title: "SMA America: SC 2750-EV-US {600V} Inverter (2,600,000W)"
url: https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-2750-ev-us-600v/
description: "CEC specs for SMA America: SC 2750-EV-US {600V}: 2,600,000W AC, 600V, 3150A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# SMA America: SC 2750-EV-US {600V} — CEC Inverter Specifications

Manufacturer: [**SMA America**](https://epri-peac.com/solar-equipment/brands/sma-america/) Registry: **CEC Verified Engineering Specification**

SMA America: SC 2750-EV-US {600V} outputs 2,600,000 W AC at 600 V, 3-phase (2501.9 A continuous, 3,150 A OCPD), ranking #868 of 2,343 CEC inverters at 97.12% efficiency with a 875-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 2,600,000 W

- **AC Voltage** : 600 V, 3-phase

- **Min PV Breaker** : 3,150 A (parallel Cu feeders)

- **CEC Efficiency** : 97.12%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does SMA America: SC 2750-EV-US {600V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 600 V, 3-phase grid-support overview for SMA America: SC 2750-EV-US {600V}.

Rated at 2,600,000 W AC (2501.9 A continuous), SMA America: SC 2750-EV-US {600V} ranks #868 of 2,343 CEC units at 97.12% efficiency (-1.16 pts vs the 98.28% 600 V median). Minimum 75 C copper conductor sizing for its 3,150 A circuit is parallel Cu feeders per NEC Table 310.16. Cold-weather string Voc must remain under 1,200 V DC at record local winter lows.

## Where Does SMA America: SC 2750-EV-US {600V} Fall Across Listed CEC Models?

Marks SMA America: SC 2750-EV-US {600V} (2,600,000 W AC) across the California Energy Commission inverter AC capacity distribution.

## What Dataset Percentiles Define SMA America: SC 2750-EV-US {600V}?

Benchmarks SMA America: SC 2750-EV-US {600V} continuous AC output, 97.12% CEC weighted efficiency, and 3,150 A OCPD breaker demand.

## What Do the Dataset Ranks Show for SMA America: SC 2750-EV-US {600V}?

Four key NEC 705.12 and California Energy Commission metrics defining SMA America: SC 2750-EV-US {600V} by SMA America.

Eff #868 / 2,343

### 97.12% CEC Weighted Efficiency

-1.16 pts vs the 98.28% 600 V median; overall power rank #72 (2,600,000 W, top 3.1%; higher than 96.9% of peers).

NEC 705.12 Check

### 3,150 A Required Backfeed OCPD

125% x 2501.9 A = 3127.4 A -> 3,150 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 875 V - 1,200 V (Max 1,200 V DC)

Tracking span of 325.0 V; listed since 2019-02-15 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 600 V, 3-phase switchgear (200A Bus / 200A Main (600V) to 1,200A Bus / 1,200A Main (600V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 2600000.0W / 600 V 3-phase -> 2501.9 A | Breaker >= 1.25 * 2501.9 = 3127.4 A -> 3,150 A

CEC Inverters.csv for SMA America: SC 2750-EV-US {600V}: Paco=2600000.0 W, Vac=600 V, Vdcmax=1200.0 V, Eff=97.12%.

**Result:** Min 3,150 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (600V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for SMA America: SC 2750-EV-US {600V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for SMA America: SC 2750-EV-US {600V}.

Official California Energy Commission (NREL SAM) test parameters for SMA America: SC 2750-EV-US {600V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 2,600,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 600 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 875 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 2797.28 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 97.12% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2019-02-15 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to SMA America: SC 2750-EV-US {600V} (600 V, 3-phase)?

Evaluates SMA America: SC 2750-EV-US {600V} (3,150 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates SMA America: SC 2750-EV-US {600V} (3150 A required OCPD at 600 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (600V)** | 40 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (600V)** | 80 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (600V)** | 120 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (600V)** | 160 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (600V)** | 240 A | 3,150 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which CEC PV Module Strings Pair With SMA America: SC 2750-EV-US {600V}?

Sample PV string lengths aligned within 875-1,200 V MPPT and 1,200 V DC max at -10 C. Compare thermal ratings, overcurrent protection caps, and continuous load headroom carefully before expanding an existing home service panel.

Sampled CEC PV modules aligned within 875.0-1200.0 V MPPT and 1200.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 21 panels (fixed) | 12.39 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 27 to 28 panels | 12.32 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 26 panels (fixed) | 11.05 kW |
| [**Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515**](https://epri-peac.com/solar-equipment/modules/chint-new-energy-technology-co-ltd/chint-new-energy-technology-co-ltd-chsm72m-dg-f-bh-515/) | 515.0 W | 53.76 V | 22 panels (fixed) | 11.33 kW |

## Which Competing Grid-Support Inverters Compare to SMA America: SC 2750-EV-US {600V}?

Competing CEC grid-support inverters near 2,600,000 W AC and 600 V, 3-phase, led by INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3930TL U HV C600 {600V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3930TL U HV C600 {600V}**](https://epri-peac.com/solar-equipment/inverters/ingeteam-power-technology-sa/ingeteam-power-technology-sa-ingecon-sun-storage-3930tl-u-hv-c600-600v/) INGETEAM POWER TECHNOLOGY SA | 2,582,000 W | -18000 W | 600.0 V | 1500.0 V | 97.65% |
| [**Power Electronics: FS2600CU15O3 {600V}**](https://epri-peac.com/solar-equipment/inverters/power-electronics/power-electronics-fs2600cu15o3-600v/) Power Electronics | 2,770,200 W | +170200 W | 600.0 V | 1200.0 V | 97.85% |
| [**Power Electronics: FS2250CU15O3 {600V}**](https://epri-peac.com/solar-equipment/inverters/power-electronics/power-electronics-fs2250cu15o3-600v/) Power Electronics | 2,420,370 W | -179630 W | 600.0 V | 1200.0 V | 97.82% |
| [**Power Electronics: FS2225CU15 {600V}**](https://epri-peac.com/solar-equipment/inverters/power-electronics/power-electronics-fs2225cu15-600v/) Power Electronics | 2,417,080 W | -182920 W | 600.0 V | 1200.0 V | 97.76% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for SMA America: SC 2750-EV-US {600V}?

Check SMA America: SC 2750-EV-US {600V} (2,600,000 W AC, 3,150 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 600 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (600V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on SMA America: SC 2750-EV-US {600V}.

### SMA America: SC 2750-EV-US {600V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 3,150 A OCPD breaker (2501.9 A continuous).

### Alternative Inverter Comparison

Compare efficiency (97.12%) and MPPT window (875-1,200 V) directly against INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3930TL U HV C600 {600V} (2,582,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for SMA America: SC 2750-EV-US {600V} by SMA America covering breaker sizing, MPPT limits, and 600 V, 3-phase interconnection.

### What breaker and wire size does SMA America: SC 2750-EV-US {600V} require?

At 2,600,000 W continuous AC (600 V, 3-phase), continuous current is 2501.9 A; 125% NEC 690.8/705.12 sizing requires a 3,150 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does SMA America: SC 2750-EV-US {600V} require?

At 2,600,000 W AC and 600 V, 3-phase, continuous line current is 2501.9 A, requiring a 3,150 A OCPD and 1,200A Bus / 1,200A Main (600V) or NEC 705.11 interconnection.

### How does SMA America: SC 2750-EV-US {600V} compare to INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3930TL U HV C600 {600V}?

SMA America: SC 2750-EV-US {600V} delivers 2,600,000 W AC at 97.12% CEC efficiency with a 1,200 V DC ceiling, while INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3930TL U HV C600 {600V} outputs 2,582,000 W at 600 V, 3-phase.

## Related Pages

Explore SMA America hardware, INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3930TL U HV C600 {600V}, utility rates, and NEC 705.12 sizing calculators alongside SMA America: SC 2750-EV-US {600V}.

[All SMA America Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/sma-america/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From SMA America

- [All SMA America Specs](https://epri-peac.com/solar-equipment/brands/sma-america/)
- [SMA America: SC 4600 UP-US 690V 3850A {690V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4600-up-us-690v-3850a-690v/)
- [SMA America: SC 4400 UP-US 660V 3850A {660V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4400-up-us-660v-3850a-660v/)
- [SMA America: SC 4200 UP-US 630V 3850A {630V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4200-up-us-630v-3850a-630v/)
- [SMA America: SC 4000 UP-US 600V 3850A {600V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4000-up-us-600v-3850a-600v/)
- [SMA America: SC 3060 UP-US 690V 2566A {690V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-3060-up-us-690v-2566a-690v/)