title: "Sungrow: SG36CX-US {480V} Inverter (36,046W)"
url: https://epri-peac.com/solar-equipment/inverters/sungrow/sungrow-sg36cx-us-480v/
description: "CEC specs for Sungrow: SG36CX-US {480V}: 36,046W AC, 480V, 60A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# Sungrow: SG36CX-US {480V} — CEC Inverter Specifications

Manufacturer: [**Sungrow**](https://epri-peac.com/solar-equipment/brands/sungrow/) Registry: **CEC Verified Engineering Specification**

Sungrow: SG36CX-US {480V} outputs 36,046 W AC at 480 V, 3-phase (43.4 A continuous, 60 A OCPD), ranking #350 of 2,343 CEC inverters at 97.99% efficiency with a 550-850 V MPPT window and 850 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 36,046 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 60 A (6 AWG Cu)

- **CEC Efficiency** : 97.99%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Sungrow: SG36CX-US {480V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 480 V, 3-phase grid-support overview for Sungrow: SG36CX-US {480V}. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

Rated at 36,046 W AC (43.4 A continuous), Sungrow: SG36CX-US {480V} ranks #350 of 2,343 CEC units at 97.99% efficiency (-0.03 pts vs the 98.02% 480 V median). Minimum 75 C copper conductor sizing for its 60 A circuit is 6 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 850 V DC at record local winter lows.

## Where Does Sungrow: SG36CX-US {480V} Fall Across Listed CEC Models?

Marks Sungrow: SG36CX-US {480V} (36,046 W AC) across the California Energy Commission inverter AC capacity distribution. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

## What Dataset Percentiles Define Sungrow: SG36CX-US {480V}?

Benchmarks Sungrow: SG36CX-US {480V} continuous AC output, 97.99% CEC weighted efficiency, and 60 A OCPD breaker demand. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

## What Do the Dataset Ranks Show for Sungrow: SG36CX-US {480V}?

Four key NEC 705.12 and California Energy Commission metrics defining Sungrow: SG36CX-US {480V} by Sungrow. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Eff #350 / 2,343

### 97.99% CEC Weighted Efficiency

-0.03 pts vs the 98.02% 480 V median; overall power rank #509 (36,046 W, top 21.7%; higher than 78.3% of peers).

NEC 705.12 Check

### 60 A Required Backfeed OCPD

125% x 43.4 A = 54.2 A -> 60 A standard OCPD using 6 AWG Cu (75 C).

MPPT Window

### 550 V - 850 V (Max 850 V DC)

Tracking span of 300.0 V; listed since 2024-09-23 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### PASS (120% Commercial Busbar)

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 36046.0W / 480 V 3-phase -> 43.4 A | Breaker >= 1.25 * 43.4 = 54.2 A -> 60 A

CEC Inverters.csv for Sungrow: SG36CX-US {480V}: Paco=36046.0 W, Vac=480 V, Vdcmax=850.0 V, Eff=97.99%.

**Result:** Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for Sungrow: SG36CX-US {480V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Sungrow: SG36CX-US {480V}. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Official California Energy Commission (NREL SAM) test parameters for Sungrow: SG36CX-US {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 36,046 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 850 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 550 V - 850 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 51.8112 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 97.99% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2024-09-23 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to Sungrow: SG36CX-US {480V} (480 V, 3-phase)?

Evaluates Sungrow: SG36CX-US {480V} (60 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates Sungrow: SG36CX-US {480V} (60 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 60 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 60 A | PASS (120% Commercial Busbar) |
| **600A Bus / 600A Main (480V)** | 120 A | 60 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (480V)** | 160 A | 60 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 60 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With Sungrow: SG36CX-US {480V}?

Sample PV string lengths aligned within 550-850 V MPPT and 850 V DC max at -10 C. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.

Sampled CEC PV modules aligned within 550.0-850.0 V MPPT and 850.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 13 to 15 panels | 8.85 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 17 to 20 panels | 8.8 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 16 to 18 panels | 7.65 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 20 panels (fixed) | 4.0 kW |

## Which Competing Grid-Support Inverters Compare to Sungrow: SG36CX-US {480V}?

Competing CEC grid-support inverters near 36,046 W AC and 480 V, 3-phase, led by Canadian Solar Inc: CSI-36KTL-CT {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Canadian Solar Inc: CSI-36KTL-CT {480V}**](https://epri-peac.com/solar-equipment/inverters/canadian-solar-inc/canadian-solar-inc-csi-36ktl-ct-480v/) Canadian Solar Inc | 36,000 W | -46 W | 480.0 V | 800.0 V | 98.09% |
| [**Canadian Solar Inc: CSI-36KTL-GS-FL {480V}**](https://epri-peac.com/solar-equipment/inverters/canadian-solar-inc/canadian-solar-inc-csi-36ktl-gs-fl-480v/) Canadian Solar Inc | 36,000 W | -46 W | 480.0 V | 780.0 V | 98.05% |
| [**Chint Power Systems America: CPS SCA36KTL-DO/US-480 {480V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sca36ktl-do-us-480-480v/) Chint Power Systems America | 36,000 W | -46 W | 480.0 V | 850.0 V | 97.62% |
| [**Chint Power Systems America: CPS SCA36KTL-DO/US {480V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-sca36ktl-do-us-480v/) Chint Power Systems America | 36,000 W | -46 W | 480.0 V | 800.0 V | 98.09% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Sungrow: SG36CX-US {480V}?

Check Sungrow: SG36CX-US {480V} (36,046 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 850 V DC on Sungrow: SG36CX-US {480V}.

### Sungrow: SG36CX-US {480V} Panel & Wire Spec

Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (43.4 A continuous).

### Alternative Inverter Comparison

Compare efficiency (97.99%) and MPPT window (550-850 V) directly against Canadian Solar Inc: CSI-36KTL-CT {480V} (36,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Sungrow: SG36CX-US {480V} by Sungrow covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection. All figures trace directly to published federal energy filings, state electrical boards, CEC datasheets, and NFPA 70 NEC tables.

### What breaker and wire size does Sungrow: SG36CX-US {480V} require?

At 36,046 W continuous AC (480 V, 3-phase), continuous current is 43.4 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does Sungrow: SG36CX-US {480V} require?

At 36,046 W AC and 480 V, 3-phase, continuous line current is 43.4 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does Sungrow: SG36CX-US {480V} compare to Canadian Solar Inc: CSI-36KTL-CT {480V}?

Sungrow: SG36CX-US {480V} delivers 36,046 W AC at 97.99% CEC efficiency with a 850 V DC ceiling, while Canadian Solar Inc: CSI-36KTL-CT {480V} outputs 36,000 W at 480 V, 3-phase.

## Related Pages

Explore Sungrow hardware, Canadian Solar Inc: CSI-36KTL-CT {480V}, utility rates, and NEC 705.12 sizing calculators alongside Sungrow: SG36CX-US {480V}.

[All Sungrow Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/sungrow/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Sungrow

- [All Sungrow Specs](https://epri-peac.com/solar-equipment/brands/sungrow/)
- [Sungrow: SG60CX-US {480V}](https://epri-peac.com/solar-equipment/inverters/sungrow/sungrow-sg60cx-us-480v/)