title: "SMA America: SB50-1SP-US-41 {208V} Inverter (5,000W)"
url: https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sb50-1sp-us-41-208v/
description: "CEC specs for SMA America: SB50-1SP-US-41 {208V}: 5,000W AC, 208V, 30A OCPD, and NEC 705.12 checks. Verified US government and CEC engineering data."
---

CEC Grid-Support Inverter

# SMA America: SB50-1SP-US-41 {208V} — CEC Inverter Specifications

Manufacturer: [**SMA America**](https://epri-peac.com/solar-equipment/brands/sma-america/) Registry: **CEC Verified Engineering Specification**

SMA America: SB50-1SP-US-41 {208V} outputs 5,000 W AC at 208 V, commercial single-phase (24.0 A continuous, 30 A OCPD), ranking #1,430 of 2,343 CEC inverters at 96.57% efficiency with a 220-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 5,000 W

- **AC Voltage** : 208 V, commercial single-phase

- **Min PV Breaker** : 30 A (10 AWG Cu)

- **CEC Efficiency** : 96.57%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does SMA America: SB50-1SP-US-41 {208V} Compare Against Peer CEC Listings?

NEC 705.12 breaker requirements, efficiency placement, and 208 V, commercial single-phase grid-support overview for SMA America: SB50-1SP-US-41 {208V}.

Rated at 5,000 W AC (24.0 A continuous), SMA America: SB50-1SP-US-41 {208V} ranks #1,430 of 2,343 CEC units at 96.57% efficiency (+0.16 pts vs the 96.41% 208 V median). Minimum 75 C copper conductor sizing for its 30 A circuit is 10 AWG Cu per NEC Table 310.16. Cold-weather string Voc must remain under 480 V DC at record local winter lows.

## Where Does SMA America: SB50-1SP-US-41 {208V} Fall Across Listed CEC Models?

Marks SMA America: SB50-1SP-US-41 {208V} (5,000 W AC) across the California Energy Commission inverter AC capacity distribution. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

## What Dataset Percentiles Define SMA America: SB50-1SP-US-41 {208V}?

Benchmarks SMA America: SB50-1SP-US-41 {208V} continuous AC output, 96.57% CEC weighted efficiency, and 30 A OCPD breaker demand.

## What Do the Dataset Ranks Show for SMA America: SB50-1SP-US-41 {208V}?

Four key NEC 705.12 and California Energy Commission metrics defining SMA America: SB50-1SP-US-41 {208V} by SMA America. Cross-check local Authority Having Jurisdiction amendments and serving utility net-metering terms before finalizing project sizing.

Eff #1,430 / 2,343

### 96.57% CEC Weighted Efficiency

+0.16 pts vs the 96.41% 208 V median; overall power rank #1,516 (5,000 W, below CEC median; higher than 33.9% of peers).

NEC 705.12 Check

### 30 A Required Backfeed OCPD

125% x 24.0 A = 30.0 A -> 30 A standard OCPD using 10 AWG Cu (75 C).

MPPT Window

### 220 V - 480 V (Max 480 V DC)

Tracking span of 260.0 V; listed since 2020-01-21 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### PASS (120% Commercial Busbar)

Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 5000.0W / 208 V -> 24.0 A | Breaker >= 1.25 * 24.0 = 30.0 A -> 30 A

CEC Inverters.csv for SMA America: SB50-1SP-US-41 {208V}: Paco=5000.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=96.57%.

**Result:** Min 30 A breaker & 10 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for SMA America: SB50-1SP-US-41 {208V}?

Official laboratory CEC ratings, MPPT operating window, and DC voltage bounds recorded for SMA America: SB50-1SP-US-41 {208V}. Review related calculators, peer benchmarks, and source citations below to validate design assumptions for your electrical service.

Official California Energy Commission (NREL SAM) test parameters for SMA America: SB50-1SP-US-41 {208V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 5,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 220 V - 480 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 14.1857 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 96.57% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2020-01-21 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to SMA America: SB50-1SP-US-41 {208V} (208 V, commercial single-phase)?

Evaluates SMA America: SB50-1SP-US-41 {208V} (30 A OCPD) across standard 100 A to 225 A busbars or commercial switchboards.

Evaluates SMA America: SB50-1SP-US-41 {208V} (30 A required OCPD at 208 V, commercial single-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (208V)** | 40 A | 30 A | PASS (120% Commercial Busbar) |
| **400A Bus / 400A Main (208V)** | 80 A | 30 A | PASS (120% Commercial Busbar) |
| **600A Bus / 600A Main (208V)** | 120 A | 30 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (208V)** | 160 A | 30 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (208V)** | 240 A | 30 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With SMA America: SB50-1SP-US-41 {208V}?

Sample PV string lengths aligned within 220-480 V MPPT and 480 V DC max at -10 C. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

Sampled CEC PV modules aligned within 220.0-480.0 V MPPT and 480.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 6 to 8 panels | 4.72 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 7 to 11 panels | 4.84 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 7 to 10 panels | 4.25 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 8 to 11 panels | 2.2 kW |

## Which Competing Grid-Support Inverters Compare to SMA America: SB50-1SP-US-41 {208V}?

Competing CEC grid-support inverters near 5,000 W AC and 208 V, commercial single-phase, led by ABB: PVI-5000-OUTD-US-A {208V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**ABB: PVI-5000-OUTD-US-A {208V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvi-5000-outd-us-a-208v/) ABB | 5,000 W | Tie (0 W) | 208.0 V | 480.0 V | 96.0% |
| [**ABB: PVI-5000-OUTD-US-Z-A {208V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvi-5000-outd-us-z-a-208v/) ABB | 5,000 W | Tie (0 W) | 208.0 V | 480.0 V | 96.0% |
| [**ABB: PVI-5000-OUTD-US-Z-M-A {208V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvi-5000-outd-us-z-m-a-208v/) ABB | 5,000 W | Tie (0 W) | 208.0 V | 480.0 V | 96.0% |
| [**Delta Electronics: E6-TL-US(AC) {208V}**](https://epri-peac.com/solar-equipment/inverters/delta-electronics/delta-electronics-e6-tl-us-ac-208v/) Delta Electronics | 5,000 W | Tie (0 W) | 208.0 V | 480.0 V | 97.6% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for SMA America: SB50-1SP-US-41 {208V}?

Check SMA America: SB50-1SP-US-41 {208V} (5,000 W AC, 30 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on SMA America: SB50-1SP-US-41 {208V}.

### SMA America: SB50-1SP-US-41 {208V} Panel & Wire Spec

Size 75 C copper conductors at 10 AWG Cu on a 30 A OCPD breaker (24.0 A continuous).

### Alternative Inverter Comparison

Compare efficiency (96.57%) and MPPT window (220-480 V) directly against ABB: PVI-5000-OUTD-US-A {208V} (5,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for SMA America: SB50-1SP-US-41 {208V} by SMA America covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.

### What breaker and wire size does SMA America: SB50-1SP-US-41 {208V} require?

At 5,000 W continuous AC (208 V, commercial single-phase), continuous current is 24.0 A; 125% NEC 690.8/705.12 sizing requires a 30 A breaker and 10 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does SMA America: SB50-1SP-US-41 {208V} require?

At 5,000 W AC and 208 V, commercial single-phase, continuous line current is 24.0 A, requiring a 30 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

### How does SMA America: SB50-1SP-US-41 {208V} compare to ABB: PVI-5000-OUTD-US-A {208V}?

SMA America: SB50-1SP-US-41 {208V} delivers 5,000 W AC at 96.57% CEC efficiency with a 480 V DC ceiling, while ABB: PVI-5000-OUTD-US-A {208V} outputs 5,000 W at 208 V, commercial single-phase.

## Related Pages

Explore SMA America hardware, ABB: PVI-5000-OUTD-US-A {208V}, utility rates, and NEC 705.12 sizing calculators alongside SMA America: SB50-1SP-US-41 {208V}.

[All SMA America Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/sma-america/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From SMA America

- [All SMA America Specs](https://epri-peac.com/solar-equipment/brands/sma-america/)
- [SMA America: SC 4600 UP-US 690V 3850A {690V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4600-up-us-690v-3850a-690v/)
- [SMA America: SC 4400 UP-US 660V 3850A {660V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4400-up-us-660v-3850a-660v/)
- [SMA America: SC 4200 UP-US 630V 3850A {630V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4200-up-us-630v-3850a-630v/)
- [SMA America: SC 4000 UP-US 600V 3850A {600V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4000-up-us-600v-3850a-600v/)
- [SMA America: SC 3060 UP-US 690V 2566A {690V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-3060-up-us-690v-2566a-690v/)