600v/)
- [Yaskawa Solectria Solar: SGI 750XTM {380V}](https://epri-peac.com/solar-equipment/inverters/yaskawa-solectria-solar/yaskawa-solectria-solar-sgi-750xtm-380v/)
- [Yaskawa Solectria Solar: XGI 1500-075MW-600 {600V}](https://epri-peac.com/solar-equipment/inverters/yaskawa-solectria-solar/yaskawa-solectria-solar-xgi-1500-075mw-600-600v/)