title: "Trystar LLC: OZPCS-EP40-000 {480V} Inverter (39,540W)"
url: https://epri-peac.com/solar-equipment/inverters/trystar-llc/trystar-llc-ozpcs-ep40-000-480v/
description: "CEC specs for Trystar LLC: OZPCS-EP40-000 {480V}: 39,540W AC, 480V, 60A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# Trystar LLC: OZPCS-EP40-000 {480V} — CEC Inverter Specifications

Manufacturer: [**Trystar LLC**](https://epri-peac.com/solar-equipment/brands/trystar-llc/) Registry: **CEC Verified Engineering Specification**

Trystar LLC: OZPCS-EP40-000 {480V} outputs 39,540 W AC at 480 V, 3-phase (47.6 A continuous, 60 A OCPD), ranking #1,217 of 2,343 CEC inverters at 96.77% efficiency with a 550-820 V MPPT window and 820 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 39,540 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 60 A (6 AWG Cu)

- **CEC Efficiency** : 96.77%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Trystar LLC: OZPCS-EP40-000 {480V} Compare Against Peer CEC Listings?

CEC efficiency rank (#1,217), 550-820 V MPPT tracking, and panel fit for Trystar LLC: OZPCS-EP40-000 {480V}. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Trystar LLC: OZPCS-EP40-000 {480V} from Trystar LLC outputs 47.6 A continuous AC at 480 V, 3-phase (39,540 W AC, rank #506). Paired with 6 AWG Cu conductors and a 60 A OCPD, its 96.77% CEC efficiency compares closely with Delta Electronics: M36U_120 {480V} (39,737 W). Keep NEC 690.7 winter string Voc below 820 V DC.

## Where Does Trystar LLC: OZPCS-EP40-000 {480V} Fall Across Listed CEC Models?

CEC inverter wattage histogram highlighting Trystar LLC: OZPCS-EP40-000 {480V} at 39,540 W continuous AC output. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

## What Dataset Percentiles Define Trystar LLC: OZPCS-EP40-000 {480V}?

Dataset percentiles comparing Trystar LLC: OZPCS-EP40-000 {480V} against 2,343 certified grid-support inverters nationwide. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

## What Do the Dataset Ranks Show for Trystar LLC: OZPCS-EP40-000 {480V}?

Engineering highlights for Trystar LLC: OZPCS-EP40-000 {480V} covering efficiency, 6 AWG Cu feeder, and panel compatibility. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

Eff #1,217 / 2,343

### 96.77% CEC Weighted Efficiency

-1.25 pts vs the 98.02% 480 V median; overall power rank #506 (39,540 W, top 21.7%; higher than 78.3% of peers).

NEC 705.12 Check

### 60 A Required Backfeed OCPD

125% x 47.6 A = 59.5 A -> 60 A standard OCPD using 6 AWG Cu (75 C).

MPPT Window

### 550 V - 820 V (Max 820 V DC)

Tracking span of 270.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

### PASS (120% Commercial Busbar)

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 39540.0W / 480 V 3-phase -> 47.6 A | Breaker >= 1.25 * 47.6 = 59.5 A -> 60 A

CEC Inverters.csv for Trystar LLC: OZPCS-EP40-000 {480V}: Paco=39540.0 W, Vac=480 V, Vdcmax=820.0 V, Eff=96.77%.

**Result:** Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for Trystar LLC: OZPCS-EP40-000 {480V}?

California Energy Commission Solar Equipment List parameters for Trystar LLC: OZPCS-EP40-000 {480V} (grid-tied PV inverter) interconnection. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Official California Energy Commission (NREL SAM) test parameters for Trystar LLC: OZPCS-EP40-000 {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 39,540 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 820 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 550 V - 820 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 58.3686 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 96.77% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to Trystar LLC: OZPCS-EP40-000 {480V} (480 V, 3-phase)?

Panelboard and switchgear backfeed allowances for Trystar LLC: OZPCS-EP40-000 {480V} (60 A OCPD). Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

Evaluates Trystar LLC: OZPCS-EP40-000 {480V} (60 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 60 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 60 A | PASS (120% Commercial Busbar) |
| **600A Bus / 600A Main (480V)** | 120 A | 60 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (480V)** | 160 A | 60 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 60 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With Trystar LLC: OZPCS-EP40-000 {480V}?

Representative PV panel pairings verified under NEC 690.7 cold Voc for Trystar LLC: OZPCS-EP40-000 {480V}. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

Sampled CEC PV modules aligned within 550.0-820.0 V MPPT and 820.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 13 to 14 panels | 8.26 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 17 to 19 panels | 8.36 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 16 to 18 panels | 7.65 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 20 panels (fixed) | 4.0 kW |

## Which Competing Grid-Support Inverters Compare to Trystar LLC: OZPCS-EP40-000 {480V}?

Four alternative CEC inverters matched to Trystar LLC: OZPCS-EP40-000 {480V} (39,540 W AC), led by Delta Electronics: M36U_120 {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Delta Electronics: M36U_120 {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-m36u-120-480v/) Delta Electronics | 39,737 W | +197 W | 480.0 V | 830.0 V | 97.97% |
| [**Delta Electronics: M36U_121 {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-m36u-121-480v/) Delta Electronics | 39,737 W | +197 W | 480.0 V | 830.0 V | 97.97% |
| [**Delta Electronics: M36U_122 {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-m36u-122-480v/) Delta Electronics | 39,737 W | +197 W | 480.0 V | 830.0 V | 97.97% |
| [**CSI Solar Co Ltd: CSI-40K-T480GL03-U {480V}**](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-40k-t480gl03-u-480v/) CSI Solar Co Ltd | 39,841 W | +301 W | 480.0 V | 850.0 V | 98.02% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Trystar LLC: OZPCS-EP40-000 {480V}?

Check Trystar LLC: OZPCS-EP40-000 {480V} (39,540 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 820 V DC on Trystar LLC: OZPCS-EP40-000 {480V}.

### Trystar LLC: OZPCS-EP40-000 {480V} Panel & Wire Spec

Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (47.6 A continuous).

### Alternative Inverter Comparison

Compare efficiency (96.77%) and MPPT window (550-820 V) directly against Delta Electronics: M36U_120 {480V} (39,737 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Trystar LLC: OZPCS-EP40-000 {480V} by Trystar LLC covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

### What breaker and wire size does Trystar LLC: OZPCS-EP40-000 {480V} require?

At 39,540 W continuous AC (480 V, 3-phase), continuous current is 47.6 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does Trystar LLC: OZPCS-EP40-000 {480V} require?

At 39,540 W AC and 480 V, 3-phase, continuous line current is 47.6 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does Trystar LLC: OZPCS-EP40-000 {480V} compare to Delta Electronics: M36U_120 {480V}?

Trystar LLC: OZPCS-EP40-000 {480V} delivers 39,540 W AC at 96.77% CEC efficiency with a 820 V DC ceiling, while Delta Electronics: M36U_120 {480V} outputs 39,737 W at 480 V, 3-phase.

## Related Pages

Explore Trystar LLC hardware, Delta Electronics: M36U_120 {480V}, utility rates, and NEC 705.12 sizing calculators alongside Trystar LLC: OZPCS-EP40-000 {480V}.

[All Trystar LLC Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/trystar-llc/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Trystar LLC

- [All Trystar LLC Specs](https://epri-peac.com/solar-equipment/brands/trystar-llc/)
- [Trystar LLC: OZPCS-RS40-Bxx {480V}](https://epri-peac.com/solar-equipment/inverters/trystar-llc/trystar-llc-ozpcs-rs40-bxx-480v/)
- [Trystar LLC: OZPCS-RS40-Fxx {480V}](https://epri-peac.com/solar-equipment/inverters/trystar-llc/trystar-llc-ozpcs-rs40-fxx-480v/)
- [Trystar LLC: OZPCS-RS40-BB1 {480V}](https://epri-peac.com/solar-equipment/inverters/trystar-llc/trystar-llc-ozpcs-rs40-bb1-480v/)
- [Trystar LLC: OZPCS-RS40-FB1 {480V}](https://epri-peac.com/solar-equipment/inverters/trystar-llc/trystar-llc-ozpcs-rs40-fb1-480v/)
- [Trystar LLC: OZPCS-RS35-FB0 {208V}](https://epri-peac.com/solar-equipment/inverters/trystar-llc/trystar-llc-ozpcs-rs35-fb0-208v/)