title: "SMA America: STP 33-US-41 {480V} Inverter (33,300W)"
url: https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-stp-33-us-41-480v/
description: "CEC specs for SMA America: STP 33-US-41 {480V}: 33,300W AC, 480V, 60A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# SMA America: STP 33-US-41 {480V} — CEC Inverter Specifications

Manufacturer: [**SMA America**](https://epri-peac.com/solar-equipment/brands/sma-america/) Registry: **CEC Verified Engineering Specification**

SMA America: STP 33-US-41 {480V} outputs 33,300 W AC at 480 V, 3-phase (40.1 A continuous, 60 A OCPD), ranking #522 of 2,343 CEC inverters at 97.57% efficiency with a 330-800 V MPPT window and 800 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 33,300 W

- **AC Voltage** : 480 V, 3-phase

- **Min PV Breaker** : 60 A (6 AWG Cu)

- **CEC Efficiency** : 97.57%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does SMA America: STP 33-US-41 {480V} Compare Against Peer CEC Listings?

How SMA America SMA America: STP 33-US-41 {480V} compares on 97.57% efficiency, MPPT span, and 120% busbar interconnection.

With a 330-800 V MPPT tracking band and 800 V DC ceiling, SMA America: STP 33-US-41 {480V} handles 33,300 W continuous AC (16,700 W below the 50,000 W 480 V median). Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap. Installers comparing SMA America against CSI Solar Co Ltd: CSI-33K-T480GL03-U {480V} (32,865 W) should verify whether listed since 2022-11-01 grid-support firmware meets local IEEE 1547 utility rules.

## Where Does SMA America: STP 33-US-41 {480V} Fall Across Listed CEC Models?

Position of SMA America: STP 33-US-41 {480V} (33,300 W AC) relative to the 7,680 W CEC median inverter.

## What Dataset Percentiles Define SMA America: STP 33-US-41 {480V}?

Percentile placement of SMA America: STP 33-US-41 {480V} across AC power class, conversion efficiency, and backfeed breaker size.

## What Do the Dataset Ranks Show for SMA America: STP 33-US-41 {480V}?

Primary electrical sizing limits, efficiency ranks, and NEC 705.12 / 690.7 thresholds for SMA America: STP 33-US-41 {480V}. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

Eff #522 / 2,343

### 97.57% CEC Weighted Efficiency

-0.45 pts vs the 98.02% 480 V median; overall power rank #533 (33,300 W, top 22.9%; higher than 77.1% of peers).

NEC 705.12 Check

### 60 A Required Backfeed OCPD

125% x 40.1 A = 50.1 A -> 60 A standard OCPD using 6 AWG Cu (75 C).

MPPT Window

### 330 V - 800 V (Max 800 V DC)

Tracking span of 470.0 V; listed since 2022-11-01 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### PASS (120% Commercial Busbar)

Evaluated for 480 V, 3-phase switchgear (200A Bus / 200A Main (480V) to 1,200A Bus / 1,200A Main (480V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 33300.0W / 480 V 3-phase -> 40.1 A | Breaker >= 1.25 * 40.1 = 50.1 A -> 60 A

CEC Inverters.csv for SMA America: STP 33-US-41 {480V}: Paco=33300.0 W, Vac=480 V, Vdcmax=800.0 V, Eff=97.57%.

**Result:** Min 60 A breaker & 6 AWG Cu (75 C); 1,200A Bus / 1,200A Main (480V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for SMA America: STP 33-US-41 {480V}?

Official California Energy Commission electrical test parameters, AC voltage, and DC limits for SMA America: STP 33-US-41 {480V}.

Official California Energy Commission (NREL SAM) test parameters for SMA America: STP 33-US-41 {480V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 33,300 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 480 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 800 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 330 V - 800 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 49.9722 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 97.57% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2022-11-01 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to SMA America: STP 33-US-41 {480V} (480 V, 3-phase)?

Check whether SMA America: STP 33-US-41 {480V} (60 A breaker) fits without main breaker derate or supply-side taps.

Evaluates SMA America: STP 33-US-41 {480V} (60 A required OCPD at 480 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (480V)** | 40 A | 60 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (480V)** | 80 A | 60 A | PASS (120% Commercial Busbar) |
| **600A Bus / 600A Main (480V)** | 120 A | 60 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (480V)** | 160 A | 60 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (480V)** | 240 A | 60 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With SMA America: STP 33-US-41 {480V}?

Verified cold-weather (-10 C) series module counts matched to SMA America: STP 33-US-41 {480V}'s 800 V DC ceiling.

Sampled CEC PV modules aligned within 330.0-800.0 V MPPT and 800.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 8 to 14 panels | 8.26 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 10 to 18 panels | 7.92 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 10 to 17 panels | 7.22 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 12 to 19 panels | 3.8 kW |

## Which Competing Grid-Support Inverters Compare to SMA America: STP 33-US-41 {480V}?

Alternative CEC inverters comparable to SMA America: STP 33-US-41 {480V}, including CSI Solar Co Ltd: CSI-33K-T480GL03-U {480V} (32,865 W) at 480 V, 3-phase.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**CSI Solar Co Ltd: CSI-33K-T480GL03-U {480V}**](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-33k-t480gl03-u-480v/) CSI Solar Co Ltd | 32,865 W | -435 W | 480.0 V | 850.0 V | 98.36% |
| [**CSI Solar Co Ltd: CSI-36K-T480GL03-U {480V}**](https://epri-peac.com/solar-equipment/inverters/csi-solar-co-ltd/csi-solar-co-ltd-csi-36k-t480gl03-u-480v/) CSI Solar Co Ltd | 35,866 W | +2566 W | 480.0 V | 850.0 V | 98.21% |
| [**Delta Electronics: M28U_120 {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-m28u-120-480v/) Delta Electronics | 30,709 W | -2591 W | 480.0 V | 830.0 V | 98.14% |
| [**Delta Electronics: M28U_121 {480V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-m28u-121-480v/) Delta Electronics | 30,709 W | -2591 W | 480.0 V | 830.0 V | 98.14% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for SMA America: STP 33-US-41 {480V}?

Check SMA America: STP 33-US-41 {480V} (33,300 W AC, 60 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 480 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (480V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 800 V DC on SMA America: STP 33-US-41 {480V}.

### SMA America: STP 33-US-41 {480V} Panel & Wire Spec

Size 75 C copper conductors at 6 AWG Cu on a 60 A OCPD breaker (40.1 A continuous).

### Alternative Inverter Comparison

Compare efficiency (97.57%) and MPPT window (330-800 V) directly against CSI Solar Co Ltd: CSI-33K-T480GL03-U {480V} (32,865 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for SMA America: STP 33-US-41 {480V} by SMA America covering breaker sizing, MPPT limits, and 480 V, 3-phase interconnection.

### What breaker and wire size does SMA America: STP 33-US-41 {480V} require?

At 33,300 W continuous AC (480 V, 3-phase), continuous current is 40.1 A; 125% NEC 690.8/705.12 sizing requires a 60 A breaker and 6 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does SMA America: STP 33-US-41 {480V} require?

At 33,300 W AC and 480 V, 3-phase, continuous line current is 40.1 A, requiring a 60 A OCPD and 1,200A Bus / 1,200A Main (480V) or NEC 705.11 interconnection.

### How does SMA America: STP 33-US-41 {480V} compare to CSI Solar Co Ltd: CSI-33K-T480GL03-U {480V}?

SMA America: STP 33-US-41 {480V} delivers 33,300 W AC at 97.57% CEC efficiency with a 800 V DC ceiling, while CSI Solar Co Ltd: CSI-33K-T480GL03-U {480V} outputs 32,865 W at 480 V, 3-phase.

## Related Pages

Explore SMA America hardware, CSI Solar Co Ltd: CSI-33K-T480GL03-U {480V}, utility rates, and NEC 705.12 sizing calculators alongside SMA America: STP 33-US-41 {480V}.

[All SMA America Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/sma-america/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From SMA America

- [All SMA America Specs](https://epri-peac.com/solar-equipment/brands/sma-america/)
- [SMA America: SC 4600 UP-US 690V 3850A {690V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4600-up-us-690v-3850a-690v/)
- [SMA America: SC 4400 UP-US 660V 3850A {660V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4400-up-us-660v-3850a-660v/)
- [SMA America: SC 4200 UP-US 630V 3850A {630V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4200-up-us-630v-3850a-630v/)
- [SMA America: SC 4000 UP-US 600V 3850A {600V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4000-up-us-600v-3850a-600v/)
- [SMA America: SC 3060 UP-US 690V 2566A {690V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-3060-up-us-690v-2566a-690v/)