title: "Sungrow: SG60CX-US {480V} Inverter (60,182W)"
url: https://epri-peac.com/solar-equipment/inverters/sungrow/sungrow-sg60cx-us-480v/
description: "CEC specs for Sungrow: SG60CX-US {480V}: 60,182W AC, 480V, 100A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# Sungrow: SG60CX-US {480V} — CEC Inverter Specifications

Manufacturer: [**Sungrow**](https://epri-peac.com/solar-equipment/brands/sungrow/) Registry: **CEC Verified Engineering Specification**

Sungrow: SG60CX-US {480V} outputs 60,182 W AC at 480 V, 3-phase (72.4 A continuous, 100 A OCPD), ranking #363 of 2,343 CEC inverters at 97.96% efficiency with a 550-850 V MPPT window and 850 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 60,182 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 100 A (3 AWG Cu)

- **CEC Efficiency** : 97.96%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Sungrow: SG60CX-US {480V} Compare Against Peer CEC Listings?

How Sungrow Sungrow: SG60CX-US {480V} compares on 97.96% efficiency, MPPT span, and 120% busbar interconnection. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

Sungrow certifies Sungrow: SG60CX-US {480V} (grid-tied PV inverter, listed since 2024-09-23) at 60,182 W AC (10,182 W above the 50,000 W 480 V median). Its 850 V DC ceiling pairs with an MPPT window of 550-850 V (span 300.0 V). Under NEC 690.8/705.12, 125% sizing demands 3 AWG Cu conductors on a 100 A OCPD.

## Where Does Sungrow: SG60CX-US {480V} Fall Across Listed CEC Models?

Position of Sungrow: SG60CX-US {480V} (60,182 W AC) relative to the 7,680 W CEC median inverter. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

## What Dataset Percentiles Define Sungrow: SG60CX-US {480V}?

Percentile placement of Sungrow: SG60CX-US {480V} across AC power class, conversion efficiency, and backfeed breaker size. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

## What Do the Dataset Ranks Show for Sungrow: SG60CX-US {480V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for Sungrow: SG60CX-US {480V}. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Eff #363 / 2,343

### 97.96% CEC Weighted Efficiency

-0.06 pts vs the 98.02% 480 V median; overall power rank #398 (60,182 W, top 17.0%; higher than 83.0% of peers).

NEC 705.12 Check

### 100 A Required Backfeed OCPD

125% x 72.4 A = 90.5 A -> 100 A standard OCPD using 3 AWG Cu (75 C).

MPPT Window

### 550 V - 850 V (Max 850 V DC)

Tracking span of 300.0 V; listed since 2024-09-23 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 60182.0W / 480 V 3-phase -> 72.4 A | Breaker >= 1.25 * 72.4 = 90.5 A -> 100 A

CEC Inverters.csv for Sungrow: SG60CX-US {480V}: Paco=60182.0 W, Vac=480 V, Vdcmax=850.0 V, Eff=97.96%.

**Result:** Min 100 A breaker & 3 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for Sungrow: SG60CX-US {480V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for Sungrow: SG60CX-US {480V}. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Official California Energy Commission (NREL SAM) test parameters for Sungrow: SG60CX-US {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 60,182 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 850 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 550 V - 850 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 86.5296 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 97.96% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2024-09-23 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to Sungrow: SG60CX-US {480V} (480 V, 3-phase)?

Check whether Sungrow: SG60CX-US {480V} (100 A breaker) fits without main breaker derate or supply-side taps. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Evaluates Sungrow: SG60CX-US {480V} (100 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 100 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 100 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (480V)** | 120 A | 100 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (480V)** | 160 A | 100 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 100 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With Sungrow: SG60CX-US {480V}?

Verified cold-weather (-10 C) series module counts matched to Sungrow: SG60CX-US {480V}'s 850 V DC ceiling. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

Sampled CEC PV modules aligned within 550.0-850.0 V MPPT and 850.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 13 to 15 panels | 8.85 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 17 to 20 panels | 8.8 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 16 to 18 panels | 7.65 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 20 panels (fixed) | 4.0 kW |

## Which Competing Grid-Support Inverters Compare to Sungrow: SG60CX-US {480V}?

Alternative CEC inverters comparable to Sungrow: SG60CX-US {480V}, including BYD Auto Industry Company Limited: BEG60KTL-U-R1 {480V} (60,276 W) at 480 V, 3-phase.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**BYD Auto Industry Company Limited: BEG60KTL-U-R1 {480V}**](https://epri-peac.com/solar-equipment/inverters/byd-auto-industry-company-limited/byd-auto-industry-company-limited-beg60ktl-u-r1-480v/) BYD Auto Industry Company Limited | 60,276 W | +94 W | 480.0 V | 950.0 V | 95.69% |
| [**ABB: PVS-60-TL-R-US {480V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-60-tl-r-us-480v/) ABB | 60,033 W | -149 W | 480.0 V | 800.0 V | 98.18% |
| [**ABB: PVS-60-TL-S-R-US {480V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-60-tl-s-r-us-480v/) ABB | 60,033 W | -149 W | 480.0 V | 800.0 V | 98.18% |
| [**ABB: PVS-60-TL-S-US {480V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-60-tl-s-us-480v/) ABB | 60,033 W | -149 W | 480.0 V | 800.0 V | 98.18% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Sungrow: SG60CX-US {480V}?

Check Sungrow: SG60CX-US {480V} (60,182 W AC, 100 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 850 V DC on Sungrow: SG60CX-US {480V}.

### Sungrow: SG60CX-US {480V} Panel & Wire Spec

Size 75 C copper conductors at 3 AWG Cu on a 100 A OCPD breaker (72.4 A continuous).

### Alternative Inverter Comparison

Compare efficiency (97.96%) and MPPT window (550-850 V) directly against BYD Auto Industry Company Limited: BEG60KTL-U-R1 {480V} (60,276 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Sungrow: SG60CX-US {480V} by Sungrow covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection. Inspect manufacturer nameplate documentation, UL listing boundaries, and utility rate schedules closely before ordering electrical hardware.

### What breaker and wire size does Sungrow: SG60CX-US {480V} require?

At 60,182 W continuous AC (480 V, 3-phase), continuous current is 72.4 A; 125% NEC 690.8/705.12 sizing requires a 100 A breaker and 3 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does Sungrow: SG60CX-US {480V} require?

At 60,182 W AC and 480 V, 3-phase, continuous line current is 72.4 A, requiring a 100 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does Sungrow: SG60CX-US {480V} compare to BYD Auto Industry Company Limited: BEG60KTL-U-R1 {480V}?

Sungrow: SG60CX-US {480V} delivers 60,182 W AC at 97.96% CEC efficiency with a 850 V DC ceiling, while BYD Auto Industry Company Limited: BEG60KTL-U-R1 {480V} outputs 60,276 W at 480 V, 3-phase.

## Related Pages

Explore Sungrow hardware, BYD Auto Industry Company Limited: BEG60KTL-U-R1 {480V}, utility rates, and NEC 705.12 sizing calculators alongside Sungrow: SG60CX-US {480V}.

[All Sungrow Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/sungrow/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Sungrow

- [All Sungrow Specs](https://epri-peac.com/solar-equipment/brands/sungrow/)
- [Sungrow: SG36CX-US {480V}](https://epri-peac.com/solar-equipment/inverters/sungrow/sungrow-sg36cx-us-480v/)