title: "Schneider Electric USA Inc Inverter (1,800,000W)"
url: https://epri-peac.com/solar-equipment/inverters/schneider-electric-usa-inc/schneider-electric-usa-inc-cs1800-na-575v/
description: "CEC specs for Schneider Electric USA Inc: CS1800-NA {575V}: 1,800,000W AC, 575V, 2300A OCPD, and NEC 705.12 checks. Source-verified US engineering data."
---

CEC Grid-Support Inverter

# Schneider Electric USA Inc: CS1800-NA {575V} — CEC Inverter Specifications

Manufacturer: [**Schneider Electric USA Inc**](https://epri-peac.com/solar-equipment/brands/schneider-electric-usa-inc/) Registry: **CEC Verified Engineering Specification**

Schneider Electric USA Inc: CS1800-NA {575V} outputs 1,800,000 W AC at 575 V, 3-phase (1807.4 A continuous, 2,300 A OCPD), ranking #576 of 2,343 CEC inverters at 97.43% efficiency with a 856-1,200 V MPPT window and 1,200 V DC limit. All figures reconcile directly against federal energy archives, state electrical licensing boards, California Energy Commission datasheets, and National Electrical Code engineering constants.

- **AC Output (Paco)** : 1,800,000 W

- **AC Voltage** : 575 V, 3-phase

- **Min PV Breaker** : 2,300 A (parallel Cu feeders)

- **CEC Efficiency** : 97.43%

Wall-mounted residential hybrid solar inverter and modular battery cabinet piped with galvanized EMT conduit

## How Does Schneider Electric USA Inc: CS1800-NA {575V} Compare Against Peer CEC Listings?

Breaker sizing (2,300 A), parallel Cu feeders wire rules, and DC input limits for Schneider Electric USA Inc: CS1800-NA {575V}.

Classified as a grid-tied PV inverter (listed since 2024-04-02), Schneider Electric USA Inc: CS1800-NA {575V} requires 2259.2 A design capacity -> 2,300 A breaker using parallel Cu feeders copper at 75 C terminals. Weighted efficiency sits at 97.43% (+0.61 pts vs overall CEC median) across 2,343 CEC models, while commercial 575 v, 3-phase switchgear interconnection uses 1,200a bus / 1,200a main (575v) or nec 705.11 supply-side tap.

## Where Does Schneider Electric USA Inc: CS1800-NA {575V} Fall Across Listed CEC Models?

Output power comparison showing where Schneider Electric USA Inc: CS1800-NA {575V} sits among all 2,343 CEC-listed grid-support inverters.

## What Dataset Percentiles Define Schneider Electric USA Inc: CS1800-NA {575V}?

Relative ranking of Schneider Electric USA Inc: CS1800-NA {575V} on continuous AC power, CEC weighted efficiency, and OCPD breaker current.

## What Do the Dataset Ranks Show for Schneider Electric USA Inc: CS1800-NA {575V}?

Snapshot of Schneider Electric USA Inc: CS1800-NA {575V} efficiency rank (#576), OCPD breaker size, MPPT span, and busbar verdict.

Eff #576 / 2,343

### 97.43% CEC Weighted Efficiency

-0.11 pts vs the 97.54% 575 V median; overall power rank #109 (1,800,000 W, top 4.7%; higher than 95.3% of peers).

NEC 705.12 Check

### 2,300 A Required Backfeed OCPD

125% x 1807.4 A = 2259.2 A -> 2,300 A standard OCPD using parallel Cu feeders (75 C).

MPPT Window

### 856 V - 1,200 V (Max 1,200 V DC)

Tracking span of 344.0 V; listed since 2024-04-02 (grid-tied PV inverter).

Commercial / 3-Phase Fit

### Supply-Side Tap (705.11) / Dedicated Switchboard

Evaluated for 575 V, 3-phase switchgear (200A Bus / 200A Main (575V) to 1,200A Bus / 1,200A Main (575V)) under NEC 705.12 / 705.11.

NEC 705.12 Backfeed OCPD & 120% Busbar Formula

I_cont = 1800000.0W / 575 V 3-phase -> 1807.4 A | Breaker >= 1.25 * 1807.4 = 2259.2 A -> 2,300 A

CEC Inverters.csv for Schneider Electric USA Inc: CS1800-NA {575V}: Paco=1800000.0 W, Vac=575 V, Vdcmax=1200.0 V, Eff=97.43%.

**Result:** Min 2,300 A breaker & parallel Cu feeders (75 C); 1,200A Bus / 1,200A Main (575V): Supply-Side Tap (705.11) / Dedicated Switchboard.

## What Are the Published CEC Specifications for Schneider Electric USA Inc: CS1800-NA {575V}?

Complete California Energy Commission grid-support inverter ratings and hybrid battery capabilities for Schneider Electric USA Inc: CS1800-NA {575V}.

Official California Energy Commission (NREL SAM) test parameters for Schneider Electric USA Inc: CS1800-NA {575V}.

| Parameter | Measured / Listed Value | Engineering Significance |
|---|---|---|
| **Max Continuous AC Power (Paco)** | 1,800,000 W | Determines required backfeed OCPD size via 125% continuous rule |
| **Nominal AC Voltage (Vac)** | 575 V, 3-phase | 240V split-phase residential vs. 208V/480V/MV commercial |
| **Max DC Input Voltage (Vdcmax)** | 1,200 V | Hard ceiling for cold-weather PV string Voc under NEC 690.7 |
| **MPPT Operating Range** | 856 V - 1,200 V | Optimal DC string Vmp window for full power harvest |
| **Max Input DC Current (Idcmax)** | 1804.16 A | Used to verify parallel string combiner limits |
| **CEC Weighted Efficiency** | 97.43% | Calculated AC/DC conversion ratio from CEC test protocol |
| **CEC Listing Date & Hybrid** | 2024-04-02 / Hybrid: No (Grid-Tied PV) | Utility interconnection approval metadata |

## What Switchgear Limits Apply to Schneider Electric USA Inc: CS1800-NA {575V} (575 V, 3-phase)?

NEC 705.12(B)(3)(2) backfeed compliance table for Schneider Electric USA Inc: CS1800-NA {575V} at 575 V, 3-phase.

Evaluates Schneider Electric USA Inc: CS1800-NA {575V} (2300 A required OCPD at 575 V, 3-phase) across standard distribution busbars.

| Switchboard / Interconnect | 120% Max Backfeed | Required PV OCPD | Compliance Verdict |
|---|---|---|---|
| **200A Bus / 200A Main (575V)** | 40 A | 2,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **400A Bus / 400A Main (575V)** | 80 A | 2,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **600A Bus / 600A Main (575V)** | 120 A | 2,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **800A Bus / 800A Main (575V)** | 160 A | 2,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |
| **1,200A Bus / 1,200A Main (575V)** | 240 A | 2,300 A | Supply-Side Tap (705.11) / Dedicated Switchboard |

## Which CEC PV Module Strings Pair With Schneider Electric USA Inc: CS1800-NA {575V}?

Minimum and maximum series solar module strings fitting Schneider Electric USA Inc: CS1800-NA {575V} MPPT and 1,200 V limits.

Sampled CEC PV modules aligned within 856.0-1200.0 V MPPT and 1200.0 V max DC at -10 C.

| CEC Module | STC (W) | -10 C Voc | Valid String Range | Max String DC |
|---|---|---|---|---|
| [**AXITEC AC-590TGB/144TS**](https://epri-peac.com/solar-equipment/modules/axitec/axitec-ac-590tgb-144ts/) | 590.0 W | 56.24 V | 20 to 21 panels | 12.39 kW |
| [**Aptos Solar Technology LLC DNA-108-MFN10-440W**](https://epri-peac.com/solar-equipment/modules/aptos-solar-technology-llc/aptos-solar-technology-llc-dna-108-mfn10-440w/) | 440.0 W | 42.15 V | 26 to 28 panels | 12.32 kW |
| [**Boviet Solar Technology Co Ltd BVM7610M-425-H-HC-BF**](https://epri-peac.com/solar-equipment/modules/boviet-solar-technology-co-ltd/boviet-solar-technology-co-ltd-bvm7610m-425-h-hc-bf/) | 425.0 W | 44.75 V | 25 to 26 panels | 11.05 kW |
| [**Chint New Energy Technology Co Ltd CHSM72M(DG)/F-BH-515**](https://epri-peac.com/solar-equipment/modules/chint-new-energy-technology-co-ltd/chint-new-energy-technology-co-ltd-chsm72m-dg-f-bh-515/) | 515.0 W | 53.76 V | 21 to 22 panels | 11.33 kW |

## Which Competing Grid-Support Inverters Compare to Schneider Electric USA Inc: CS1800-NA {575V}?

Peer 575 V, 3-phase CEC inverters near 1,800,000 W AC output such as SINENG ELECTRIC CO LTD: EH-1725-HA-UD-US {690V}.

Alternative CEC inverters at comparable AC output power and voltage class.

| Alternative Inverter | AC Output | Delta | Vac | Max DC | CEC Eff |
|---|---|---|---|---|---|
| [**SINENG ELECTRIC CO LTD: EH-1725-HA-UD-US {690V}**](https://epri-peac.com/solar-equipment/inverters/sineng-electric-co-ltd/sineng-electric-co-ltd-eh-1725-ha-ud-us-690v/) SINENG ELECTRIC CO LTD | 1,726,700 W | -73300 W | 690.0 V | 1500.0 V | 98.32% |
| [**Power Electronics: FS2250CU15O3 {600V}**](https://epri-peac.com/solar-equipment/inverters/power-electronics/power-electronics-fs2250cu15o3-600v/) Power Electronics | 2,420,370 W | +620370 W | 600.0 V | 1200.0 V | 97.82% |
| [**INGETEAM POWER TECHNOLOGY SA: INGECON SUN STORAGE 3660TL U C480 {480V}**](https://epri-peac.com/solar-equipment/inverters/ingeteam-power-technology-sa/ingeteam-power-technology-sa-ingecon-sun-storage-3660tl-u-c480-480v/) INGETEAM POWER TECHNOLOGY SA | 2,467,620 W | +667620 W | 480.0 V | 1300.0 V | 96.63% |
| [**EPC Power Corp: 50-200100 {720V}**](https://epri-peac.com/solar-equipment/inverters/epc-power-corp/epc-power-corp-50-200100-720v/) EPC Power Corp | 561,806 W | -1238194 W | 720.0 V | 1500.0 V | 98.58% |

What to Check & Best-Fit Scenarios

## What Are the Interconnection Limits and Best-Fit Uses for Schneider Electric USA Inc: CS1800-NA {575V}?

Check Schneider Electric USA Inc: CS1800-NA {575V} (1,800,000 W AC, 2,300 A OCPD) against your main panel busbar, winter string Voc, and IEEE 1547 outage rules.

- Anti-islanding shutdown: grid-tied inverters shut off within 2 seconds during blackouts under IEEE 1547 unless paired with a battery microgrid interconnect.
- Busbar 120% limit: Commercial 575 V, 3-phase switchgear interconnection uses 1,200A Bus / 1,200A Main (575V) or NEC 705.11 supply-side tap.
- Cold Voc hard ceiling: never allow winter open-circuit PV string voltage to exceed 1,200 V DC on Schneider Electric USA Inc: CS1800-NA {575V}.

### Schneider Electric USA Inc: CS1800-NA {575V} Panel & Wire Spec

Size 75 C copper conductors at parallel Cu feeders on a 2,300 A OCPD breaker (1807.4 A continuous).

### Alternative Inverter Comparison

Compare efficiency (97.43%) and MPPT window (856-1,200 V) directly against SINENG ELECTRIC CO LTD: EH-1725-HA-UD-US {690V} (1,726,700 W).

## Which Homeowner Electrical & Solar Questions Come Up Most Often?

Answers for Schneider Electric USA Inc: CS1800-NA {575V} by Schneider Electric USA Inc covering breaker sizing, MPPT limits, and 575 V, 3-phase interconnection.

### What breaker and wire size does Schneider Electric USA Inc: CS1800-NA {575V} require?

At 1,800,000 W continuous AC (575 V, 3-phase), continuous current is 1807.4 A; 125% NEC 690.8/705.12 sizing requires a 2,300 A breaker and parallel Cu feeders (75 C) wire.

### What commercial switchgear or feeder sizing does Schneider Electric USA Inc: CS1800-NA {575V} require?

At 1,800,000 W AC and 575 V, 3-phase, continuous line current is 1807.4 A, requiring a 2,300 A OCPD and 1,200A Bus / 1,200A Main (575V) or NEC 705.11 interconnection.

### How does Schneider Electric USA Inc: CS1800-NA {575V} compare to SINENG ELECTRIC CO LTD: EH-1725-HA-UD-US {690V}?

Schneider Electric USA Inc: CS1800-NA {575V} delivers 1,800,000 W AC at 97.43% CEC efficiency with a 1,200 V DC ceiling, while SINENG ELECTRIC CO LTD: EH-1725-HA-UD-US {690V} outputs 1,726,700 W at 575 V, 3-phase.

## Related Pages

Explore Schneider Electric USA Inc hardware, SINENG ELECTRIC CO LTD: EH-1725-HA-UD-US {690V}, utility rates, and NEC 705.12 sizing calculators alongside Schneider Electric USA Inc: CS1800-NA {575V}.

[All Schneider Electric USA Inc Certified Solar Hardware](https://epri-peac.com/solar-equipment/brands/schneider-electric-usa-inc/) [Browse All CEC Solar Modules & Inverters](https://epri-peac.com/solar-equipment/) [Check NEC 705.12 120% Busbar Capacity Calculator](https://epri-peac.com/tools/solar-busbar-120/) [Run NEC 690.7 Cold-Temp PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/)

## Sources

1. [CEC Solar Equipment List — Grid-Support Inverters (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Inverters.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
2. [CEC Solar Equipment List — PV Modules (NREL SAM Distribution)](https://raw.githubusercontent.com/NREL/SAM/develop/deploy/libraries/CEC%20Modules.csv) — California Energy Commission / NREL SAM, 2026-Q4 SAM Develop (retrieved 2026-11-23)
3. [NFPA 70 National Electrical Code (Section Numbers & Standard Engineering Tables Only)](https://www.nfpa.org/codes-and-standards/nfpa-70-standard-development/70) — National Fire Protection Association (NFPA), 2020 / 2023 / 2026 Editions (retrieved 2026-11-23)

Spec Sheet Sections

- Dataset Ranks & Thresholds
- CEC Electrical Table
- Alternative Peers
- Engineering FAQ
- Official Sources

Interactive NEC Tools

Run custom cold-temp string Voc or 120% panel busbar checks for this hardware.
[PV String Voc Calculator](https://epri-peac.com/tools/pv-string-voc/) [120% Busbar Checker](https://epri-peac.com/tools/solar-busbar-120/)

More From Schneider Electric USA Inc

- [All Schneider Electric USA Inc Specs](https://epri-peac.com/solar-equipment/brands/schneider-electric-usa-inc/)
- [Schneider Electric USA Inc: CS2200-NA {600V}](https://epri-peac.com/solar-equipment/inverters/schneider-electric-usa-inc/schneider-electric-usa-inc-cs2200-na-600v/)
- [Schneider Electric USA Inc: CS2000-NA {575V}](https://epri-peac.com/solar-equipment/inverters/schneider-electric-usa-inc/schneider-electric-usa-inc-cs2000-na-575v/)
- [Schneider Electric USA Inc: CS1666-1-NA {575V}](https://epri-peac.com/solar-equipment/inverters/schneider-electric-usa-inc/schneider-electric-usa-inc-cs1666-1-na-575v/)
- [Schneider Electric USA Inc: CS1666-2-NA {575V}](https://epri-peac.com/solar-equipment/inverters/schneider-electric-usa-inc/schneider-electric-usa-inc-cs1666-2-na-575v/)
- [Schneider Electric USA Inc: CS1666-3-NA {575V}](https://epri-peac.com/solar-equipment/inverters/schneider-electric-usa-inc/schneider-electric-usa-inc-cs1666-3-na-575v/)