CEC Grid-Support Inverter

# SMA America: SB30-1SP-US-41 {208V} — CEC Inverter Specifications

Manufacturer: [**SMA America**](https://epri-peac.com/solar-equipment/brands/sma-america/) Registry: **CEC Verified Engineering Specification**

SMA America: SB30-1SP-US-41 {208V} outputs 3,000 W AC at 208 V, commercial single-phase (14.4 A continuous, 20 A OCPD), ranking #1,412 of 2,343 CEC inverters at 96.59% efficiency with a 155-480 V MPPT window and 480 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 3,000 W

- **AC Voltage** : 208 V, commercial single-phase

- **Min PV Breaker** : 20 A (12 AWG Cu)

- **CEC Efficiency** : 96.59%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does SMA America: SB30-1SP-US-41 {208V} Compare Against Peer CEC Listings?

Breaker sizing (20 A), 12 AWG Cu wire rules, and DC input limits for SMA America: SB30-1SP-US-41 {208V}.

For NEC 705.12 solar interconnection, SMA America: SB30-1SP-US-41 {208V} outputs 14.4 A continuous AC at 208 V, commercial single-phase and needs a 20 A backfeed breaker on 12 AWG Cu (75 C). Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap. Conversion efficiency scores 96.59% (#1,412 of 2,343, -0.23 pts vs overall CEC median).

## Where Does SMA America: SB30-1SP-US-41 {208V} Fall Across Listed CEC Models?

Output power comparison showing where SMA America: SB30-1SP-US-41 {208V} sits among all 2,343 CEC-listed grid-support inverters. Regional housing vintage, storm hazard frequency, and wholesale utility prices directly govern residential upgrade payback across jurisdictions.

## What Dataset Percentiles Define SMA America: SB30-1SP-US-41 {208V}?

Relative ranking of SMA America: SB30-1SP-US-41 {208V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

## What Do the Dataset Ranks Show for SMA America: SB30-1SP-US-41 {208V}?

Snapshot of SMA America: SB30-1SP-US-41 {208V} efficiency rank (#1,412), OCPD breaker size, MPPT span, and busbar verdict. Data intervals combine current 2025 federal utility and BLS wage releases with verified state electrical board rosters.

Eff #1,412 / 2,343

### 96.59% CEC Weighted Efficiency

+0.18 pts vs the 96.41% 208 V median; overall power rank #1,729 (3,000 W, below CEC median; higher than 25.3% of peers).

NEC 705.12 Check

### 20 A Required Backfeed OCPD

125% x 14.4 A = 18.0 A -> 20 A standard OCPD using 12 AWG Cu (75 C).

MPPT Window

### 155 V - 480 V (Max 480 V DC)

Tracking span of 325.0 V; listed since 2020-01-21 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### PASS (120% Commercial Busbar)

Evaluated for 208 V, commercial single-phase switchgear (200A Bus / 200A Main (208V) to 1,200A Bus / 1,200A Main (208V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 3000.0W / 208 V -> 14.4 A | Breaker >= 1.25 * 14.4 = 18.0 A -> 20 A

CEC Inverters.csv for SMA America: SB30-1SP-US-41 {208V}: Paco=3000.0 W, Vac=208 V, Vdcmax=480.0 V, Eff=96.59%.

**Result:** Min 20 A breaker & 12 AWG Cu (75 C); 1,200A Bus / 1,200A Main (208V): PASS (120% Commercial Busbar).

## What Are the Published CEC Specifications for SMA America: SB30-1SP-US-41 {208V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for SMA America: SB30-1SP-US-41 {208V}. Homeowners and permit reviewers can filter tables below to benchmark specific ratings, wiring ages, and code allowances side by side.

Official California Energy Commission (NREL SAM) test parameters for SMA America: SB30-1SP-US-41 {208V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 3,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 208 V, commercial single-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 480 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 155 V - 480 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 8.50949 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 96.59% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2020-01-21 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to SMA America: SB30-1SP-US-41 {208V} (208 V, commercial single-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for SMA America: SB30-1SP-US-41 {208V} at 208 V, commercial single-phase.

Evaluates SMA America: SB30-1SP-US-41 {208V} (20 A required OCPD at 208 V, commercial single-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (208V)** | 40 A | 20 A | PASS (120% Commercial Busbar) |
| **400A Bus / 400A Main (208V)** | 80 A | 20 A | PASS (120% Commercial Busbar) |
| **600A Bus / 600A Main (208V)** | 120 A | 20 A | PASS (120% Commercial Busbar) |
| **800A Bus / 800A Main (208V)** | 160 A | 20 A | PASS (120% Commercial Busbar) |
| **1,200A Bus / 1,200A Main (208V)** | 240 A | 20 A | PASS (120% Commercial Busbar) |

## Which CEC PV Module Strings Pair With SMA America: SB30-1SP-US-41 {208V}?

Minimum and maximum series solar module strings fitting SMA America: SB30-1SP-US-41 {208V} MPPT and 480 V limits. Published percentiles compare local state, county, metro, and certified equipment metrics against nationwide residential electrical baselines.

Sampled CEC PV modules aligned within 155.0-480.0 V MPPT and 480.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 4 to 8 panels | 4.72 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 5 to 11 panels | 4.84 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 5 to 10 panels | 4.25 kW |
| [**CSI Solar Co Ltd CS6P-200P**](https://epri-peac.com/solar-equipment/modules/csi-solar-co-ltd/csi-solar-co-ltd-cs6p-200p/) | 200.0 W | 40.6 V | 6 to 11 panels | 2.2 kW |

## Which Competing Grid-Support Inverters Compare to SMA America: SB30-1SP-US-41 {208V}?

Peer 208 V, commercial single-phase CEC inverters near 3,000 W AC output such as ABB: PVI-30-OUTD-S-US-A {208V}. Always verify current state NEC adoption cycles, local utility interconnection tariffs, and panel busbar ratings before pulling project permits.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**ABB: PVI-30-OUTD-S-US-A {208V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvi-30-outd-s-us-a-208v/) ABB | 3,000 W | Tie (0 W) | 208.0 V | 480.0 V | 95.47% |
| [**ABB: PVI-30-OUTD-S-US-Z-A {208V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvi-30-outd-s-us-z-a-208v/) ABB | 3,000 W | Tie (0 W) | 208.0 V | 480.0 V | 95.47% |
| [**ABB: PVI-30-OUTD-S-US-Z-M-A {208V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvi-30-outd-s-us-z-m-a-208v/) ABB | 3,000 W | Tie (0 W) | 208.0 V | 480.0 V | 95.47% |
| [**ABB: UNO-DM-33-TL-PLUS-US-SB-RA {208V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-uno-dm-33-tl-plus-us-sb-ra-208v/) ABB | 3,000 W | Tie (0 W) | 208.0 V | 480.0 V | 95.8% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for SMA America: SB30-1SP-US-41 {208V}?

Check SMA America: SB30-1SP-US-41 {208V} (3,000 W AC, 20 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 208 V, commercial single-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (208V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 480 V DC on SMA America: SB30-1SP-US-41 {208V}.

### SMA America: SB30-1SP-US-41 {208V} Panel & Wire Spec

Size 75 C copper conductors at 12 AWG Cu on a 20 A OCPD breaker (14.4 A continuous).

### Alternative Inverter Comparison

Compare efficiency (96.59%) and MPPT window (155-480 V) directly against ABB: PVI-30-OUTD-S-US-A {208V} (3,000 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for SMA America: SB30-1SP-US-41 {208V} by SMA America covering breaker sizing, MPPT limits, and 208 V, commercial single-phase interconnection.

### What breaker and wire size does SMA America: SB30-1SP-US-41 {208V} require?

At 3,000 W continuous AC (208 V, commercial single-phase), continuous current is 14.4 A; 125% NEC 690.8/705.12 sizing requires a 20 A breaker and 12 AWG Cu (75 C) wire.

### What commercial switchgear or feeder sizing does SMA America: SB30-1SP-US-41 {208V} require?

At 3,000 W AC and 208 V, commercial single-phase, continuous line current is 14.4 A, requiring a 20 A OCPD and 1,200A Bus / 1,200A Main (208V) or NEC 705.11 interconnection.

### How does SMA America: SB30-1SP-US-41 {208V} compare to ABB: PVI-30-OUTD-S-US-A {208V}?

SMA America: SB30-1SP-US-41 {208V} delivers 3,000 W AC at 96.59% CEC efficiency with a 480 V DC ceiling, while ABB: PVI-30-OUTD-S-US-A {208V} outputs 3,000 W at 208 V, commercial single-phase.

## Related Pages

Explore SMA America hardware, ABB: PVI-30-OUTD-S-US-A {208V}, utility rates, and NEC 705.12 sizing calculators alongside SMA America: SB30-1SP-US-41 {208V}.

[All SMA America Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/sma-america/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From SMA America

- [All SMA America Specs](https://epri-peac.com/solar-equipment/brands/sma-america/)
- [SMA America: SC 4600 UP-US 690V 3850A {690V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4600-up-us-690v-3850a-690v/)
- [SMA America: SC 4400 UP-US 660V 3850A {660V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4400-up-us-660v-3850a-660v/)
- [SMA America: SC 4200 UP-US 630V 3850A {630V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4200-up-us-630v-3850a-630v/)
- [SMA America: SC 4000 UP-US 600V 3850A {600V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-4000-up-us-600v-3850a-600v/)
- [SMA America: SC 3060 UP-US 690V 2566A {690V}](https://epri-peac.com/solar-equipment/inverters/sma-america/sma-america-sc-3060-up-us-690v-2566a-690v/)