title: "Shenzhen Sinexcel Electric Co Inverter (shenzhen-sinex)"
url: https://epri-peac.com/solar-equipment/inverters/shenzhen-sinexcel-electric-co-ltd/shenzhen-sinexcel-electric-co-ltd-pws1-500ktl-na-8m1-400v/
description: "CEC specs for Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}: 498,340W AC, 400V, 900A OCPD, and NEC 705.12 checks."
---

CEC Grid-Support Inverter

# Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} — CEC Inverter Specifications

Manufacturer: [**Shenzhen Sinexcel Electric Co Ltd**](https://epri-peac.com/solar-equipment/brands/shenzhen-sinexcel-electric-co-ltd/) Registry: **CEC Verified Engineering Specification**

Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} outputs 498,340 W AC at 400 V, 3-phase (719.3 A continuous, 900 A OCPD), ranking #1,816 of 2,343 CEC inverters at 96.25% efficiency with a 640-900 V MPPT window and 900 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 498,340 W

- **AC Voltage** : 400 V, 3-phase

- **Min PV Breaker** : 900 A (parallel Cu feeders)

- **CEC Efficiency** : 96.25%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} Compare Against Peer CEC Listings?

Breaker sizing (900 A), parallel Cu feeders wire rules, and DC input limits for Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}.

Classified as a grid-tied PV inverter (active in CEC directory), Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} requires 899.1 A design capacity -> 900 A breaker using parallel Cu feeders copper at 75 C terminals. Weighted efficiency sits at 96.25% (-0.57 pts vs overall CEC median) across 2,343 CEC models, while commercial 400 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (400v) or nec 705.11 supply-side tap.

## Where Does Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} Fall Across Listed CEC Models?

Output power comparison showing where Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} sits among all 2,343 CEC-listed grid-support inverters.

## What Dataset Percentiles Define Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}?

Relative ranking of Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

## What Do the Dataset Ranks Show for Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}?

Snapshot of Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} efficiency rank (#1,816), OCPD breaker size, MPPT span, and busbar verdict.

Eff #1,816 / 2,343

### 96.25% CEC Weighted Efficiency

-0.56 pts vs the 96.81% 400 V median; overall power rank #200 (498,340 W, top 8.6%; higher than 91.4% of peers).

NEC 705.12 Check

### 900 A Required Backfeed OCPD

125% x 719.3 A = 899.1 A -> 900 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 640 V - 900 V (Max 900 V DC)

Tracking span of 260.0 V; active in CEC directory (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 400 V, 3-phase switchgear (200A Bus / 200A Main (400V) to 1,200A Bus / 1,200A Main (400V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 498340.0W / 400 V 3-phase -> 719.3 A | Breaker >= 1.25 * 719.3 = 899.1 A -> 900 A

CEC Inverters.csv for Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}: Paco=498340.0 W, Vac=400 V, Vdcmax=900.0 V, Eff=96.25%.

**Result:** Min 900 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (400V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}.

Official California Energy Commission (NREL SAM) test parameters for Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 498,340 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 400 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 900 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 640 V - 900 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 690.319 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 96.25% | Calculated AC/DC conversion ratio from CEC test protocol |
| **Inverter Topology** | Hybrid: No (Grid-Tied PV) | CEC Solar Equipment List grid-support certification |

## What Switchgear Limits Apply to Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} (400 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} at 400 V, 3-phase.

Evaluates Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} (900 A required OCPD at 400 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (400V)** | 40 A | 900 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (400V)** | 80 A | 900 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (400V)** | 120 A | 900 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (400V)** | 160 A | 900 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (400V)** | 240 A | 900 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which CEC PV Module Strings Pair With Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}?

Minimum and maximum series solar module strings fitting Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} MPPT and 900 V limits.

Sampled CEC PV modules aligned within 640.0-900.0 V MPPT and 900.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 15 to 16 panels | 9.44 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 20 to 21 panels | 9.24 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 19 to 20 panels | 8.5 kW |
| [**Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515**](https://epri-peac.com/solar-equipment/modules/chint-new-energy-technology-co-ltd/chint-new-energy-technology-co-ltd-chsm72m-dg-f-bh-515/) | 515.0 W | 53.76 V | 16 panels (fixed) | 8.24 kW |

## Which Competing Grid-Support Inverters Compare to Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}?

Peer 400 V, 3-phase CEC inverters near 498,340 W AC output such as EPC Power Corp: 50-200100 {720V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**EPC Power Corp: 50-200100 {720V}**](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-200100-720v/) EPC Power Corp | 561,806 W | +63466 W | 720.0 V | 1500.0 V | 98.58% |
| [**ABB: PVS-175-TL-POWER-MODULE-1-US {800V}**](https://epri-peac.com/solar-equipment/inverters/abb/abb-pvs-175-tl-power-module-1-us-800v/) ABB | 179,574 W | -318766 W | 800.0 V | 1200.0 V | 97.39% |
| [**LS Energy Solutions LLC: PBE-6140-R61-1A0-1000 {600V}**](https://epri-peac.com/solar-equipment/inverters/ls-energy-solutions-llc/ls-energy-solutions-llc-pbe-6140-r61-1a0-1000-600v/) LS Energy Solutions LLC | 139,449 W | -358891 W | 600.0 V | 1350.0 V | 98.27% |
| [**JingTsing Technology Ltd: JTES-PCS125K-1000/480-L03C1 {480V}**](https://epri-peac.com/solar-equipment/inverters/jingtsing-technology-ltd/jingtsing-technology-ltd-jtes-pcs125k-1000-480-l03c1-480v/) JingTsing Technology Ltd | 127,819 W | -370521 W | 480.0 V | 950.0 V | 98.0% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}?

Check Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} (498,340 W AC, 900 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 400 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (400V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 900 V DC on Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}.

### Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 900 A OCPD breaker (719.3 A continuous).

### Alternative Inverter Comparison

Compare efficiency (96.25%) and MPPT window (640-900 V) directly against EPC Power Corp: 50-200100 {720V} (561,806 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} by Shenzhen Sinexcel Electric Co Ltd covering breaker sizing, MPPT limits, and 400 V, 3-phase interconnection.

### What breaker and wire size does Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} require?

At 498,340 W continuous AC (400 V, 3-phase), continuous current is 719.3 A; 125% NEC 690.8/705.12 sizing requires a 900 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} require?

At 498,340 W AC and 400 V, 3-phase, continuous line current is 719.3 A, requiring a 900 A OCPD and 1,200A Bus / 1,200A Main (400V) or NEC 705.11 interconnection.

### How does Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} compare to EPC Power Corp: 50-200100 {720V}?

Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V} delivers 498,340 W AC at 96.25% CEC efficiency with a 900 V DC ceiling, while EPC Power Corp: 50-200100 {720V} outputs 561,806 W at 400 V, 3-phase.

## Related Pages

Explore Shenzhen Sinexcel Electric Co Ltd hardware, EPC Power Corp: 50-200100 {720V}, utility rates, and NEC 705.12 sizing calculators alongside Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M1 {400V}.

[All Shenzhen Sinexcel Electric Co Ltd Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/shenzhen-sinexcel-electric-co-ltd/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Shenzhen Sinexcel Electric Co Ltd

- [All Shenzhen Sinexcel Electric Co Ltd Specs](https://epri-peac.com/solar-equipment/brands/shenzhen-sinexcel-electric-co-ltd/)
- [Shenzhen Sinexcel Electric Co Ltd: PWS1-1725KTL-H-NA-8M8 {690V}](https://epri-peac.com/solar-equipment/inverters/shenzhen-sinexcel-electric-co-ltd/shenzhen-sinexcel-electric-co-ltd-pws1-1725ktl-h-na-8m8-690v/)
- [Shenzhen Sinexcel Electric Co Ltd: PWS1-1725KTL-H-NA-8M1 {690V}](https://epri-peac.com/solar-equipment/inverters/shenzhen-sinexcel-electric-co-ltd/shenzhen-sinexcel-electric-co-ltd-pws1-1725ktl-h-na-8m1-690v/)
- [Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA-8M8 {400V}](https://epri-peac.com/solar-equipment/inverters/shenzhen-sinexcel-electric-co-ltd/shenzhen-sinexcel-electric-co-ltd-pws1-500ktl-na-8m8-400v/)
- [Shenzhen Sinexcel Electric Co Ltd: PWS1-500KTL-NA {400V}](https://epri-peac.com/solar-equipment/inverters/shenzhen-sinexcel-electric-co-ltd/shenzhen-sinexcel-electric-co-ltd-pws1-500ktl-na-400v/)
- [Shenzhen Sinexcel Electric Co Ltd: PWS1-250K-NA {480V}](https://epri-peac.com/solar-equipment/inverters/shenzhen-sinexcel-electric-co-ltd/shenzhen-sinexcel-electric-co-ltd-pws1-250k-na-480v/)