title: "Sparq Systems: Q1200-4102 {240V} Inverter (1,203W)"
url: https://epri-peac.com/solar-equipment/inverters/sparq-systems/sparq-systems-q1200-4102-240v/
description: "CEC specs for Sparq Systems: Q1200-4102 {240V}: 1,203W AC, 240V, 15A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# Sparq Systems: Q1200-4102 {240V} — CEC Inverter Specifications

Manufacturer: [**Sparq Systems**](https://epri-peac.com/solar-equipment/brands/sparq-systems/) Registry: **CEC Verified Engineering Specification**

Sparq Systems: Q1200-4102 {240V} outputs 1,203 W AC at 240 V (5.0 A continuous, 15 A OCPD), ranking #743 of 2,343 CEC inverters at 97.23% efficiency with a 36-38 V MPPT window and 38 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 1,203 W

- **AC Voltage** : 240 V

- **Min PV Breaker** : 15 A (14 AWG Cu)

- **CEC Efficiency** : 97.23%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Sparq Systems: Q1200-4102 {240V} Compare Against Peer CEC Listings?

Breaker sizing (15 A), 14 AWG Cu wire rules, and DC input limits for Sparq Systems: Q1200-4102 {240V}.

For NEC 705.12 solar interconnection, Sparq Systems: Q1200-4102 {240V} outputs 5.0 A continuous AC at 240 V and needs a 15 A backfeed breaker on 14 AWG Cu (75 C). Requires a 15 A breaker, passing directly inside a standard 200 A main / 200 A busbar panel (40 A limit). Conversion efficiency scores 97.23% (#743 of 2,343, +0.41 pts vs overall CEC median).

## Where Does Sparq Systems: Q1200-4102 {240V} Fall Across Listed CEC Models?

Output power comparison showing where Sparq Systems: Q1200-4102 {240V} sits among all 2,343 CEC-listed grid-support inverters. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

## What Dataset Percentiles Define Sparq Systems: Q1200-4102 {240V}?

Relative ranking of Sparq Systems: Q1200-4102 {240V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

## What Do the Dataset Ranks Show for Sparq Systems: Q1200-4102 {240V}?

Snapshot of Sparq Systems: Q1200-4102 {240V} efficiency rank (#743), OCPD breaker size, MPPT span, and busbar verdict. Every reported metric links directly to federal public records or state regulatory filings with zero paid contractor placements.

Eff #743 / 2,343

### 97.23% CEC Weighted Efficiency

+0.55 pts vs the 96.68% 240 V median; overall power rank #1,813 (1,203 W, below CEC median; higher than 22.6% of peers).

NEC 705.12 Check

### 15 A Required Backfeed OCPD

125% x 5.0 A = 6.2 A -> 15 A standard OCPD using 14 AWG Cu (75 C).

MPPT Window

### 36 V - 38 V (Max 38 V DC)

Tracking span of 2.0 V; active in CEC directory (grid-tied PV inverter).

Panel Fit (240V)

### PASS (120% Rule)

200A/200A panel allows 40A PV backfeed; 200A/175A derate allows 65A; 225A/200A allows 70A.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 1203.0W / 240 V -> 5.0 A | Breaker >= 1.25 * 5.0 = 6.2 A -> 15 A

CEC Inverters.csv for Sparq Systems: Q1200-4102 {240V}: Paco=1203.0 W, Vac=240 V, Vdcmax=38.0 V, Eff=97.23%.

**Result:** Min 15 A breaker & 14 AWG Cu (75 C); 200A Bus / 200A Main: PASS (120% Rule).

## What Are the Published CEC Specifications for Sparq Systems: Q1200-4102 {240V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Sparq Systems: Q1200-4102 {240V}. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Official California Energy Commission (NREL SAM) test parameters for Sparq Systems: Q1200-4102 {240V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 1,203 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 240 V | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 38 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 36 V - 38 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 33.44 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 97.23% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |

## Can a Residential Panel Meet 120% Busbar Limits for Sparq Systems: Q1200-4102 {240V}?

NEC 705.12(B)(3)(2) backfeed compliance table for Sparq Systems: Q1200-4102 {240V} at 240 V. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.

Evaluates Sparq Systems: Q1200-4102 {240V} (15 A required OCPD at 240 V) across standard distribution busbars.

| Panel Configuration | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **100A Bus / 100A Main** | 20 A | 15 A | PASS (120% Rule) |
| **150A Bus / 150A Main** | 30 A | 15 A | PASS (120% Rule) |
| **200A Bus / 200A Main** | 40 A | 15 A | PASS (120% Rule) |
| **200A Bus / 175A Main** | 65 A | 15 A | PASS (120% Rule) |
| **225A Bus / 200A Main** | 70 A | 15 A | PASS (120% Rule) |

## Which Competing Grid-Support Inverters Compare to Sparq Systems: Q1200-4102 {240V}?

Peer 240 V CEC inverters near 1,203 W AC output such as Altenergy Power System Inc: QS1 {240V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Altenergy Power System Inc: QS1 {240V}**](https://epri-peac.com/solar-equipment/inverters/altenergy-power-system-inc/altenergy-power-system-inc-qs1-240v/) Altenergy Power System Inc | 1,225 W | +22 W | 240.0 V | 48.0 V | 96.02% |
| [**Altenergy Power System Inc: QS1200 {240V}**](https://epri-peac.com/solar-equipment/inverters/altenergy-power-system-inc/altenergy-power-system-inc-qs1200-240v/) Altenergy Power System Inc | 1,225 W | +22 W | 240.0 V | 48.0 V | 96.02% |
| [**Altenergy Power System Inc: DS3-H {240V}**](https://epri-peac.com/solar-equipment/inverters/altenergy-power-system-inc/altenergy-power-system-inc-ds3-h-240v/) Altenergy Power System Inc | 1,068 W | -135 W | 240.0 V | 43.0 V | 96.73% |
| [**Anker Innovations Limited: MI80H {240V}**](https://epri-peac.com/solar-equipment/inverters/anker-innovations-limited/anker-innovations-limited-mi80h-240v/) Anker Innovations Limited | 1,068 W | -135 W | 240.0 V | 43.0 V | 96.73% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Sparq Systems: Q1200-4102 {240V}?

Check Sparq Systems: Q1200-4102 {240V} (1,203 W AC, 15 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Requires a 15 A breaker, passing directly inside a standard 200 A main / 200 A busbar panel (40 A limit).
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 38 V DC on Sparq Systems: Q1200-4102 {240V}.

### Sparq Systems: Q1200-4102 {240V} Panel & Wire Spec

Size 75 C copper conductors at 14 AWG Cu on a 15 A OCPD breaker (5.0 A continuous).

### Alternative Inverter Comparison

Compare efficiency (97.23%) and MPPT window (36-38 V) directly against Altenergy Power System Inc: QS1 {240V} (1,225 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Sparq Systems: Q1200-4102 {240V} by Sparq Systems covering breaker sizing, MPPT limits, and 240 V interconnection.

### What breaker and wire size does Sparq Systems: Q1200-4102 {240V} require?

At 1,203 W continuous AC (240 V), continuous current is 5.0 A; 125% NEC 690.8/705.12 sizing requires a 15 A breaker and 14 AWG Cu (75 C) wire.

### Does Sparq Systems: Q1200-4102 {240V} fit a 200 A main panel under the 120% busbar rule?

A 200 A busbar with a 200 A main allows 40 A of solar backfeed. Requiring 15 A at 240 V means PASS (120% Rule).

### How does Sparq Systems: Q1200-4102 {240V} compare to Altenergy Power System Inc: QS1 {240V}?

Sparq Systems: Q1200-4102 {240V} delivers 1,203 W AC at 97.23% CEC efficiency with a 38 V DC ceiling, while Altenergy Power System Inc: QS1 {240V} outputs 1,225 W at 240 V.

## Related Pages

Explore Sparq Systems hardware, Altenergy Power System Inc: QS1 {240V}, utility rates, and NEC 705.12 sizing calculators alongside Sparq Systems: Q1200-4102 {240V}.

[All Sparq Systems Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/sparq-systems/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)
