title: "SMA America: SHP FLEX-US-21 {420V} Inverter (112,714W)"
url: https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-shp-flex-us-21-420v/
description: "CEC specs for SMA America: SHP FLEX-US-21 {420V}: 112,714W AC, 420V, 200A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# SMA America: SHP FLEX-US-21 {420V} — CEC Inverter Specifications

Manufacturer: [**SMA America**](https://epri-peac.com/solar-equipment/brands/sma-america/) Registry: **CEC Verified Engineering Specification**

SMA America: SHP FLEX-US-21 {420V} outputs 112,714 W AC at 420 V, 3-phase (154.9 A continuous, 200 A OCPD), ranking #318 of 2,343 CEC inverters at 98.05% efficiency with a 630-1,195 V MPPT window and 1,195 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 112,714 W

- **AC Voltage** : 420 V, 3-phase

- **Min PV Breaker** : 200 A (3/0 AWG Cu)

- **CEC Efficiency** : 98.05%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does SMA America: SHP FLEX-US-21 {420V} Compare Against Peer CEC Listings?

Breaker sizing (200 A), 3/0 AWG Cu wire rules, and DC input limits for SMA America: SHP FLEX-US-21 {420V}.

For NEC 705.12 solar interconnection, SMA America: SHP FLEX-US-21 {420V} outputs 154.9 A continuous AC at 420 V, 3-phase and needs a 200 A backfeed breaker on 3/0 AWG Cu (75 C). Commercial 420 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (420V) or NEC 705.11 supply-side tap. Conversion efficiency scores 98.05% (#318 of 2,343, +1.23 pts vs overall CEC median).

## Where Does SMA America: SHP FLEX-US-21 {420V} Fall Across Listed CEC Models?

Output power comparison showing where SMA America: SHP FLEX-US-21 {420V} sits among all 2,343 CEC-listed grid-support inverters. Use these verified dataset benchmarks alongside a licensed electrician load calculation to compare residential upgrade bids with confidence.

## What Dataset Percentiles Define SMA America: SHP FLEX-US-21 {420V}?

Relative ranking of SMA America: SHP FLEX-US-21 {420V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

## What Do the Dataset Ranks Show for SMA America: SHP FLEX-US-21 {420V}?

Snapshot of SMA America: SHP FLEX-US-21 {420V} efficiency rank (#318), OCPD breaker size, MPPT span, and busbar verdict.

Eff #318 / 2,343

### 98.05% CEC Weighted Efficiency

+0.28 pts vs the 97.77% 420 V median; overall power rank #324 (112,714 W, top 13.8%; higher than 86.2% of peers).

NEC 705.12 Check

### 200 A Required Backfeed OCPD

125% x 154.9 A = 193.6 A -> 200 A standard OCPD using 3/0 AWG Cu (75 C).

MPPT Window

### 630 V - 1,195 V (Max 1,195 V DC)

Tracking span of 565.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 420 V, 3-phase switchgear (200A Bus / 200A Main (420V) to 1,200A Bus / 1,200A Main (420V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 112714.0W / 420 V 3-phase -> 154.9 A | Breaker >= 1.25 * 154.9 = 193.6 A -> 200 A

CEC Inverters.csv for SMA America: SHP FLEX-US-21 {420V}: Paco=112714.0 W, Vac=420 V, Vdcmax=1195.0 V, Eff=98.05%.

**Result:** Min 200 A breaker & 3/0 AWG Cu (75 C); 1,200A Bus / 1,200A Main (420V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for SMA America: SHP FLEX-US-21 {420V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SMA America: SHP FLEX-US-21 {420V}. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.

Official California Energy Commission (NREL SAM) test parameters for SMA America: SHP FLEX-US-21 {420V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 112,714 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 420 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,195 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 630 V - 1,195 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 147.375 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 98.05% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to SMA America: SHP FLEX-US-21 {420V} (420 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for SMA America: SHP FLEX-US-21 {420V} at 420 V, 3-phase.

Evaluates SMA America: SHP FLEX-US-21 {420V} (200 A required OCPD at 420 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (420V)** | 40 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (420V)** | 80 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (420V)** | 120 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (420V)** | 160 A | 200 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (420V)** | 240 A | 200 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With SMA America: SHP FLEX-US-21 {420V}?

Minimum and maximum series solar module strings fitting SMA America: SHP FLEX-US-21 {420V} MPPT and 1,195 V limits.

Sampled CEC PV modules aligned within 630.0-1195.0 V MPPT and 1195.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 15 to 21 panels | 12.39 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 19 to 28 panels | 12.32 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 19 to 26 panels | 11.05 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 22 to 29 panels | 5.8 kW |

## Which Competing Grid-Support Inverters Compare to SMA America: SHP FLEX-US-21 {420V}?

Peer 420 V, 3-phase CEC inverters near 112,714 W AC output such as Yaskawa Solectria Solar: PVI-100TL-480 {480V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**Yaskawa Solectria Solar: PVI-100TL-480 {480V}**](https://epri-peac.com/solar-equipment/inverters/yaskawa-solectria-solar/yaskawa-solectria-solar-pvi-100tl-480-480v/) Yaskawa Solectria Solar | 100,000 W | -12714 W | 480.0 V | 850.0 V | 98.06% |
| [**JingTsing Technology Ltd: JTES-PCS125K-1000/480-L03C1 {480V}**](https://epri-peac.com/solar-equipment/inverters/jingtsing-technology-ltd/jingtsing-technology-ltd-jtes-pcs125k-1000-480-l03c1-480v/) JingTsing Technology Ltd | 127,819 W | +15105 W | 480.0 V | 950.0 V | 98.0% |
| [**Ginlong Technologies Co Ltd: S5-GC90K-US {480V}**](https://epri-peac.com/solar-equipment/inverters/ginlong-technologies-co-ltd/ginlong-technologies-co-ltd-s5-gc90k-us-480v/) Ginlong Technologies Co Ltd | 89,449 W | -23265 W | 480.0 V | 850.0 V | 97.99% |
| [**LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V}**](https://epri-peac.com/solar-equipment/inverters/ls-energy-solutions-llc/ls-energy-solutions-llc-pbe-6140-r61-1a0-1000-600v/) LS Energy Solutions LLC | 139,449 W | +26735 W | 600.0 V | 1350.0 V | 98.27% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for SMA America: SHP FLEX-US-21 {420V}?

Check SMA America: SHP FLEX-US-21 {420V} (112,714 W AC, 200 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 420 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (420V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,195 V DC on SMA America: SHP FLEX-US-21 {420V}.

### SMA America: SHP FLEX-US-21 {420V} Panel & Wire Spec

Size 75 C copper conductors at 3/0 AWG Cu on a 200 A OCPD breaker (154.9 A continuous).

### Alternative Inverter Comparison

Compare efficiency (98.05%) and MPPT window (630-1,195 V) directly against Yaskawa Solectria Solar: PVI-100TL-480 {480V} (100,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for SMA America: SHP FLEX-US-21 {420V} by SMA America covering breaker sizing, MPPT limits, and 420 V, 3-phase interconnection.

### What breaker and wire size does SMA America: SHP FLEX-US-21 {420V} require?

At 112,714 W continuous AC (420 V, 3-phase), continuous current is 154.9 A; 125% NEC 690.8/705.12 sizing requires a 200 A breaker and 3/0 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does SMA America: SHP FLEX-US-21 {420V} require?

At 112,714 W AC and 420 V, 3-phase, continuous line current is 154.9 A, requiring a 200 A OCPD and 1,200A Bus / 1,200A Main (420V) or NEC 705.11 interconnection.

### How does SMA America: SHP FLEX-US-21 {420V} compare to Yaskawa Solectria Solar: PVI-100TL-480 {480V}?

SMA America: SHP FLEX-US-21 {420V} delivers 112,714 W AC at 98.05% CEC efficiency with a 1,195 V DC ceiling, while Yaskawa Solectria Solar: PVI-100TL-480 {480V} outputs 100,000 W at 420 V, 3-phase.

## Related Pages

Explore SMA America hardware, Yaskawa Solectria Solar: PVI-100TL-480 {480V}, utility rates, and NEC 705.12 sizing calculators alongside SMA America: SHP FLEX-US-21 {420V}.

[All SMA America Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/sma-america/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From SMA America

- [All SMA America Specs](https://epri-peac.com/solar-equipment/brands/sma-america/)
- [SMA America: SC 4600 UP-US 690V 3850A {690V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4600-up-us-690v-3850a-690v/)
- [SMA America: SC 4400 UP-US 660V 3850A {660V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4400-up-us-660v-3850a-660v/)
- [SMA America: SC 4200 UP-US 630V 3850A {630V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4200-up-us-630v-3850a-630v/)
- [SMA America: SC 4000 UP-US 600V 3850A {600V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4000-up-us-600v-3850a-600v/)