title: "Star Charge Americas Corp Inverter (124,382W)"
url: https://epri-peac.com/solar-equipment/inverters/star-charge-americas-corp/star-charge-americas-corp-si125tult00-480v/
description: "CEC specs for Star Charge Americas Corp: SI125TULT00 {480V}: 124,382W AC, 480V, 200A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# Star Charge Americas Corp: SI125TULT00 {480V} — CEC Inverter Specifications

Manufacturer: [**Star Charge Americas Corp**](https://epri-peac.com/solar-equipment/brands/star-charge-americas-corp/) Registry: **CEC Verified Engineering Specification**

Star Charge Americas Corp: SI125TULT00 {480V} outputs 124,382 W AC at 480 V, 3-phase (149.6 A continuous, 200 A OCPD), ranking #79 of 2,343 CEC inverters at 98.49% efficiency with a 750-1,000 V MPPT window and 1,000 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 124,382 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 200 A (3/0 AWG Cu)

- **CEC Efficiency** : 98.49%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Star Charge Americas Corp: SI125TULT00 {480V} Compare Against Peer CEC Listings?

How Star Charge Americas Corp Star Charge Americas Corp: SI125TULT00 {480V} compares on 98.49% efficiency, MPPT span, and 120% busbar interconnection.

With a 750-1,000 V MPPT tracking band and 1,000 V DC ceiling, Star Charge Americas Corp: SI125TULT00 {480V} handles 124,382 W continuous AC (74,382 W above the 50,000 W 480 V median). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Installers comparing Star Charge Americas Corp against Delta Electronics: PCS125HV {480V} (124,312 W) should verify whether active in CEC directory grid-support firmware meets local IEEE 1547 utility rules.

## Where Does Star Charge Americas Corp: SI125TULT00 {480V} Fall Across Listed CEC Models?

Position of Star Charge Americas Corp: SI125TULT00 {480V} (124,382 W AC) relative to the 7,680 W CEC median inverter.

## What Dataset Percentiles Define Star Charge Americas Corp: SI125TULT00 {480V}?

Percentile placement of Star Charge Americas Corp: SI125TULT00 {480V} across AC power class, conversion efficiency, and backfeed breaker size.

## What Do the Dataset Ranks Show for Star Charge Americas Corp: SI125TULT00 {480V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for Star Charge Americas Corp: SI125TULT00 {480V}.

Eff #79 / 2,343

### 98.49% CEC Weighted Efficiency

+0.47 pts vs the 98.02% 480 V median; overall power rank #320 (124,382 W, top 13.7%; higher than 86.3% of peers).

NEC 705.12 Check

### 200 A Required Backfeed OCPD

125% x 149.6 A = 187.0 A -> 200 A standard OCPD using 3/0 AWG Cu (75 C).

MPPT Window

### 750 V - 1,000 V (Max 1,000 V DC)

Tracking span of 250.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 124382.0W / 480 V 3-phase -> 149.6 A | Breaker >= 1.25 * 149.6 = 187.0 A -> 200 A

CEC Inverters.csv for Star Charge Americas Corp: SI125TULT00 {480V}: Paco=124382.0 W, Vac=480 V, Vdcmax=1000.0 V, Eff=98.49%.

**Result:** Min 200 A breaker & 3/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for Star Charge Americas Corp: SI125TULT00 {480V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for Star Charge Americas Corp: SI125TULT00 {480V}.

Official California Energy Commission (NREL SAM) test parameters for Star Charge Americas Corp: SI125TULT00 {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 124,382 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,000 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 750 V - 1,000 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 154.011 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.49% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to Star Charge Americas Corp: SI125TULT00 {480V} (480 V, 3-phase)?

Check whether Star Charge Americas Corp: SI125TULT00 {480V} (200 A breaker) fits without main breaker derate or supply-side taps.

Evaluates Star Charge Americas Corp: SI125TULT00 {480V} (200 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (480V)** | 120 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (480V)** | 160 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 200 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With Star Charge Americas Corp: SI125TULT00 {480V}?

Verified cold-weather (-10 C) series module counts matched to Star Charge Americas Corp: SI125TULT00 {480V}'s 1,000 V DC ceiling.

Sampled CEC PV modules aligned within 750.0-1000.0 V MPPT and 1000.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 23 panels (fixed) | 10.12 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 22 panels (fixed) | 9.35 kW |
| [**G-Star Pte Ltd GSN8K66T(H)740WT**](https://epri-peac.com/solar-equipment/modules/g-star-pte-ltd/g-star-pte-ltd-gsn8k66t-h-740wt/) | 740.0 W | 54.38 V | 18 panels (fixed) | 13.32 kW |
| [**Hansol Technics Co Ltd HA650-AE-NNEA0**](https://epri-peac.com/solar-equipment/modules/hansol-technics-co-ltd/hansol-technics-co-ltd-ha650-ae-nnea0/) | 650.0 W | 61.2 V | 16 panels (fixed) | 10.4 kW |

## Which Competing Grid-Support Inverters Compare to Star Charge Americas Corp: SI125TULT00 {480V}?

Alternative CEC inverters comparable to Star Charge Americas Corp: SI125TULT00 {480V}, including Delta Electronics: PCS125HV {480V} (124,312 W) at 480 V, 3-phase.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Delta Electronics: PCS125HV {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-pcs125hv-480v/) Delta Electronics | 124,312 W | -70 W | 480.0 V | 1250.0 V | 97.65% |
| [**Ginlong Technologies Co Ltd: S5-GC125K-US {480V}**](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-s5-gc125k-us-480v/) Ginlong Technologies Co Ltd | 124,991 W | +609 W | 480.0 V | 850.0 V | 97.88% |
| [**Chint Power Systems America: CPS ECB125KTL-M/US-480 {480V}**](https://epri-peac.com/solar-equipment/inverters/chint-power-systems-america/chint-power-systems-america-cps-ecb125ktl-m-us-480-480v/) Chint Power Systems America | 125,000 W | +618 W | 480.0 V | 1100.0 V | 97.2% |
| [**Delta Electronics: DES10JB125K01 {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-des10jb125k01-480v/) Delta Electronics | 125,000 W | +618 W | 480.0 V | 1000.0 V | 97.01% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Star Charge Americas Corp: SI125TULT00 {480V}?

Check Star Charge Americas Corp: SI125TULT00 {480V} (124,382 W AC, 200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,000 V DC on Star Charge Americas Corp: SI125TULT00 {480V}.

### Star Charge Americas Corp: SI125TULT00 {480V} Panel & Wire Spec

Size 75 C copper conductors at 3/0 AWG Cu on a 200 A OCPD breaker (149.6 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.49%) and MPPT window (750-1,000 V) directly against Delta Electronics: PCS125HV {480V} (124,312 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Star Charge Americas Corp: SI125TULT00 {480V} by Star Charge Americas Corp covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

### What breaker and wire size does Star Charge Americas Corp: SI125TULT00 {480V} require?

At 124,382 W continuous AC (480 V, 3-phase), continuous current is 149.6 A; 125% NEC 690.8/705.12 sizing requires a 200 A breaker and 3/0 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does Star Charge Americas Corp: SI125TULT00 {480V} require?

At 124,382 W AC and 480 V, 3-phase, continuous line current is 149.6 A, requiring a 200 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does Star Charge Americas Corp: SI125TULT00 {480V} compare to Delta Electronics: PCS125HV {480V}?

Star Charge Americas Corp: SI125TULT00 {480V} delivers 124,382 W AC at 98.49% CEC efficiency with a 1,000 V DC ceiling, while Delta Electronics: PCS125HV {480V} outputs 124,312 W at 480 V, 3-phase.

## Related Pages

Explore Star Charge Americas Corp hardware, Delta Electronics: PCS125HV {480V}, utility rates, and NEC 705.12 sizing calculators alongside Star Charge Americas Corp: SI125TULT00 {480V}.

[All Star Charge Americas Corp Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/star-charge-americas-corp/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Star Charge Americas Corp

- [All Star Charge Americas Corp Specs](https://epri-peac.com/solar-equipment/brands/star-charge-americas-corp/)
- [Star Charge Americas Corp: SI135TULT10 {480V}](https://epri-peac.com/solar-equipment/inverters/star-charge-americas-corp/star-charge-americas-corp-si135tult10-480v/)
- [Star Charge Americas Corp: SI135TULT00 {480V}](https://epri-peac.com/solar-equipment/inverters/star-charge-americas-corp/star-charge-americas-corp-si135tult00-480v/)
- [Star Charge Americas Corp: SI125TULT10 {480V}](https://epri-peac.com/solar-equipment/inverters/star-charge-americas-corp/star-charge-americas-corp-si125tult10-480v/)
- [Star Charge Americas Corp: SI104LULA00 {240V}](https://epri-peac.com/solar-equipment/inverters/star-charge-americas-corp/star-charge-americas-corp-si104lula00-240v/)
- [Star Charge Americas Corp: SI104LULA00 {208V}](https://epri-peac.com/solar-equipment/inverters/star-charge-americas-corp/star-charge-americas-corp-si104lula00-208v/)