title: "Sungrow Power Supply Co Ltd Inverter (1,053,000W)"
url: https://epri-peac.com/solar-equipment/inverters/sungrow-power-supply-co-ltd/sungrow-power-supply-co-ltd-sg3150ud-mv-us-600v/
description: "CEC specs for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}: 1,053,000W AC, 600V, 1300A OCPD, and NEC 705.12 checks. Source-verified US engineering data."
---

CEC Grid-Support Inverter

# Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} — CEC Inverter Specifications

Manufacturer: [**Sungrow Power Supply Co Ltd**](https://epri-peac.com/solar-equipment/brands/sungrow-power-supply-co-ltd/) Registry: **CEC Verified Engineering Specification**

Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} outputs 1,053,000 W AC at 600 V, 3-phase (1013.3 A continuous, 1,300 A OCPD), ranking #1,002 of 2,343 CEC inverters at 97.01% efficiency with a 875-1,438 V MPPT window and 1,438 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 1,053,000 W

- **AC Voltage** : 600 V, 3-phase

- **Min PV Breaker** : 1,300 A (parallel Cu feeders)

- **CEC Efficiency** : 97.01%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 600 V, 3-phase grid-support overview for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}.

Ranking #160 of 2,343 CEC inverters (top 6.8%; higher than 93.2% of peers), Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} is a hybrid battery-capable inverter delivering 1,053,000 W continuous AC at 600 V, 3-phase (1013.3 A continuous). Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap. Weighted CEC efficiency reaches 97.01% (-1.27 pts vs the 98.28% 600 V median) against peers like Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V} (1,000,000 W).

## Where Does Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} Fall Across Listed CEC Models?

Marks Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} (1,053,000 W AC) across the California Energy Commission inverter AC capacity distribution.

## What Dataset Percentiles Define Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}?

Benchmarks Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} continuous AC output, 97.01% CEC weighted efficiency, and 1,300 A OCPD breaker demand.

## What Do the Dataset Ranks Show for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}?

Four key NEC 705.12 and California Energy Commission metrics defining Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} by Sungrow Power Supply Co Ltd.

Eff #1,002 / 2,343

### 97.01% CEC Weighted Efficiency

-1.27 pts vs the 98.28% 600 V median; overall power rank #160 (1,053,000 W, top 6.8%; higher than 93.2% of peers).

NEC 705.12 Check

### 1,300 A Required Backfeed OCPD

125% x 1013.3 A = 1266.6 A -> 1,300 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 875 V - 1,438 V (Max 1,438 V DC)

Tracking span of 563.0 V; listed since 2024-04-11 (hybrid battery-capable inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 1053000.0W / 600 V 3-phase -> 1013.3 A | Breaker >= 1.25 * 1013.3 = 1266.6 A -> 1,300 A

CEC Inverters.csv for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}: Paco=1053000.0 W, Vac=600 V, Vdcmax=1438.0 V, Eff=97.01%.

**Result:** Min 1,300 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (600V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}.

Official California Energy Commission (NREL SAM) test parameters for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 1,053,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 600 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,438 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 875 V - 1,438 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 986.828 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 97.01% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2024-04-11 / Hybrid: Yes (Battery Capable) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} (600 V, 3-phase)?

Evaluates Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} (1,300 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} (1300 A required OCPD at 600 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (600V)** | 40 A | 1,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (600V)** | 80 A | 1,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (600V)** | 120 A | 1,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (600V)** | 160 A | 1,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (600V)** | 240 A | 1,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which CEC PV Module Strings Pair With Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}?

Sample PV string lengths aligned within 875-1,438 V MPPT and 1,438 V DC max at -10 C. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Sampled CEC PV modules aligned within 875.0-1438.0 V MPPT and 1438.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 21 to 25 panels | 14.75 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 27 to 34 panels | 14.96 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 26 to 32 panels | 13.6 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 31 to 35 panels | 7.0 kW |

## Which Competing Grid-Support Inverters Compare to Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}?

Competing CEC grid-support inverters near 1,053,000 W AC and 600 V, 3-phase, led by Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V}**](https://epri-peac.com/solar-equipment/inverters/yaskawa-solectria-solar/yaskawa-solectria-solar-xgi-1500-1mw-600-600v/) Yaskawa Solectria Solar | 1,000,000 W | -53000 W | 600.0 V | 1250.0 V | 98.47% |
| [**DYNAPOWER COMPANY LLC: CPS-1250 Gen5 {600V}**](https://epri-peac.com/solar-equipment/inverters/dynapower-company-llc/dynapower-company-llc-cps-1250-gen5-600v/) DYNAPOWER COMPANY LLC | 999,576 W | -53424 W | 600.0 V | 1500.0 V | 98.44% |
| [**Yaskawa Solectria Solar: XGI 1500-099MW-600 {600V}**](https://epri-peac.com/solar-equipment/inverters/yaskawa-solectria-solar/yaskawa-solectria-solar-xgi-1500-099mw-600-600v/) Yaskawa Solectria Solar | 999,000 W | -54000 W | 600.0 V | 1250.0 V | 98.47% |
| [**Power Electronics: FS1100CU15O3 {600V}**](https://epri-peac.com/solar-equipment/inverters/power-electronics/power-electronics-fs1100cu15o3-600v/) Power Electronics | 1,176,440 W | +123440 W | 600.0 V | 1200.0 V | 97.93% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}?

Check Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} (1,053,000 W AC, 1,300 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,438 V DC on Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}.

### Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 1,300 A OCPD breaker (1013.3 A continuous).

### Alternative Inverter Comparison

Compare efficiency (97.01%) and MPPT window (875-1,438 V) directly against Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V} (1,000,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} by Sungrow Power Supply Co Ltd covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.

### What breaker and wire size does Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} require?

At 1,053,000 W continuous AC (600 V, 3-phase), continuous current is 1013.3 A; 125% NEC 690.8/705.12 sizing requires a 1,300 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} require?

At 1,053,000 W AC and 600 V, 3-phase, continuous line current is 1013.3 A, requiring a 1,300 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.

### How does Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} compare to Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V}?

Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V} delivers 1,053,000 W AC at 97.01% CEC efficiency with a 1,438 V DC ceiling, while Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V} outputs 1,000,000 W at 600 V, 3-phase.

## Related Pages

Explore Sungrow Power Supply Co Ltd hardware, Yaskawa Solectria Solar: XGI 1500-1MW-600 {600V}, utility rates, and NEC 705.12 sizing calculators alongside Sungrow Power Supply Co Ltd: SG3150UD-MV-US {600V}.

[All Sungrow Power Supply Co Ltd Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/sungrow-power-supply-co-ltd/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Sungrow Power Supply Co Ltd

- [All Sungrow Power Supply Co Ltd Specs](https://epri-peac.com/solar-equipment/brands/sungrow-power-supply-co-ltd/)
- [Sungrow Power Supply Co Ltd: SG3600UD {630V}](https://epri-peac.com/solar-equipment/inverters/sungrow-power-supply-co-ltd/sungrow-power-supply-co-ltd-sg3600ud-630v/)
- [Sungrow Power Supply Co Ltd: SG3425UD {600V}](https://epri-peac.com/solar-equipment/inverters/sungrow-power-supply-co-ltd/sungrow-power-supply-co-ltd-sg3425ud-600v/)
- [Sungrow Power Supply Co Ltd: SG3150U {630V}](https://epri-peac.com/solar-equipment/inverters/sungrow-power-supply-co-ltd/sungrow-power-supply-co-ltd-sg3150u-630v/)
- [Sungrow Power Supply Co Ltd: SC2500UD-US {900V}](https://epri-peac.com/solar-equipment/inverters/sungrow-power-supply-co-ltd/sungrow-power-supply-co-ltd-sc2500ud-us-900v/)
- [Sungrow Power Supply Co Ltd: SC2500U {550V}](https://epri-peac.com/solar-equipment/inverters/sungrow-power-supply-co-ltd/sungrow-power-supply-co-ltd-sc2500u-550v/)